Spare Coils

Spare Coils

Spare Coils

Item Number: LX1D6R7

Retail
$295.75
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor coil

Product compatibility

  • LC1D80
  • LC1D95
    • Warranty

      18 months

      Physical

      Mechanical durability

      4 Mcycles

      Ambient air temperature for operation

      -5-60 °C

      Net weight

      0.28 kg

      Others

      Device short name

      LX1D6

      Control circuit type

      AC at 50/60 Hz

      [Uc] control circuit voltage

      440 V AC 50/60 Hz

      Average resistance

      410 Ohm at 20 °C

      Inductance of closed circuit

      27 H

      Maximum operating rate

      3600 cyc/h 60 °C

      Coil technology

      without built-in suppressor module

      Control circuit voltage limits

    • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
    • operational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
    • operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
      • Inrush power in VA

      • 245-245 VA 60 Hz cos phi 0.75 (at 20 °C)
      • 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
        • Hold-in power consumption in VA

        • 26-26 VA 60 Hz cos phi 0.3 (at 20 °C)
        • 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
          • Heat dissipation

            6-10 W at 50/60 Hz

            Package 1 Weight

            0.325 kg

            Package 1 Height

            0.57 dm

            Package 1 width

            1.26 dm

            Package 1 Length

            0.88 dm
            Show all specifications

            Documents & downloads

            hide show
            Filter items
            • All

            • Product Brochures

            • Technical Data Catalogues

            • Installation Instruction

            • Product Environmental

            Frequently Asked Questions

            hide show

            What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

            Issue:
            AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

            Product Line:
            Tesys D Replacement Parts

            Environment:
            TeSys™ D AC Coils

            Resolution:

            What is the 240V coil needed for a LC1D80008 contactor

             The coil is a LX1D6U7

            spare 415VAC coil for LC1D80 Contactor ?

            Code = LX1D6N7

            What is the replacement for LC1D115 with LX1D6G7 coil?

            The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

            LC1D1156F7
            TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

            For more information see:
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

            What is the 240v coil to fit an LC1D1506

             The 240v coil is an LX1D8U7

            What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

            Issue:
            Identifying power terminal lug data for the D2 style contactors

            Product Line:
            IEC Contactors and Starters

            Environment:
            Tesys D line contactors

            Cause:
            Power terminal lug data required

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
            stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
            solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.
            Show More