Spare Coils

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor coil

Product compatibility

  • LC1D150
  • LC1D115
    • Warranty

      18 months

      Physical

      Mechanical durability

      8 Mcycles

      Ambient air temperature for operation

      -5-60 °C

      Others

      Device short name

      LX1D8

      Control circuit type

      AC at 50/60 Hz

      [Uc] control circuit voltage

      220 V AC 50/60 Hz

      Average resistance

      9895 Ohm at 20 °C

      Inductance of closed circuit

      210.72 H

      Maximum operating rate

      1200 cyc/h 60 °C

      Coil technology

      without built-in suppressor module

      Control circuit voltage limits

    • drop-out: 0.3...0.5 Uc at 50/60 Hz (at <55 °C)
    • operational: 0.8...1.15 Uc at 50/60 Hz (at <55 °C)
      • Inrush power in VA

      • 280-350 VA 60 Hz cos phi 0.9 (at 20 °C)
      • 280-350 VA 50 Hz cos phi 0.9 (at 20 °C)
        • Hold-in power consumption in VA

        • 2-18 VA 60 Hz cos phi 0.9 (at 20 °C)
        • 2-18 VA 50 Hz cos phi 0.9 (at 20 °C)
          • Heat dissipation

            3-4.5 W at 50/60 Hz

            Unit Type of Package 1

            PCE

            Number of Units in Package 1

            1

            Package 1 Weight

            303 g

            Package 1 Height

            6.2 cm

            Package 1 width

            11.5 cm

            Package 1 Length

            17 cm

            Unit Type of Package 2

            S03

            Number of Units in Package 2

            20

            Package 2 Weight

            6.544 kg

            Package 2 Height

            30 cm

            Package 2 width

            30 cm

            Package 2 Length

            40 cm
            Show all specifications

            Documents & downloads

            hide show
            Filter items
            • All

            • Product Brochures

            • Technical Data Catalogues

            • End of Life Manual

            • Installation Instruction

            • Product Environmental

            Frequently Asked Questions

            hide show

            What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

            Issue:
            AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

            Product Line:
            Tesys D Replacement Parts

            Environment:
            TeSys™ D AC Coils

            Resolution:

            Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

            Issue:
            Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

            Product Line: 
            Tesys D Contactors

            Environment:
            IEC contactors

            Resolution:
            The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
             

            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

            Issue:
            Identifying maximum voltage of an LC1D contactor

            Product Line:
            TeSys D Contactors

            Environment:
            IEC contactors and starters used in North America

            Cause:
            n/a

            Resolution:
            IThe maximum voltage per UL and CSA is 600VAC. 
             

            What is the altitude derating for a TeSys D-Line contactor?

            Issue:​
            What is the altitude derating for a TeSys D-Line contactor?

            Product Line:
            Digest 177 Section 18 : Contactors and Starters, IEC

            Environment:
            North American Products

            Resolution:
            The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

            Voltage
            3500m x 0.90
            4000m x 0.80
            4500m x 0.70
            5000m x 0.60

            Current
            3500m x 0.92
            4000m x 0.90
            4500m x 0.88
            5000m x 0.86

            For example, an LC1D80 at 5000 meters:
            - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
            - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



             

            What is the 240v coil to fit an LC1D1506

             The 240v coil is an LX1D8U7

            What replaces a LC1D18M7

            Use the LC1D18U7

            What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

            Issue:
            Identifying replacement coils for tesys D non-reversing and reversing conactors

            Product Line:
            IEC Contactors and Starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement coil is needed

            Resolution:
            DC replacement coils are not available.
            AC Coils are 50/60 hertz for voltages as listed below:

            Volts - Part Number
            12 ____ LXD1J7
            21 ____ LXD1Z7
            24 ____ LXD1B7
            32 ____ LXD1C7
            36 ____ LXD1CC7
            42 ____ LXD1D7
            48 ____ LXD1E7
            60 ____ LXD1EE7
            100 ___ LXD1K7 ( never brought to North America )
            110 ___ LXD1F7
            115 ___ LXD1FE7
            120 ___ LXD1G7
            127 ___ LXD1FC7
            200 ___ LXD1L7
            208 ___ LXD1LE7
            220 ___ LXD1M7
            230 ___ LXD1P7
            240 ___ LXD1U7
            277 ___ LXD1W7
            380 ___ LXD1Q7
            400 ___ LXD1V7
            415 ___ LXD1N7
            440 ___ LXD1R7
            480 ___ LXD1T7
            575 ___ LXD1SC7
            600 ___ LXD1X7
            690 ___ LXD1Y7


            Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

            Is 240 volt replacement control coil available for LC1D11500?

            Issue:
            Identifying replacement coil part number

            Product Line:
            IEC contactors and starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement control coil needed for older style Tesys Contactor

            Resolution:
            Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


            CTA-ID : 11321

            What is the 240V coil needed for a LC1D80008 contactor

             The coil is a LX1D6U7

            spare 415VAC coil for LC1D80 Contactor ?

            Code = LX1D6N7

            What is the replacement for LC1D115 with LX1D6G7 coil?

            The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

            LC1D1156F7
            TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

            For more information see:
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

            What is the plastic arm for LE1D18U7 stop button

            Part code LAD91810
            Show More