LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors

Spare Coils

Catalogue Number: LX1D6N5
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
LX coil for D range contactors
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LX1D6
Control circuit type
AC at 50 Hz
[Uc] control circuit voltage
415 V AC 50 Hz
Average resistance
463 Ohm at 20 °C
Inductance of closed circuit
26 H
Product compatibility
  • LC1D95
  • LC1D80
    • Mechanical durability
      10 Mcycles
      Maximum operating rate
      3600 cyc/h 60 °C
      Coil technology
      without built-in suppressor module
      Control circuit voltage limits
    • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
    • operational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
    • operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
      • Inrush power in VA
        200-200 VA 50 Hz cos phi 0.75 (at 20 °C)
        Hold-in power consumption in VA
        20-20 VA 50 Hz cos phi 0.3 (at 20 °C)
        Heat dissipation
        6-10 W at 50/60 Hz
        Ambient air temperature for operation
        -5-60 °C
        Net weight
        0.28 kg
        California proposition 65
        WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
        Warranty
        18 months

        Documents & downloads

        hide show
        Filter items
        • All

        • Product Brochures

        • Technical Data Catalogues

        • Product Environmental

        Frequently Asked Questions

        hide show

        What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

        Issue:
        AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

        Product Line:
        Tesys D Replacement Parts

        Environment:
        TeSys™ D AC Coils

        Resolution:

        spare 415VAC coil for LC1D80 Contactor ?

        Code = LX1D6N7

        What is the replacement for LC1D115 with LX1D6G7 coil?

        The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

        LC1D1156F7
        TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

        For more information see:
        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

        What is the 240V coil needed for a LC1D80008 contactor

         The coil is a LX1D6U7

        What is the altitude derating for a TeSys D-Line contactor?

        Issue:​
        What is the altitude derating for a TeSys D-Line contactor?

        Product Line:
        Digest 177 Section 18 : Contactors and Starters, IEC

        Environment:
        North American Products

        Resolution:
        The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

        Voltage
        3500m x 0.90
        4000m x 0.80
        4500m x 0.70
        5000m x 0.60

        Current
        3500m x 0.92
        4000m x 0.90
        4500m x 0.88
        5000m x 0.86

        For example, an LC1D80 at 5000 meters:
        - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
        - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



         

        What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

        Issue:
        Identifying power terminal lug data for the D2 style contactors

        Product Line:
        Tesys D line contactors

        Environment:
        Products sold and used in the United States

        Cause:
        Power terminal lug data required

        Resolution:
        For contactors with screw clamp terminals:
        stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
        stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
        solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

        Is 240 volt replacement control coil available for LC1D11500?

        Issue:
        Identifying replacement coil part number

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Replacement control coil needed for older style Tesys Contactor

        Resolution:
        Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


        CTA-ID : 11321

        On the TeSys D-Line contactor with AC coils, which are the coil terminals?

        Issue:
        Identifying the coil terminals for an LC1D TeSys D-Line contactor.

        Product Line:
        D Line contactors.

        Environment:
        Products sold in the United States.

        Cause:
        Product features.

        Resolution:
        The coil terminals are labelled A1 and A2.

        Are the D-Line contactors rated to break DC voltages?

        Issue: 
        Can the TeSys D line be used to control DC loads? 

        Product Line:
        Tesys D contactors

        Environment:
        Products sold and used in the United States
         
        Cause:
         DC power circuit
         
        Resolution:
         
        Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

        Devices are suitable but not UL Listed for DC applications.

        More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


         

        What is the color scheme of the Tesys D-Line contactors?

        Issue:
        Looking for different color scheme of the Tesys D-Line contactors.

        Product Line:
        Tesys D Contactors

        Environment:
        LC1D contactors

        Resolution:
        Beige and dark gray.
         

        What is the 240v coil to fit an LC1D1506

         The 240v coil is an LX1D8U7

        Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

        ISSUE
        Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?
        PRODUCT LINE
        Auxiliary contacts for the Tesys D line
        ENVIRONMENT
        Tesys D-Line and Tesys F
        CAUSE
        Fit
        RESOLUTION
        These contacts will only fit on the following contactors:
        Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
        Left side mount only to LC1F contactors
        CTA-ID : 2002751
        Show More