Spare Coils

Spare Coils

Spare Coils

Item Number: LX1D8N5

Retail
$468.83
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor coil

Product compatibility

LC1D115

Warranty

18 months

Physical

Mechanical durability

8 Mcycles

Ambient air temperature for operation

-5-60 °C

Net weight

0.26 kg

Others

Device short name

LX1D8

Control circuit type

AC at 50 Hz

[Uc] control circuit voltage

415 V AC 50 Hz

Average resistance

368.43 Ohm at 20 °C

Inductance of closed circuit

27.65 H

Maximum operating rate

2400 cyc/h 60 °C

Coil technology

without built-in suppressor module

Control circuit voltage limits

  • drop-out: 0.3...0.6 Uc at 50 Hz (at <55 °C)
  • operational: 0.85...1.1 Uc at 50 Hz (at <55 °C)
    • Inrush power in VA

      300-300 VA 50 Hz cos phi 0.8 (at 20 °C)

      Hold-in power consumption in VA

      22-22 VA 50 Hz cos phi 0.3 (at 20 °C)

      Heat dissipation

      3-8 W at 50 Hz

      Unit Type of Package 1

      PCE

      Number of Units in Package 1

      1

      Package 1 Weight

      280 g

      Package 1 Height

      6.2 cm

      Package 1 width

      11.5 cm

      Package 1 Length

      17 cm
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Technical Data Catalogues

      • End of Life Manual

      • Product Environmental

      Frequently Asked Questions

      hide show

      What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

      Issue:
      AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

      Product Line:
      Tesys D Replacement Parts

      Environment:
      TeSys™ D AC Coils

      Resolution:

      Is 240 volt replacement control coil available for LC1D11500?

      Issue:
      Identifying replacement coil part number

      Product Line:
      IEC contactors and starters

      Environment:
      Products sold and used in the United States

      Cause:
      Replacement control coil needed for older style Tesys Contactor

      Resolution:
      Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


      CTA-ID : 11321

      What is the 240v coil to fit an LC1D1506

       The 240v coil is an LX1D8U7

      spare 415VAC coil for LC1D80 Contactor ?

      Code = LX1D6N7

      What is the replacement for LC1D115 with LX1D6G7 coil?

      The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

      LC1D1156F7
      TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

      For more information see:
      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

      What is the altitude derating for a TeSys D-Line contactor?

      Issue:​
      What is the altitude derating for a TeSys D-Line contactor?

      Product Line:
      Digest 177 Section 18 : Contactors and Starters, IEC

      Environment:
      North American Products

      Resolution:
      The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

      Voltage
      3500m x 0.90
      4000m x 0.80
      4500m x 0.70
      5000m x 0.60

      Current
      3500m x 0.92
      4000m x 0.90
      4500m x 0.88
      5000m x 0.86

      For example, an LC1D80 at 5000 meters:
      - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
      - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



       

      What is the 240V coil needed for a LC1D80008 contactor

       The coil is a LX1D6U7

      What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

      Issue:
      Identifying maximum voltage of an LC1D contactor

      Product Line:
      TeSys D Contactors

      Environment:
      IEC contactors and starters used in North America

      Cause:
      n/a

      Resolution:
      IThe maximum voltage per UL and CSA is 600VAC. 
       

      What is the difference between LC1DT25 and LC1D25

       LC1DT25 is 4 pole and LC1D25 is 3 pole

      Contactor LE1D18N7 does it come with overload ?

       No - Overloads can be ordered separatly depending on the current rating required
       

      What is the part number for replacement contacts for the LC1D115 contactor??

      The part number for replacement contacts for the LC1D115 contactor is - LA5D1158031
      For further information on this part go to link below:-

      https://www.schneider-electric.com.au/en/search/LA5D1158031

      Are the D-Line contactors rated to break DC voltages?

      Issue: 
      Can the TeSys D line be used to control DC loads? 

      Product Line:
      Tesys D contactors

      Environment:
      Products sold and used in the United States
       
      Cause:
       DC power circuit
       
      Resolution:
       
      Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

      Devices are suitable but not UL Listed for DC applications.

      More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


       
      Show More