LX coil for D range contactors

Spare Coils

Catalogue Number: LX4D7CW
LX coil for D range contactors
Retail
$900.90
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LX4D7
Control circuit type
DC wide range
[Uc] control circuit voltage
36 V DC
Average resistance
51.9 Ohm at 20 °C
Inductance of closed circuit
4.18 H
Product compatibility
LC1D80
Mechanical durability
10 Mcycles
Maximum operating rate
3600 cyc/h 60 °C
Coil technology
without built-in suppressor module
Control circuit voltage limits
  • drop-out: 0.1...0.3 Uc (at <55 °C)
  • operational: 0.75...1.2 Uc (at <55 °C)
    • Time constant
      75 ms
      Inrush power in W
      22-22 W (at 20 °C)
      Hold-in power consumption in W
      22-22 W at 20 °C
      Ambient air temperature for operation
      -5-60 °C
      Net weight
      0.68 kg
      Unit Type of Package 1
      PCE
      Number of Units in Package 1
      1
      Package 1 Weight
      680 g
      Package 1 Height
      9 cm
      Package 1 width
      11.5 cm
      Package 1 Length
      14.5 cm
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      California proposition 65
      WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
      Warranty
      18 months

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Technical Data Catalogues

      Frequently Asked Questions

      hide show

      Will a LAD4RCE or LA4DRCU also fit a LC2D09 thru LC2D38 reversing contactors?

      Issue:
      Identifying accessories for reversing contactors

      Product Line:
      IEC contactors and starters

      Environment:
      Products sold and used in the United States

      Cause:
      Accessories used on non-reversing contactors are also needed for reversing application

      Resolution:
      Yes, the LC2D contactors are provided standard with one on the left contactor. One may be added to the right contactor.


      CTA-ID : 2022733

      What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

      Issue:
      AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

      Product Line:
      Tesys D Replacement Parts

      Environment:
      TeSys™ D AC Coils

      Resolution: