Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LX1D6
Control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
220 V AC 50/60 Hz
Average resistance
102 Ohm at 20 °C
Inductance of closed circuit
6.7 H
Product compatibility
  • LC1D80
  • LC1D95
    • Mechanical durability
      4 Mcycles
      Maximum operating rate
      3600 cyc/h 60 °C
      Coil technology
      without built-in suppressor module
      Control circuit voltage limits
    • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
    • operational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
    • operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
      • Inrush power in VA
      • 245-245 VA 60 Hz cos phi 0.75 (at 20 °C)
      • 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
        • Hold-in power consumption in VA
        • 26-26 VA 60 Hz cos phi 0.3 (at 20 °C)
        • 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
          • Heat dissipation
            6-10 W at 50/60 Hz
            Ambient air temperature for operation
            -5-60 °C
            Net weight
            0.28 kg
            Unit Type of Package 1
            PCE
            Number of Units in Package 1
            1
            Package 1 Weight
            307 g
            Package 1 Height
            5.6 cm
            Package 1 width
            12.5 cm
            Package 1 Length
            9 cm
            Unit Type of Package 2
            S02
            Number of Units in Package 2
            16
            Package 2 Weight
            5.358 kg
            Package 2 Height
            15 cm
            Package 2 width
            30 cm
            Package 2 Length
            40 cm
            Warranty
            18 months

            Documents & downloads

            hide show
            Filter items
            • All

            • Product Brochures

            • Technical Data Catalogues

            • Installation Instruction

            • Product Environmental

            Frequently Asked Questions

            hide show

            What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

            Issue:
            AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

            Product Line:
            Tesys D Replacement Parts

            Environment:
            TeSys™ D AC Coils

            Resolution:

            What is the 240V coil needed for a LC1D80008 contactor

             The coil is a LX1D6U7

            spare 415VAC coil for LC1D80 Contactor ?

            Code = LX1D6N7

            What is the replacement for LC1D115 with LX1D6G7 coil?

            The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

            LC1D1156F7
            TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

            For more information see:
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

            What is the altitude derating for a TeSys D-Line contactor?

            Issue:​
            What is the altitude derating for a TeSys D-Line contactor?

            Product Line:
            Digest 177 Section 18 : Contactors and Starters, IEC

            Environment:
            North American Products

            Resolution:
            The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

            Voltage
            3500m x 0.90
            4000m x 0.80
            4500m x 0.70
            5000m x 0.60

            Current
            3500m x 0.92
            4000m x 0.90
            4500m x 0.88
            5000m x 0.86

            For example, an LC1D80 at 5000 meters:
            - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
            - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



             

            What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

            Issue:
            Identifying power terminal lug data for the D2 style contactors

            Product Line:
            Tesys D line contactors

            Environment:
            Products sold and used in the United States

            Cause:
            Power terminal lug data required

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
            stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
            solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

            Issue:
            Identifying maximum voltage of an LC1D contactor

            Product Line:
            TeSys D Contactors

            Environment:
            IEC contactors and starters used in North America

            Cause:
            n/a

            Resolution:
            IThe maximum voltage per UL and CSA is 600VAC. 
             

            What is the 240v coil to fit an LC1D1506

             The 240v coil is an LX1D8U7

            Is 240 volt replacement control coil available for LC1D11500?

            Issue:
            Identifying replacement coil part number

            Product Line:
            IEC contactors and starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement control coil needed for older style Tesys Contactor

            Resolution:
            Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


            CTA-ID : 11321

            What replaces a LC1D18M7

            Use the LC1D18U7

            Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

            Issue:
            Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

            Product Line: 
            Tesys D Contactors

            Environment:
            IEC contactors

            Resolution:
            The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
             

            Will the LR3D325 overload relay fit a LC1D65G7 contactor?

            Issue:
            Will the LC1D65G7 mount to the LR3D325 overload relay?

            Product Line:
            IEC contactors and starters

            Environment:
            Products sold and used in the United States

            Cause:
            Identifying product compatibility

            Resolution:
            No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


            CTA-ID : 2050461
            Show More