Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LX1D6
Control circuit type
AC at 50 Hz
[Uc] control circuit voltage
240 V AC 50 Hz
Average resistance
152 Ohm at 20 °C
Inductance of closed circuit
8.7 H
Product compatibility
  • LC1D95
  • LC1D80
    • Mechanical durability
      10 Mcycles
      Maximum operating rate
      3600 cyc/h 60 °C
      Coil technology
      without built-in suppressor module
      Control circuit voltage limits
    • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
    • operational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
    • operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
      • Inrush power in VA
        200-200 VA 50 Hz cos phi 0.75 (at 20 °C)
        Hold-in power consumption in VA
        20-20 VA 50 Hz cos phi 0.3 (at 20 °C)
        Heat dissipation
        6-10 W at 50/60 Hz
        Ambient air temperature for operation
        -5-60 °C
        Net weight
        0.28 kg
        Warranty
        18 months

        Documents & downloads

        hide show
        Filter items
        • All

        • Product Brochures

        • Technical Data Catalogues

        • Product Environmental

        Frequently Asked Questions

        hide show

        What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

        Issue:
        AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

        Product Line:
        Tesys D Replacement Parts

        Environment:
        TeSys™ D AC Coils

        Resolution:

        What is the 240V coil needed for a LC1D80008 contactor

         The coil is a LX1D6U7

        Is 240 volt replacement control coil available for LC1D11500?

        Issue:
        Identifying replacement coil part number

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Replacement control coil needed for older style Tesys Contactor

        Resolution:
        Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


        CTA-ID : 11321

        What is the altitude derating for a TeSys D-Line contactor?

        Issue:​
        What is the altitude derating for a TeSys D-Line contactor?

        Product Line:
        Digest 177 Section 18 : Contactors and Starters, IEC

        Environment:
        North American Products

        Resolution:
        The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

        Voltage
        3500m x 0.90
        4000m x 0.80
        4500m x 0.70
        5000m x 0.60

        Current
        3500m x 0.92
        4000m x 0.90
        4500m x 0.88
        5000m x 0.86

        For example, an LC1D80 at 5000 meters:
        - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
        - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



         

        What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

        Issue:
        Identifying power terminal lug data for the D2 style contactors

        Product Line:
        Tesys D line contactors

        Environment:
        Products sold and used in the United States

        Cause:
        Power terminal lug data required

        Resolution:
        For contactors with screw clamp terminals:
        stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
        stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
        solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

        What is the replacement for LC1D115 with LX1D6G7 coil?

        The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

        LC1D1156F7
        TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

        For more information see:
        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

        What is the 240v coil to fit an LC1D1506

         The 240v coil is an LX1D8U7

        spare 415VAC coil for LC1D80 Contactor ?

        Code = LX1D6N7

        What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

        Issue:
        Identifying maximum voltage of an LC1D contactor

        Product Line:
        TeSys D Contactors

        Environment:
        IEC contactors and starters used in North America

        Cause:
        n/a

        Resolution:
        IThe maximum voltage per UL and CSA is 600VAC. 
         

        On the TeSys D-Line contactor with AC coils, which are the coil terminals?

        Issue:
        Identifying the coil terminals for an LC1D TeSys D-Line contactor.

        Product Line:
        D Line contactors.

        Environment:
        Products sold in the United States.

        Cause:
        Product features.

        Resolution:
        The coil terminals are labelled A1 and A2.

        Are the D-Line contactors rated to break DC voltages?

        Issue: 
        Can the TeSys D line be used to control DC loads? 

        Product Line:
        Tesys D contactors

        Environment:
        Products sold and used in the United States
         
        Cause:
         DC power circuit
         
        Resolution:
         
        Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

        Devices are suitable but not UL Listed for DC applications.

        More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


         

        What is the color scheme of the Tesys D-Line contactors?

        Issue:
        Looking for different color scheme of the Tesys D-Line contactors.

        Product Line:
        Tesys D Contactors

        Environment:
        LC1D contactors

        Resolution:
        Beige and dark gray.
         

        Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

        ISSUE
        Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?
        PRODUCT LINE
        Auxiliary contacts for the Tesys D line
        ENVIRONMENT
        Tesys D-Line and Tesys F
        CAUSE
        Fit
        RESOLUTION
        These contacts will only fit on the following contactors:
        Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
        Left side mount only to LC1F contactors
        CTA-ID : 2002751

        What are the stand alone short circuit current ratings on the LC1D** contactors?

        Issue:
        Tesys D SCCR

        Product Line:
        Contactors and Overload Relays

        Environment:
        TeSys™ D Contactors and Overload Relays
         
        Resolution:
        The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

        They are as follows:
        Horsepower SCCR (A)

        0 thru 1 1,000
        1 thru 50 5,000
        51 thru 200 10,000
        201 thru 400 18,000
        401 thru 600 30,000
        601 thru 900 42,000
        901 thru 1600 85,000
        1601+ 100,000

        What is the difference between LC1DT25 and LC1D25

         LC1DT25 is 4 pole and LC1D25 is 3 pole

        Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

        Issue:
        Can new accessories be used on older style contactors

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Identifying product compatibility

        Resolution:
        Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


         

        LC1D6511 contactor with 220V coil - NZ equivalent?

        LC1D65A contactor with a U7 240VAC coil is the closest.

        What is the code for a 240VAC coil for the LC1D65A Contactor?

        The LC1D65A is the Everlink contactor and the coil code is LXD3U7. 

        The code for complete contactor + 240VAC coil is LC1D65AU7
         

        What is the replacement for the Tesys D Contactor LC1D65U7?

        use the new code - LC1D65AU7
        3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC
        See link for Data Sheet:
        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7

        How many wires can you install on the Power poles for the LC1D65A contactor?

         Issue:
        How many wires can you install on the Power poles for the LC1D65A contactor?

        Product line:
        Tesys D, Everlink

        Environment:
        LC1D40A LC1D50A LC1D65A

        Cause:
        Documentation not found

        Resolution:
        The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase.  1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2. 

        Instruction bulletin attached.

        What is the part number for replacement contacts for the LC1D115 contactor??

        The part number for replacement contacts for the LC1D115 contactor is - LA5D1158031
        For further information on this part go to link below:-

        https://www.schneider-electric.com.au/en/search/LA5D1158031

        Can our "D" contactors handle 480volts?

        Our "D" Contactors LC1D09 - LC1D65A are rated to 690volts AC and the LC1D80 to LC1D150 are rated up to 1000VAC/ 690VDC.

        What do the LA4D timing modules require for mounting on LC1D40A through LC1D65A contactors?

        Product Line:
         
        Tesys D line Contactors and Accessories

        Resolution:
         
        Mounting this module to TeSys LC1D40A through LC1D65A contactor requires the use of the LAD4BB3 wiring adaptor. This adaptor can be fitted only to contactors with no coil suppressor.
         

        What code is a mechanical interlock for the 4pole LC1D1150046 contactor?

        LA9D11502 will fit the 4p LC1D115 and LC1D150 contactors

        Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

        Issue:
        Auxiliary contact modules for the LC1D and LC2D contactors

        Product Line: 
        Contactor and Starters - IEC

        Environment:
        North American Products

        Resolution:
        Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
        Front Mounting; maximum of 1 block per contactor:

        N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
        --1-----------1---------LADN11-----------LA1DN11
        --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
        --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
        --2-----------0---------LADN20-----------LA1DN20
        --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
        --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
        --0-----------2---------LADN02-----------LA1DN02
        --2-----------2---------LADN22-----------LA1DN22
        --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
        --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
        --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
        --3-----------1---------LADN31------------LA1DN31
        --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
        --1-----------3---------LADN13------------LA1DN13
        --4-----------0---------LADN40------------LA1DN40
        --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
        --0-----------4---------LADN04------------LA1DN04




        Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

        N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
        --1-----------0--------LADN10----------LA1DN10
        --0-----------1--------LADN01----------LA1DN01

        Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
        (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

        N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
        --1-----------1--------LAD8N11----------LA8DN11
        --2-----------0--------LAD8N20----------LA8DN20
        --0-----------2--------LAD8N02----------N/A

        Footnotes:
        {1} EN50 012 Machine Tool Terminal Markings
        {2} (2) NO Sealed Dust Tight Contacts
        {3} Gold Flash Contacts
        {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
        {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
        {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

        What is the 480V coil for a CA2DN31T6 IEC Relay?

        Issue:
        What is the 480V coil for a CA2DN31T6 IEC Relay?

        Product Line:
        Tesys Relays

        Environment:
        Obsolete relays

        Cause:
        Product selection

        Resolution:
        The LX1D2T6 coil is obsolete. Replace the contactor with the new TeSys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.


        CTA-ID : 2048217

        Are the LC1D115 and LC1D150 contactors din rail mountable?

        Issue: 
        LC1D115 and D150 mounting

        Product Line:
         Tesys D contactors

        Environment:
        Products sold and used in the United States
         
        Cause:
        Din rail mounting desired for large D line contactor
         
        Resolution:
         
        Yes, they use 2-35mm din rails


         

        What is the mechanical interlock for the LC1D115 contactor?

        Issue:
        Interlock needed for a pair of LC1D115 contactors

        Product Line:
        NEMA combination starters

        Environment:
        Products sold and used in the United States

        Cause:
        Application requires mechanical interlocking

        Resolution:
        LA9D11502. It includes the electrical interlocks.

         

        What is the part code for terminal shrouds to fit LC1D115 or LC1D150

        The part code is LA9D115703 for 3 pole
        The part code for 4 pole is LA9D115704

        What is the reference for the separate mounting kit for LRD4369 overload relay

        The LRD43xx type of thermal overload relays are directly mounted to the contactors LC1D115 & LC1D150 only. There is no separate mounting kit for the LRD43xx.

        If a separate mounting is required for the contactors LC1D115 or LC1D150 type, then LRD336xx shall be selected as these range of overload relays have indepentdent mounting and have similar setting range and are of Class 10A.

        Will the LR3D325 overload relay fit a LC1D65G7 contactor?

        Issue:
        Will the LC1D65G7 mount to the LR3D325 overload relay?

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Identifying product compatibility

        Resolution:
        No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


        CTA-ID : 2050461

        What does the (3) designate in the part number LC1D123G7?

        For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



        CTA-ID : 2053127

        Do the Everlink reversing contactors come with electrical interlocking?

        Issue:
        Looking for electrical interlock kit for the LC1D65A Everlnk contactors

        Product line:
        Tesys D LC1D40A, LC1D50A, LC1D65A

        Environment:
        Everlink, all voltage codes

        Cause:
        Old D2 version offered an electrical interlock kit

        Resolution:
        The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

        What is the difference between LC1D115 and LC1D1156?

        The 6 in LC1D1156.. is that the 6 denotes lug bar terminals. Use LC1D115.. for cable connections.


         

        Which rectifier is required for the LX9F*917 48V coil?

        Issue:
        Which rectifier is required for the LX9F*917 48V coil?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        For the LX9FJ917, LX9FK917, and LX9FL917 48V coils, use rectifier part number: DR5TF4V

        Which rectifier is required for the LX9F*925 110V coil?

        Issue:
        Which rectifier is required for the LX9F*925 110V coil?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        For the LX9FJ925, LX9FK925, and LX9FL925 110V coils, use rectifier part number: DR5TF4U

        Which rectifier is required for the LX9F*925 120V coil?

        Issue:
        Which rectifier is required for the LX9F*925 120V coil?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        For the LX9FJ925, LX9FK925, and LX9FL925 120V coils, use rectifier part number: DR5TF4U

        Which rectifier is required for the LX9F*931 220V coil?

        Issue:
        Which rectifier is required for the LX9F*931 220V coil?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        For the LX9FJ931, LX9FK931, and LX9FL931 220V coils, use rectifier part number: DR5TF4U

        What terminal protection shrouds fit the LR9F5*57 overload relays?

        Issue:
        What terminal protection shrouds fit the LR9F5*57 overload relays?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        The LA9F701 protection shrouds fit the LR9F5357 and the LR9F5557 overload relays.

        What terminal protection shrouds fit the LR9F5*71 overload relays?

        Issue:
        What terminal protection shrouds fit the LR9F5*71 overload relays?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        The LA9F705 protection shrouds fit the LR9F5*71 overload relays

        What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

        Issue:
        Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

        Product Line:
        NEMA combination starters

        Environment:
        Products sold and used in the United States

        Resolution:
        For contactors with screw clamp terminals:
        stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
        stranded cable w/cable end: One or Two #18-10 AWG per terminal.
        solid cable: One or Two #18-8 AWG per terminal.

        What is the difference between LA9D11569 and LA9D115691?

        Issue:
        Identifying differences between two part numbers

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Selecting between two similar part numbers

        Resolution:
        LA9D11569 is a set of power connections. LA9D115691 is the bottom connector only as shown on page 16-9 of Digest 173 for the LC1D115 and LC1D150 contactor.


         

        What is the suggested shorting contactor part number for an ATS48C14Y?

        Issue:
        What is the suggested shorting contactor part number for an ATS48C14Y?

        Product Line:
        Altistart 48 , ATS48

        Environment:
        ATS48C11Y , ATS48C14Y 

        Cause:
        Custom enclosure

        Resolutin:
        LC1D115 G7  (120vac coil control voltage )

        Which rectifier is required for the LX9F*936 380V and 415V coils?

        Issue:
        Which rectifier is required for the LX9F*936 380V and 415V coils?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        For the LX9FJ936, LX9FK936, and LX9FL936 380V and 415V coils, use rectifier part number: DR5TF4S

        What resistor is required for the LX9FJ replacement coils?

        Issue:
        What resistor is required for the LX9FJ replacement coils?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:

        LX9FJ918 48V coil uses resistor DR2SC0047

        LX9FJ926 110V coil uses resistor DR2SC0030

        LX9FJ927 125V coil uses resistor DR2SC0390

        LX9FJ932 220V coil uses resistor DR2SC1200

        The LX9FJ938 coils are no longer available.

        What resistor is required for the LX9FK replacement coils?

        Issue:
        What resistor is required for the LX9FK replacement coils?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:

        LX9FK918 48V coil uses resistor DR2SC0039

        LX9FK926 110V coil uses resistor DR2SC0220

        LX9FK927 125V coil uses resistor DR2SC0330

        LX9FK932 220V coil uses resistor DR2SC1000

        The LX9FK938 coils are no longer available.

        What resistor is required for the LX9FL replacement coils?

        Issue:
        What resistor is required for the LX9FL replacement coils?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:

        LX9FL918 48V coil uses resistor DR2SC0047

        LX9FL925 110V coil uses resistor DR2SC0270

        LX9FL926 125V coil uses resistor DR2SC0330

        LX9FL931 220V coil uses resistor DR2SC1000

        *The LX9FL937 coils are no longer available.

        What terminal protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays?

        Issue:
        What terminal protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        The LA9F702 protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays

        What terminal protection shrouds fit the LR9F7*75, LR9F7*79, and LR9F7*81 overload relays?

        Issue:
        What terminal protection shrouds fit the LR9F7*75, LR9F7*79, and LR9F7*81 overload relays?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:
        The LA9F703 protection shrouds fit the LR9F7*75, LR9F7*79, and LR9F7*81 overload relays

        What are the coil voltage codes for the LC1D115 / LC2D115 and LC1D150 / LC2D150 TeSys contactor?

        Issue:
        LC1D115 / LC2D115 and LC1D150 / LC2D150

        Product Line:
        Tesys D line Contactors

        Environment:
        North America

        Resolution:
        The following list the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

        Note 1: LC1D150 contactors are only available with *7 coil codes.
        Note 2: Coil Code ending number represents frequency rating as follows:
        5 = 50 Hertz
        6 = 60 Hertz
        7 = 50/60 Hertz

        AC Volts ___Code                DC Volts ___Code
        24 ___ B5 or B6 or B7          12 ___ Not Avail.        
        42 ___ D5 or D7                   24 ___ BD
        48 ___ E5 or E6 or E7          36 ___ CD
        110 ___ F5 or F6 or F7         48 ___ ED
        115 ___ FE5 or FE7             60 ___ ND
        120 ___ G6 or G7                72 ___ SD
        127 ___ FC5 or FC7            110 ___ FD
        208 ___ L6 or LE7               125 ___ GD
        220 ___ M5 or M6 or M7       220 ___ MD
        230 ___ P5 or P7                 250 ___ UD
        240 ___ U5 or U6 or U7        440 ___ RD
        277 ___ W6 or UE7                
        380 ___ Q5 or Q6 or Q7                
        400 ___ V5 or V7                
        415 ___ N5 or N7                
        440 ___ R5 or R6 or R7                
        480 ___ T6 or T7                
        500 ___ S5 or S7                


         
        Show More