LX coil for D range contactors

Spare Coils

Catalogue Number: LX4D7EW
LX coil for D range contactors
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LX4D7
Control circuit type
DC wide range
[Uc] control circuit voltage
48 V DC
Average resistance
94.2 Ohm at 20 °C
Inductance of closed circuit
7 H
Product compatibility
LC1D80
Mechanical durability
10 Mcycles
Maximum operating rate
3600 cyc/h 60 °C
Coil technology
without built-in suppressor module
Control circuit voltage limits
  • drop-out: 0.1...0.3 Uc (at <55 °C)
  • operational: 0.75...1.2 Uc (at <55 °C)
    • Time constant
      75 ms
      Inrush power in W
      22-22 W (at 20 °C)
      Hold-in power consumption in W
      22-22 W at 20 °C
      Ambient air temperature for operation
      -5-60 °C
      Net weight
      0.68 kg
      Sustainable offer status
      Green Premium product
      REACh Regulation
      Free of Substances of Very High Concern above the threshold
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP060301EN
      Circularity Profile
      ENVEOLI100405
      WEEE
      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
      California proposition 65
      WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
      Warranty
      18 months

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Technical Data Catalogues

      • Product Environmental

      Frequently Asked Questions

      hide show

      What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

      Issue:
      AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

      Product Line:
      Tesys D Replacement Parts

      Environment:
      TeSys™ D AC Coils

      Resolution:

      What do the LA4D timing modules require for mounting on LC1D40A through LC1D65A contactors?

      Product Line:
       
      Tesys D line Contactors and Accessories

      Resolution:
       
      Mounting this module to TeSys LC1D40A through LC1D65A contactor requires the use of the LAD4BB3 wiring adaptor. This adaptor can be fitted only to contactors with no coil suppressor.