LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors

Spare Coils

Catalogue Number: LX1D8N5
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LX1D8
Control circuit type
AC at 50 Hz
[Uc] control circuit voltage
415 V AC 50 Hz
Average resistance
368.43 Ohm at 20 °C
Inductance of closed circuit
27.65 H
Product compatibility
LC1D115
Mechanical durability
8 Mcycles
Maximum operating rate
2400 cyc/h 60 °C
Coil technology
without built-in suppressor module
Control circuit voltage limits
  • drop-out: 0.3...0.6 Uc at 50 Hz (at <55 °C)
  • operational: 0.85...1.1 Uc at 50 Hz (at <55 °C)
    • Inrush power in VA
      300-300 VA 50 Hz cos phi 0.8 (at 20 °C)
      Hold-in power consumption in VA
      22-22 VA 50 Hz cos phi 0.3 (at 20 °C)
      Heat dissipation
      3-8 W at 50 Hz
      Ambient air temperature for operation
      -5-60 °C
      Net weight
      0.26 kg
      Warranty
      18 months

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Technical Data Catalogues

      • End of Life Manual

      • Product Environmental

      Frequently Asked Questions

      hide show

      What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

      Issue:
      AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

      Product Line:
      Tesys D Replacement Parts

      Environment:
      TeSys™ D AC Coils

      Resolution:

      Is 240 volt replacement control coil available for LC1D11500?

      Issue:
      Identifying replacement coil part number

      Product Line:
      IEC contactors and starters

      Environment:
      Products sold and used in the United States

      Cause:
      Replacement control coil needed for older style Tesys Contactor

      Resolution:
      Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


      CTA-ID : 11321

      What is the 240v coil to fit an LC1D1506

       The 240v coil is an LX1D8U7

      spare 415VAC coil for LC1D80 Contactor ?

      Code = LX1D6N7

      What is the replacement for LC1D115 with LX1D6G7 coil?

      The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

      LC1D1156F7
      TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

      For more information see:
      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

      What is the altitude derating for a TeSys D-Line contactor?

      Issue:​
      What is the altitude derating for a TeSys D-Line contactor?

      Product Line:
      Digest 177 Section 18 : Contactors and Starters, IEC

      Environment:
      North American Products

      Resolution:
      The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

      Voltage
      3500m x 0.90
      4000m x 0.80
      4500m x 0.70
      5000m x 0.60

      Current
      3500m x 0.92
      4000m x 0.90
      4500m x 0.88
      5000m x 0.86

      For example, an LC1D80 at 5000 meters:
      - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
      - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



       

      What is the 240V coil needed for a LC1D80008 contactor

       The coil is a LX1D6U7

      What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

      Issue:
      Identifying maximum voltage of an LC1D contactor

      Product Line:
      TeSys D Contactors

      Environment:
      IEC contactors and starters used in North America

      Cause:
      n/a

      Resolution:
      IThe maximum voltage per UL and CSA is 600VAC. 
       

      What is the difference between LC1DT25 and LC1D25

       LC1DT25 is 4 pole and LC1D25 is 3 pole

      Contactor LE1D18N7 does it come with overload ?

       No - Overloads can be ordered separatly depending on the current rating required
       

      What is the part number for replacement contacts for the LC1D115 contactor??

      The part number for replacement contacts for the LC1D115 contactor is - LA5D1158031
      For further information on this part go to link below:-

      https://www.schneider-electric.com.au/en/search/LA5D1158031

      Are the D-Line contactors rated to break DC voltages?

      Issue: 
      Can the TeSys D line be used to control DC loads? 

      Product Line:
      Tesys D contactors

      Environment:
      Products sold and used in the United States
       
      Cause:
       DC power circuit
       
      Resolution:
       
      Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

      Devices are suitable but not UL Listed for DC applications.

      More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


       

      What code is a mechanical interlock for the 4pole LC1D1150046 contactor?

      LA9D11502 will fit the 4p LC1D115 and LC1D150 contactors

      What is the part number for a DOL starter for 7.5kW load with 415VAC coil and overload for 16amps?

      The part number for a DOL starter for 7.5kW load with overload for 16amps is - LE1D18N7 & LRD21

      For further information , visit link below:-
      https://www.schneider-electric.com.au/en/search/LE1D18N7
      https://www.schneider-electric.com.au/en/search/LRD21
       

      What is the color scheme of the Tesys D-Line contactors?

      Issue:
      Looking for different color scheme of the Tesys D-Line contactors.

      Product Line:
      Tesys D Contactors

      Environment:
      LC1D contactors

      Resolution:
      Beige and dark gray.
       

      What is the 480V coil for a CA2DN31T6 IEC Relay?

      Issue:
      What is the 480V coil for a CA2DN31T6 IEC Relay?

      Product Line:
      Tesys Relays

      Environment:
      Obsolete relays

      Cause:
      Product selection

      Resolution:
      The LX1D2T6 coil is obsolete. Replace the contactor with the new TeSys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.


      CTA-ID : 2048217

      Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

      ISSUE
      Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?
      PRODUCT LINE
      Auxiliary contacts for the Tesys D line
      ENVIRONMENT
      Tesys D-Line and Tesys F
      CAUSE
      Fit
      RESOLUTION
      These contacts will only fit on the following contactors:
      Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
      Left side mount only to LC1F contactors
      CTA-ID : 2002751

      Are the LC1D115 and LC1D150 contactors din rail mountable?

      Issue: 
      LC1D115 and D150 mounting

      Product Line:
       Tesys D contactors

      Environment:
      Products sold and used in the United States
       
      Cause:
      Din rail mounting desired for large D line contactor
       
      Resolution:
       
      Yes, they use 2-35mm din rails


       

      What is the mechanical interlock for the LC1D115 contactor?

      Issue:
      Interlock needed for a pair of LC1D115 contactors

      Product Line:
      NEMA combination starters

      Environment:
      Products sold and used in the United States

      Cause:
      Application requires mechanical interlocking

      Resolution:
      LA9D11502. It includes the electrical interlocks.

       

      What are the stand alone short circuit current ratings on the LC1D** contactors?

      Issue:
      Tesys D SCCR

      Product Line:
      Contactors and Overload Relays

      Environment:
      TeSys™ D Contactors and Overload Relays
       
      Resolution:
      The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

      They are as follows:
      Horsepower SCCR (A)

      0 thru 1 1,000
      1 thru 50 5,000
      51 thru 200 10,000
      201 thru 400 18,000
      401 thru 600 30,000
      601 thru 900 42,000
      901 thru 1600 85,000
      1601+ 100,000

      What is the part code for terminal shrouds to fit LC1D115 or LC1D150

      The part code is LA9D115703 for 3 pole
      The part code for 4 pole is LA9D115704

      What is the reference for the separate mounting kit for LRD4369 overload relay

      The LRD43xx type of thermal overload relays are directly mounted to the contactors LC1D115 & LC1D150 only. There is no separate mounting kit for the LRD43xx.

      If a separate mounting is required for the contactors LC1D115 or LC1D150 type, then LRD336xx shall be selected as these range of overload relays have indepentdent mounting and have similar setting range and are of Class 10A.

      What is the difference between LC1D115 and LC1D1156?

      The 6 in LC1D1156.. is that the 6 denotes lug bar terminals. Use LC1D115.. for cable connections.


       

      Which rectifier is required for the LX9F*917 48V coil?

      Issue:
      Which rectifier is required for the LX9F*917 48V coil?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      For the LX9FJ917, LX9FK917, and LX9FL917 48V coils, use rectifier part number: DR5TF4V

      Which rectifier is required for the LX9F*925 110V coil?

      Issue:
      Which rectifier is required for the LX9F*925 110V coil?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      For the LX9FJ925, LX9FK925, and LX9FL925 110V coils, use rectifier part number: DR5TF4U

      Which rectifier is required for the LX9F*925 120V coil?

      Issue:
      Which rectifier is required for the LX9F*925 120V coil?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      For the LX9FJ925, LX9FK925, and LX9FL925 120V coils, use rectifier part number: DR5TF4U

      Which rectifier is required for the LX9F*931 220V coil?

      Issue:
      Which rectifier is required for the LX9F*931 220V coil?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      For the LX9FJ931, LX9FK931, and LX9FL931 220V coils, use rectifier part number: DR5TF4U

      What terminal protection shrouds fit the LR9F5*57 overload relays?

      Issue:
      What terminal protection shrouds fit the LR9F5*57 overload relays?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      The LA9F701 protection shrouds fit the LR9F5357 and the LR9F5557 overload relays.

      What terminal protection shrouds fit the LR9F5*71 overload relays?

      Issue:
      What terminal protection shrouds fit the LR9F5*71 overload relays?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      The LA9F705 protection shrouds fit the LR9F5*71 overload relays

      What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

      Issue:
      Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

      Product Line:
      NEMA combination starters

      Environment:
      Products sold and used in the United States

      Resolution:
      For contactors with screw clamp terminals:
      stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
      stranded cable w/cable end: One or Two #18-10 AWG per terminal.
      solid cable: One or Two #18-8 AWG per terminal.

      On the TeSys D-Line contactor with AC coils, which are the coil terminals?

      Issue:
      Identifying the coil terminals for an LC1D TeSys D-Line contactor.

      Product Line:
      D Line contactors.

      Environment:
      Products sold in the United States.

      Cause:
      Product features.

      Resolution:
      The coil terminals are labelled A1 and A2.

      What is the difference between LA9D11569 and LA9D115691?

      Issue:
      Identifying differences between two part numbers

      Product Line:
      IEC contactors and starters

      Environment:
      Products sold and used in the United States

      Cause:
      Selecting between two similar part numbers

      Resolution:
      LA9D11569 is a set of power connections. LA9D115691 is the bottom connector only as shown on page 16-9 of Digest 173 for the LC1D115 and LC1D150 contactor.


       

      What is the suggested shorting contactor part number for an ATS48C14Y?

      Issue:
      What is the suggested shorting contactor part number for an ATS48C14Y?

      Product Line:
      Altistart 48 , ATS48

      Environment:
      ATS48C11Y , ATS48C14Y 

      Cause:
      Custom enclosure

      Resolutin:
      LC1D115 G7  (120vac coil control voltage )

      Which rectifier is required for the LX9F*936 380V and 415V coils?

      Issue:
      Which rectifier is required for the LX9F*936 380V and 415V coils?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      For the LX9FJ936, LX9FK936, and LX9FL936 380V and 415V coils, use rectifier part number: DR5TF4S

      What resistor is required for the LX9FJ replacement coils?

      Issue:
      What resistor is required for the LX9FJ replacement coils?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:

      LX9FJ918 48V coil uses resistor DR2SC0047

      LX9FJ926 110V coil uses resistor DR2SC0030

      LX9FJ927 125V coil uses resistor DR2SC0390

      LX9FJ932 220V coil uses resistor DR2SC1200

      The LX9FJ938 coils are no longer available.

      What resistor is required for the LX9FK replacement coils?

      Issue:
      What resistor is required for the LX9FK replacement coils?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:

      LX9FK918 48V coil uses resistor DR2SC0039

      LX9FK926 110V coil uses resistor DR2SC0220

      LX9FK927 125V coil uses resistor DR2SC0330

      LX9FK932 220V coil uses resistor DR2SC1000

      The LX9FK938 coils are no longer available.

      What resistor is required for the LX9FL replacement coils?

      Issue:
      What resistor is required for the LX9FL replacement coils?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:

      LX9FL918 48V coil uses resistor DR2SC0047

      LX9FL925 110V coil uses resistor DR2SC0270

      LX9FL926 125V coil uses resistor DR2SC0330

      LX9FL931 220V coil uses resistor DR2SC1000

      *The LX9FL937 coils are no longer available.

      What terminal protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays?

      Issue:
      What terminal protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      The LA9F702 protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays

      What terminal protection shrouds fit the LR9F7*75, LR9F7*79, and LR9F7*81 overload relays?

      Issue:
      What terminal protection shrouds fit the LR9F7*75, LR9F7*79, and LR9F7*81 overload relays?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:
      The LA9F703 protection shrouds fit the LR9F7*75, LR9F7*79, and LR9F7*81 overload relays

      What are the coil voltage codes for the LC1D115 / LC2D115 and LC1D150 / LC2D150 TeSys contactor?

      Issue:
      LC1D115 / LC2D115 and LC1D150 / LC2D150

      Product Line:
      Tesys D line Contactors

      Environment:
      North America

      Resolution:
      The following list the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

      Note 1: LC1D150 contactors are only available with *7 coil codes.
      Note 2: Coil Code ending number represents frequency rating as follows:
      5 = 50 Hertz
      6 = 60 Hertz
      7 = 50/60 Hertz

      AC Volts ___Code                DC Volts ___Code
      24 ___ B5 or B6 or B7          12 ___ Not Avail.        
      42 ___ D5 or D7                   24 ___ BD
      48 ___ E5 or E6 or E7          36 ___ CD
      110 ___ F5 or F6 or F7         48 ___ ED
      115 ___ FE5 or FE7             60 ___ ND
      120 ___ G6 or G7                72 ___ SD
      127 ___ FC5 or FC7            110 ___ FD
      208 ___ L6 or LE7               125 ___ GD
      220 ___ M5 or M6 or M7       220 ___ MD
      230 ___ P5 or P7                 250 ___ UD
      240 ___ U5 or U6 or U7        440 ___ RD
      277 ___ W6 or UE7                
      380 ___ Q5 or Q6 or Q7                
      400 ___ V5 or V7                
      415 ___ N5 or N7                
      440 ___ R5 or R6 or R7                
      480 ___ T6 or T7                
      500 ___ S5 or S7                


       

      What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

      Issue:
      Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

      Product Line:
      Contactors and Starters IEC

      Environment:
      Tesys D contactors and GV manual starters

      Cause:
      Spacer required

      Resolution:
      Compensation plate catalog number GV1F03, requires 2 pieces snap together.

      What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

      Issue:
      LC*D09-38 coil consumption

      Product Line:
      Contactors and Overload Relays

      Environment:
      TeSys™ D Contactors and Overload Relays

      Resolution:
      The standard DC coil is 5.4 watts of consumption.

      What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

      Issue:
      Identifying replacement coils for tesys D non-reversing and reversing conactors

      Product Line:
      IEC Contactors and Starters

      Environment:
      Products sold and used in the United States

      Cause:
      Replacement coil is needed

      Resolution:
      DC replacement coils are not available.
      AC Coils are 50/60 hertz for voltages as listed below:

      Volts - Part Number
      12 ____ LXD1J7
      21 ____ LXD1Z7
      24 ____ LXD1B7
      32 ____ LXD1C7
      36 ____ LXD1CC7
      42 ____ LXD1D7
      48 ____ LXD1E7
      60 ____ LXD1EE7
      100 ___ LXD1K7 ( never brought to North America )
      110 ___ LXD1F7
      115 ___ LXD1FE7
      120 ___ LXD1G7
      127 ___ LXD1FC7
      200 ___ LXD1L7
      208 ___ LXD1LE7
      220 ___ LXD1M7
      230 ___ LXD1P7
      240 ___ LXD1U7
      277 ___ LXD1W7
      380 ___ LXD1Q7
      400 ___ LXD1V7
      415 ___ LXD1N7
      440 ___ LXD1R7
      480 ___ LXD1T7
      575 ___ LXD1SC7
      600 ___ LXD1X7
      690 ___ LXD1Y7


      Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

      Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

      Issue:
      Can new accessories be used on older style contactors

      Product Line:
      IEC contactors and starters

      Environment:
      Products sold and used in the United States

      Cause:
      Identifying product compatibility

      Resolution:
      Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


       

      How to disassemble an XB4 Operator

      Issue:
      How do you disassemble an XB4 operator and mounting collar

      Product Line:
      XB4 line of products, Harmony 22mm

      Environment:
      US Products

      Resolution:
      See attached file for representation.
      To disassemble an XB4 operator you need to pull the button/selector switch out of the mounting collar by using a small flat screw driver to pull down on the metal "L" shaped part on the bottom of the mounting body. You can then remove the contacts using the flat screwdriver to lift on the metal hooks that hold the contact block to the back of the mounting collar.

      To assemble you snap the head into the mounting body by lining up the arrow on the collar with with arrow on the head. You can add contact blocks by pushing the bottom latch of the contact into the collar, and then you push the contact to the collar so that the metal hooks latch on to the back of the collar.

      Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

      Issue:
      Auxiliary contact modules for the LC1D and LC2D contactors

      Product Line: 
      Contactor and Starters - IEC

      Environment:
      North American Products

      Resolution:
      Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
      Front Mounting; maximum of 1 block per contactor:

      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
      --1-----------1---------LADN11-----------LA1DN11
      --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
      --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
      --2-----------0---------LADN20-----------LA1DN20
      --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
      --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
      --0-----------2---------LADN02-----------LA1DN02
      --2-----------2---------LADN22-----------LA1DN22
      --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
      --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
      --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
      --3-----------1---------LADN31------------LA1DN31
      --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
      --1-----------3---------LADN13------------LA1DN13
      --4-----------0---------LADN40------------LA1DN40
      --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
      --0-----------4---------LADN04------------LA1DN04




      Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
      --1-----------0--------LADN10----------LA1DN10
      --0-----------1--------LADN01----------LA1DN01

      Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
      (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
      --1-----------1--------LAD8N11----------LA8DN11
      --2-----------0--------LAD8N20----------LA8DN20
      --0-----------2--------LAD8N02----------N/A

      Footnotes:
      {1} EN50 012 Machine Tool Terminal Markings
      {2} (2) NO Sealed Dust Tight Contacts
      {3} Gold Flash Contacts
      {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
      {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
      {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

      What replacement coils are available for the LC1F500?

      Issue:
      What replacement coils are available for the LC1F500?

      Product Line:
      TeSys F-Line Contactors

      Environment:
      All Product Lines

      Cause:
      Can not find it in the Digest

      Resolution:

      For LX1 standard style coils (most common):

      24VAC (40 - 400 hz) = Not Available
      48VAC (40 - 400 hz) = LX1FK048
      110VAC (40 - 400 hz) = LX1FK110
      120AC (40 - 400 hz) = LX1FK110
      208VAC (40 - 400 hz) = LX1FK200
      220VAC (40 - 400 hz) = LX1FK220
      240VAC (40 - 400 hz) = LX1FK240
      277VAC (40 - 400 hz) = LX1FK280
      380VAC (40 - 400 hz) = LX1FK380
      415VAC (40 - 400 hz) = LX1FK415
      440VAC (40 - 400 hz) = LX1FK415
      480VAC (40 - 400 hz) = LX1FK415
      600VAC (40 - 400 hz) = LX1FK600


      For LX9 special coils:


      24VAC (40 - 400 hz) = LX9FK910
      48VAC (40 - 400 hz) = LX9FK917
      110VAC (40 - 400 hz) = LX9FK925
      120AC (40 - 400 hz) = LX9FK925
      208VAC (40 - 400 hz) = LX9FK930
      220VAC (40 - 400 hz) = LX9FK931
      240VAC (40 - 400 hz) = LX9FK932
      277VAC (40 - 400 hz) = LX9FK932
      380VAC (40 - 400 hz) = LX9FK936
      415VAC (40 - 400 hz) = LX9FK936
      440VAC (40 - 400 hz) = LX9FK937
      480VAC (40 - 400 hz) = LX9FK937
      600VAC (40 - 400 hz) = Not Available







       

      What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

      Issue:
      What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

      Product Line:
      IEC Contactors

      Environment:
      Ordering

      Cause:
      Selection

      Resolution:
      The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

      AC Volts ___Code     AC Volts ___Code
      12 ___ J7                   208 ___ LE7
      21 ___ Z7                   220 ___ M7
      24 ___ B7                  230 ___ P7
      32 ___ C7                  240 ___ U7
      36 ___ CC7               277 ___ W7
      42 ___ D7                  380 ___ Q7
      48 ___ E7                   400 ___ V7
      60 ___ EE7                415 ___ N7
      100 ___ K7                440 ___ R7
      110 ___ F7                480 ___ T7
      115 ___ FE7              575 ___ SC7
      120 ___ G7                600 ___ X7
      127 ___ FC7              690 ___ Y7
      200 ___ L7                
                     
      Standard Coil                Low Consumption
      DC Volts ___Code          DC Volts ___Code
      12 ___ JD                           5 ___ AL
      24 ___ BD                         12 ___ JL
      36 ___ CD                         20 ___ ZL
      48 ___ ED                         24 ___ BL
      60 ___ ND                         48 ___ EL
      72 ___ SD                         72 ___ SL
      110 ___ FD                       96 ___ DL
      125 ___ GD                     110 ___ FL
      220 ___ MD                    220 ___ ML
      250 ___ UD                     250 ___ UL
      440 ___ RD