Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LX1D6
Control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
110 V AC 50/60 Hz
Average resistance
26 Ohm at 20 °C
Inductance of closed circuit
1.7 H
Product compatibility
  • LC1D80
  • LC1D95
    • Mechanical durability
      4 Mcycles
      Maximum operating rate
      3600 cyc/h 60 °C
      Coil technology
      without built-in suppressor module
      Control circuit voltage limits
    • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
    • operational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
    • operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
      • Inrush power in VA
      • 245-245 VA 60 Hz cos phi 0.75 (at 20 °C)
      • 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
        • Hold-in power consumption in VA
        • 26-26 VA 60 Hz cos phi 0.3 (at 20 °C)
        • 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
          • Heat dissipation
            6-10 W at 50/60 Hz
            Ambient air temperature for operation
            -5-60 °C
            Net weight
            0.28 kg
            Warranty
            18 months

            Documents & downloads

            hide show
            Filter items
            • All

            • Product Brochures

            • Technical Data Catalogues

            • Installation Instruction

            • Product Environmental

            Frequently Asked Questions

            hide show

            What is the 240V coil needed for a LC1D80008 contactor

             The coil is a LX1D6U7

            spare 415VAC coil for LC1D80 Contactor ?

            Code = LX1D6N7

            What is the replacement for LC1D115 with LX1D6G7 coil?

            The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

            LC1D1156F7
            TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

            For more information see:
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

            What is the altitude derating for a TeSys D-Line contactor?

            Issue:​
            What is the altitude derating for a TeSys D-Line contactor?

            Product Line:
            Digest 177 Section 18 : Contactors and Starters, IEC

            Environment:
            North American Products

            Resolution:
            The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

            Voltage
            3500m x 0.90
            4000m x 0.80
            4500m x 0.70
            5000m x 0.60

            Current
            3500m x 0.92
            4000m x 0.90
            4500m x 0.88
            5000m x 0.86

            For example, an LC1D80 at 5000 meters:
            - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
            - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



             

            What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

            Issue:
            Identifying power terminal lug data for the D2 style contactors

            Product Line:
            Tesys D line contactors

            Environment:
            Products sold and used in the United States

            Cause:
            Power terminal lug data required

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
            stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
            solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

            Issue:
            Identifying maximum power voltage of an LC1D contactor

            Product Line:
            Digest 177 Section 18: IEC Contactors

            Environment:
            Products sold and used in the United States

            Cause:
            Identifying ratings per UL and CSA

            Resolution:
            It is 600Vac.


             

            What is the 240v coil to fit an LC1D1506

             The 240v coil is an LX1D8U7

            Is 240 volt replacement control coil available for LC1D11500?

            Issue:
            Identifying replacement coil part number

            Product Line:
            IEC contactors and starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement control coil needed for older style Tesys Contactor

            Resolution:
            Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


            CTA-ID : 11321

            What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

            Issue:
            Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

            Product Line:
            CAD Industrial Relays

            Environment:
            Relays and Timers

            Resolution:
            Inductive:
            125V DC - 0.55 Amps make and break, 2.5 Amps cont.
            250V DC - 0.27 Amps make and break, 2.5 amps cont.
            600V DC - 0.10 Amps make and break, 2.5 Amps cont.

             

            What is the replacement AC coil for CAD32 and CAD50 relay?

            Issue:
            Are replacement  AC coil available for CAD32 and CAD50 relay?

            Product Line:
            Tesys Relays

            Environment:
            All Products

            Cause:
            Product selection

            Resolution:
            Volt = coil part number
            12 = LXD1J7
            21 = LXD1Z7
            24 = LXD1B7
            32 = LXD1C7
            36 = LXD1CC7
            42 = LXD1D7
            48 = LXD1E7
            60 = LXD1EE7
            100 = LXD1K7
            110 = LXD1F7
            115 = LXD1FE7
            120 = LXD1G7
            127 = LXD1FC7
            200 = LXD1L7
            208 = LXD1LL7
            220/230 = LXD1M7
            230 595 21 LXD1P7
            230/240 = LXD1U7
            277 781 30 LXD1W7
            380/400 = LXD1Q7
            400 = LXD1V7
            415 = LXD1N7
            440 = LXD1R7
            480 = LXD1T7
            600 = LXD1X7
            690 = LXD1Y7

             

            Will the LR3D325 overload relay fit a LC1D65G7 contactor?

            Issue:
            Will the LC1D65G7 mount to the LR3D325 overload relay?

            Product Line:
            IEC contactors and starters

            Environment:
            Products sold and used in the United States

            Cause:
            Identifying product compatibility

            Resolution:
            No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


            CTA-ID : 2050461

            Will a LC1D12F7 operate on 60V DC as a control voltage

            No it will not

            What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

            Issue:
            Identifying replacement coils for tesys D non-reversing and reversing conactors

            Product Line:
            IEC Contactors and Starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement coil is needed

            Resolution:
            DC replacement coils are not available.
            AC Coils are 50/60 hertz for voltages as listed below:

            Volts - Part Number
            12 ____ LXD1J7
            21 ____ LXD1Z7
            24 ____ LXD1B7
            32 ____ LXD1C7
            36 ____ LXD1CC7
            42 ____ LXD1D7
            48 ____ LXD1E7
            60 ____ LXD1EE7
            100 ___ LXD1K7 ( never brought to North America )
            110 ___ LXD1F7
            115 ___ LXD1FE7
            120 ___ LXD1G7
            127 ___ LXD1FC7
            200 ___ LXD1L7
            208 ___ LXD1LE7
            220 ___ LXD1M7
            230 ___ LXD1P7
            240 ___ LXD1U7
            277 ___ LXD1W7
            380 ___ LXD1Q7
            400 ___ LXD1V7
            415 ___ LXD1N7
            440 ___ LXD1R7
            480 ___ LXD1T7
            575 ___ LXD1SC7
            600 ___ LXD1X7
            690 ___ LXD1Y7


            Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

            What is the Mechanical Interlock for the LC1D12F7 ?

            LAD9R1V Is the code for the Mechanical and Electrical Interlock kit.

            LC1D6511 contactor with 220V coil - NZ equivalent?

            LC1D65A contactor with a U7 240VAC coil is the closest.

            What is the code for a 240VAC coil for the LC1D65A Contactor?

            The LC1D65A is the Everlink contactor and the coil code is LXD3U7. 

            The code for complete contactor + 240VAC coil is LC1D65AU7
             

            What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

            Issue:
            Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

            Product Line:
            NEMA combination starters

            Environment:
            Products sold and used in the United States

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
            stranded cable w/cable end: One or Two #18-10 AWG per terminal.
            solid cable: One or Two #18-8 AWG per terminal.

            What is the replacement for the Tesys D Contactor LC1D65U7?

            use the new code - LC1D65AU7
            3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC
            See link for Data Sheet:
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7

            How many wires can you install on the Power poles for the LC1D65A contactor?

             Issue:
            How many wires can you install on the Power poles for the LC1D65A contactor?

            Product line:
            Tesys D, Everlink

            Environment:
            LC1D40A LC1D50A LC1D65A

            Cause:
            Documentation not found

            Resolution:
            The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase.  1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2. 

            Instruction bulletin attached.

            Can our "D" contactors handle 480volts?

            Our "D" Contactors LC1D09 - LC1D65A are rated to 690volts AC and the LC1D80 to LC1D150 are rated up to 1000VAC/ 690VDC.

            What do the LA4D timing modules require for mounting on LC1D40A through LC1D65A contactors?

            Product Line:
             
            Tesys D line Contactors and Accessories

            Resolution:
             
            Mounting this module to TeSys LC1D40A through LC1D65A contactor requires the use of the LAD4BB3 wiring adaptor. This adaptor can be fitted only to contactors with no coil suppressor.
             

            What is the 480V coil for a CA2DN31T6 IEC Relay?

            Issue:
            What is the 480V coil for a CA2DN31T6 IEC Relay?

            Product Line:
            Tesys Relays

            Environment:
            Obsolete relays

            Cause:
            Product selection

            Resolution:
            The LX1D2T6 coil is obsolete. Replace the contactor with the new TeSys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.


            CTA-ID : 2048217

            What does the (3) designate in the part number LC1D123G7?

            For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



            CTA-ID : 2053127

            Are the D-Line contactors rated to break DC voltages?

            Issue: 
            Can the TeSys D line be used to control DC loads? 

            Product Line:
            Tesys D contactors

            Environment:
            Products sold and used in the United States
             
            Cause:
             DC power circuit
             
            Resolution:
             
            Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

            Devices are suitable but not UL Listed for DC applications.

            More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


             

            What are the stand alone short circuit current ratings on the LC1D** contactors?

            Issue:
            Tesys D SCCR

            Product Line:
            Contactors and Overload Relays

            Environment:
            TeSys™ D Contactors and Overload Relays
             
            Resolution:
            The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

            They are as follows:
            Horsepower SCCR (A)

            0 thru 1 1,000
            1 thru 50 5,000
            51 thru 200 10,000
            201 thru 400 18,000
            401 thru 600 30,000
            601 thru 900 42,000
            901 thru 1600 85,000
            1601+ 100,000

            What is the overload part number for the LC1D65U7 Contactor with 48....65 A?

            The overload part number for the LC1D65U7 Contactor with 48....65A is "LRD3359"

            https://www.schneider-electric.com.au/en/search/lrd3359