NSX250B TM200D 3P3T
3P TM-D NSX100B- Compact circuit breaker
NSX250F TM250D 3P3T
3P TM-D NSX250B- Compact circuit breaker
NSX250B TM200D 3P3T
3P TM-D NSX100B- Compact circuit breaker
NSX250F TM250D 3P3T
3P TM-D NSX250B- Compact circuit breaker

Compact NSX Circuit Breaker, TMD, 200A, 3 Poles 3d

Catalogue Number: LV431111
NSX250B TM200D 3P3T
3P TM-D NSX100B- Compact circuit breaker
NSX250F TM250D 3P3T
3P TM-D NSX250B- Compact circuit breaker
NSX250B TM200D 3P3T
3P TM-D NSX100B- Compact circuit breaker
NSX250F TM250D 3P3T
3P TM-D NSX250B- Compact circuit breaker
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Compact
Range of product
NSX100...250
Product name
Compact NSX
Product or component type
circuit breaker
Device short name
Compact NSX250B
Device application
distribution
Poles description
3P
Protected poles description
3t
Network type
AC
Network frequency
50/60 Hz
[In] rated current
200 A at 40 °C
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ue] rated operational voltage
690 V AC 50/60 Hz
Breaking capacity code
B 25 kA 415 V AC
Breaking capacity
  • 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
  • 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    • [Ics] rated service breaking capacity
    • 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    • 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    • 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    • 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
      • Suitability for isolation
      • yes conforming to EN 60947-2
      • yes conforming to IEC 60947-2
        • Utilisation category
          category A
          Trip unit name
          TM-D
          Trip unit technology
          thermal-magnetic
          Trip unit protection functions
          LI
          Pollution degree
          3 conforming to IEC 60664-1
          Control type
          toggle
          Mounting mode
          fixed
          Mounting support
          backplate
          Upside connection
          front
          Downside connection
          front
          Mechanical durability
          20000 cycles
          Electrical durability
        • 10000 cycles 440 V In conforming to IEC 60947-2
        • 10000 cycles 690 V In/2 conforming to IEC 60947-2
        • 20000 cycles 440 V In/2 conforming to IEC 60947-2
        • 5000 cycles 690 V In conforming to IEC 60947-2
          • Connection pitch
            35 mm
            Local signalling
            positive contact indication
            Protection type
          • L : for overload protection (thermal)
          • I : for short-circuit protection (magnetic)
            • Trip unit rating
              200-200 A at 40 °C
              Long time pick-up adjustment type Ir
              adjustable
              Long time pick-up adjustment range
              0.7...1 x In
              Long time delay adjustment type
              fixed
              [tr] long-time delay adjustment range
            • 120-400 s at 1.5 x In
            • 15-15 s at 6 x Ir
              • Short-time pick-up adjustment type Isd
                adjustable
                [Isd] short-time pick-up adjustment range
                5...10 x In
                Short-time delay adjustment type
                fixed
                Height
                161 mm
                Width
                105 mm
                Depth
                86 mm
                Net weight
                2.4 kg
                Compatibility code
                NSX250
                Overvoltage category
                class II
                Electrical shock protection class
                class II
                Standards
                EN/IEC 60947
                Product certifications
              • EAC
              • CCC
              • Marine
                • IP degree of protection
                  IP40 conforming to IEC 60529
                  IK degree of protection
                  IK07 conforming to IEC 62262
                  Ambient air temperature for operation
                  -35-70 °C
                  Ambient air temperature for storage
                  -55-85 °C
                  Sustainable offer status
                  Green Premium product
                  REACh Regulation
                  Free of Substances of Very High Concern above the threshold
                  EU RoHS Directive
                  Compliant
                  Mercury free
                  Yes
                  RoHS exemption information
                  Yes
                  China RoHS Regulation
                  Product out of China RoHS scope. Substance declaration for your information
                  Environmental Disclosure
                  ENVPEP120606EN
                  Circularity Profile
                  ENVEOLI120604EN
                  WEEE
                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                  California proposition 65
                  WARNING: This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
                  Warranty
                  18 months

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Technical Data Catalogues

                  • Installation Instruction

                  • Operating Manuals

                  • Marine Certificate

                  • Declaration of Conformity

                  Frequently Asked Questions

                  hide show

                  Will the Compact NSX breaker be for sale in the USA or Canada?

                  Issue:
                  Where can I buy a Compact NSX breaker?

                  Product Line:
                  Circuit Breakers

                  Cause:
                  This breaker is popular overseas and there is interest in the US

                  Resolution:
                  There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

                  If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

                  For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
                  https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page

                  ETSNZ What is the IFE Model with Modbus Connection

                  The modbus equipped module is LV434011 as opposed to the ULP only  type = LV434010

                  What is the part code for a NS breaker 3P 250Amp 40kA with 200Amp trip unit and fit busbar system

                  You can use an LV431406 frame with a LV431431 trip unit and also LV429372 busbar adaptor

                  What is the fixed lock part name for the LV431110?

                  The part name is as follows: LV429371

                  Are EasyPact CVS circuit breakers for sale in the USA or Canada?

                  Product Line:
                  EasyPact CVS circuit breakers

                  Cause:
                  This breaker is popular overseas and there is interest in the US

                  Resolution:
                  There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.

                  What is a 3P 50kA MCCB with 125A trip unit and vigi block, would also need a 125Amp RCBO

                  Use a LV430406 - 160Amp frame + LV430431 125Amp trip unit + LV429211 Vigi module + LV431536 connector = 125Amp RCBO

                  will the LV429338 fit the LV430631 and the LV431630?

                              YES            ! The LV429338.....Extended rotary handle will fit the LV430631 or the LV431630 circuit breakers
                  see data sheet...
                  https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lv429338

                  Can LV432631 be locked in ON position?

                  Part number LV432631 can be locked in ON or OFF position.

                  How to Connect the NW/NT Circuit breaker in the Modbus Network

                  The Micrologic of the NW/NT Circuit breaker has only ULP communication. So you require a Modbus or Ethernet Interface to put the NW/NT Circuit breaker in the Modbus/Ethernet Network.
                  Attached Modbus/Ethernet architecture connection drawing for the NW/NT circuit breakers. 

                  Modbus Interface Device - IFM - TRV00210
                  Ethernet Interface Device - IFE - LV434011 or LV434010

                  How to Connect the NW/NT Circuit breaker in the Modbus Network

                  The Micrologic of the NW/NT Circuit breaker has only ULP communication. So you require a Modbus or Ethernet Interface to put the NW/NT Circuit breaker in the Modbus/Ethernet Network.
                  Attached Modbus/Ethernet architecture connection drawing for the NW/NT circuit breakers. 

                  Modbus Interface Device - IFM - TRV00210
                  Ethernet Interface Device - IFE - LV434011 or LV434010

                  Does the IFE ethernet module support the SNMP protocol?

                  Issue:
                  Does the IFE ethernet module support the SNMP protocol?

                  Product Line:
                  Enerlin'X Ethernet Interface IFE (LV434011 and LV434010)

                  Environment:
                  communications protocols

                  Resolution:
                  The IFE module supports the SNMP protocol strictly to report information from the unit itself to a Network Manager System. It is not designed to collect data from sub devices, or to be used as a SNMP to Modbus gateway.

                  LV431403 - Does it come with the Trip Unit ?

                  No - just the switch body itself. Trip Unit is separate 

                  What is the part code for a 4P 160Amp RCCB

                   Use a LV430639 switch disconnector with a LV429211 vigi module

                  What is the part code for a extended rotary handle for a LV431406 NSX250 breaker

                   The part code is LV429338

                  Whats is the part no# for NSX250N?

                  LV431406 is the code for the NSX250N

                  Where are the part numbers of filter boards for ATV61 drives?

                  What is the IFE Switchboard Server (LV434011)?

                  Product Line:
                  Smart Systems

                  Resolution:
                  Same as IFE Module plus:
                  IFE Switchboard Server (LV434011) adds a Modbus serial input and supports the stacking of up to 12 IFMs for the input of RS485 Modbus connections.
                  The IFE Web pages support up to 13 total devices, however the IFE can support the throughput of up to 20 serial devices.  Each IFE supports only one ULP connection.
                  (Note that the LV434011 is replaced by the LV434002.)
                   

                  How to connect NSX circuit breaker to the Modbus/Ethernet Netowrk?

                  The Micrologic of the NSX Circuit breaker has only ULP communication. So you require a Modbus or Ethernet Interface to put the NSX Circuit breaker in the Modbus/Ethernet Network.
                  Attached Modbus/Ethernet architecture connection drawing for the NSX circuit breakers. 
                  Part No. Reference: 
                  Modbus Interface Device - IFM - TRV00210
                  Ethernet Interface Device - IFE - LV434011 or LV434010

                  Ref: FAQ FA315869  for NW/NT Circuit breakers

                  Is the LV431050 (NSX) or 31050 (NS) extended rotary handle padlockable?

                  Yes the handle has three M8 holes that can accept three padlocks.
                   

                  What is the IFE Module (LV434001)?

                  Product Line:
                  Smart Systems

                  Resolution:
                  The Interface Ethernet (IFE) Module allows you to view and streamline data from your Low Voltage Electrical Equipment assets and allows the display of status and energy data, and alarm notification from each circuit breaker via TCP/ IP connectivity.  The embedded web pages within the IFE module allow this data to be viewed on a Web browser with a simple Ethernet connection. Optional breaker on/off control is available through the Web interface.
                  • The IFE uses ULP (Universal Logic Plug – Data Protocol) data directly from Micrologic Trip Units and converts the data to Modbus TCP/IP.

                  What is the minimum adjustment of the LV431630?

                  The minimum adjustment of the LV431630 is 175A.

                  The range is 175A to 250A.

                  Video: VW3A1111 - adjust backlight time out (ATV32/ATV320)

                  Video: VW3A1111 - adjust backlight time out (ATV630/ATV930/ATV340)

                  What is the part number of NSX250B with TM200D Trip Unit?

                  The part number of NSX250B with TM200D Trip Unit is LV431111

                  For further information refer to:
                  https://eshop.schneider-electric.com/product.aspx?prod_id=LV431111&org=21&lang=1&dist=276&tab=10&ses_id

                  Is the VW3A1111 compatible for use with the ATV320 drives?

                  Issue:
                  Is the VW3A1111 compatible for use with the ATV320 drives?

                  Product Line:
                  ATV320 

                  Environment:
                  All serial numbers

                  Cause:
                  Previous version of ATV320 catalog misprint. 

                  Resolution:
                  The VW3A1111 keypad has been not developed and validated for ATV320. 
                  Hence, the keypad isn’t compatible with ATV320 (and legacy drives). 
                  Only the ATV6x0, ATV9x0 and ATV340 are supported.
                  For the ATV320, the VW3A1101, VW3A1006 and VW3A1007 are the only compatible keypads.

                  It’s true that in a previous version of ATV320 catalog VW3A1111 keypad was described, but it was mistake.
                  It has been removed from the September version.

                   

                  What is the replacement for the 31050?

                  INS range, part numbers are changed to match the compact NSX range. Only looks and part number have changed, the working, physical dimensions remain same.
                  Hence the replacement is LV431050.

                  Where can I find the Dimensions for VW3A1111 Process Drive Keypad?

                   Issue:
                  Where can I find the Dimensions for  VW3A1111 Process Drive Keypad? 

                  Product Line:  
                  Altivar 600 Altivar 900 Process Drive 

                  Environment:  
                  All

                  Cause:  
                  Dimensions

                  Resolution:  
                  VW3A1111 Dimensions are provided in the attached PDF

                  What are the Parts required to make up an NSX250F Breaker with Micrologic 2.2 Trip Unit 160 Amps?

                  We can make it up with following two items:

                  Part number LV431403 - NSX250F Basic Frame
                  Part number LV430470 - Micrologic 2.2 Trip Unit 160 Amps

                   

                  What is the part number for NSX100F, DC rated with TM125D, trip unit with a separate basic frame?

                  The part numbers will be LV438103 and LV438136.
                  For more information please follow the below link:
                  https://www.schneider-electric.com/en/product/LV438103/circuit-breaker-compact-nsx160f-dc---160-a---3-poles---without-trip-unit/
                  User-added image
                   

                  What are the dimensions for the VW3A1111 Process keypad?

                  Issue:
                  What are the dimensions for VW3A1111?

                  Product Line:
                  ATV600 ATV900 Process Drive

                  Environment:
                  All

                  Cause:
                  N/A

                  Resolution:
                  See the attached document for dimensions in mm, PDF format.
                   

                  How do you set the backlight timeout in the VW3A1111 keypad?

                  Issue:
                  How do you set the backlight timeout in the VW3A1111 keypad?

                  Product Line:
                  Altivar Process Drives using the VW3A1111 keypad

                  Environment:
                  All

                  Cause:
                  Preference 

                  Resolution:
                  There is parameter for standby timeout in VW3A1111 with default value 60s. It is possible to set it to 'NO'. This parameter is stored in the remote keypad (not in drive). How to change it depends on the drive being used.

                  ATV32/ATV320:
                  Main menu -> interface -> Display cofig. -> LCD Settings -> Stand-by delay
                  Note: access level has to be set to expert

                  ATV630/ATV930/ATV340:
                  Main menu -> My preferences -> LCD settings ->Stand by

                  ATV61/ATV71
                  Main menu -> Display cofig. -> LCD Settings -> Stand-by delay
                  Note: access level has to be set to expert

                  What is PowerView software?

                  Issue:
                  What is the Power View embedded web page in the IFE?

                  Product Line:
                  Smart Systems and Molded Case Circuit Breakers

                  Environment: 
                  Circuit Breaker Communications

                  Resolution:
                  PowerView refers to Embedded Web Pages in IFE Module (LV434010 and LV434001), and the IFE Switchboard Server (LV434011 and LV434002).
                   

                  Video: Can you use a standard CAT5 cable to connect the ATV630 process drive and the VW3A1111 remote keypad. 

                  Issue:
                  Can you use a standard CAT5 cable to connect the ATV630 process drive and the VW3A1111 remote keypad. 

                  Product Line:
                  ATV630 and ATV930 drive

                  Environment:
                  All 

                  Cause:
                  Wants to connect a standard CAT5 cable to connect the VW3A1111 to the ATV61 drives HMI port. 

                  Resolution:
                  Yes can you connect a standard CAT5 cable to the VW3A1111 keypad display.

                  You will need to remove the bottom rubber cover on the VW3A1111 keypad display.   Once the rubber cover is pulled back you will see the RJ45 for attaching the CAT5 cable.

                   

                  What is the difference Between NSX Vigi Block  LV429210 & LV431535?

                  LV429210 - Is Vigi block MH type for NSX100/160 (200 to 440 V)

                  LV431535 - Is Vigi block MH type for NSX250 (200 to 440 V)

                  Even though Tech datasheet specifies the LV429210 is rated for NSX upto 250, It is recommeded to use the VIgi module only for NSX 100/160. 

                  However, LV431535 can be used for NSX100/160/250. 

                   

                  How many IFM's can be stacked to an IFE Switchboard Server (LV434011)?

                  Issue:
                  What is the maximum number of IFM that can be attached to the IFE Switchboard Server using the stacking modules?

                  Product Line:
                  Smart Systems

                  Environment:
                  Circuit Breaker Communications

                  Resolution:
                  Quantity of 12 IFM's can be stacked to an IFE Switchboard Server (LV434011 or LV434002) via the stacking module.

                  Why does the FDM128 (LV434128) ask to verify an IP Address different than the one configured during the firmware update?

                  Issue
                  After updating the FDM128, the display shows a Runtime message that asks to verify the IP address that is not the one I configured.  After the FDM128 does a power cycle, the configured address is returned to the configured value.

                  Example screenshot:
                  FDM128_VerifyIPAddress_on_FW_Update.jpg

                  Product Line/ Environment
                  FDM128 

                  Cause
                  This screen is displayed during the initialization of the Runtime.  It displays the hardware's default IP address in the event of a complete recovery.  For FDM128 users who have completed the IP Address configuration, this has no impact on the IP Address.  The IP Address that was configured will be maintained in memory and will be used after the power cycle to complete the firmware update.

                  Resolution
                  Under normal conditions, the IP Address shown in the screen above will not show the configured address in the FDM128.


                   

                  What is the door mount kit for the Altivar 600?

                  The door mount kit for the Altivar 600 is VW3A1112. It is used for mounting Remote display VW3A1111 to panel.

                  For further information see:
                  https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=VW3A1112
                   

                  Can I connect aluminium or copper, flexible or rigid cables to the single and double terminals of the NSX 400 to 630 range.?

                  In the NSX 400 to 630 range:

                  Single terminals, part numbers LV432479 or LV432480, can take: aluminium or copper rigid cables with cross-section 35 to 300 mm² and flexible cables with cross-section 240 mm² maximum.

                  Double terminals, part numbers LV432481 or LV432482, can take: aluminium or copper rigid cables with cross-section 35 to 240 mm² and flexible cables with cross-section 185 mm² maximum.

                  What is the battery life of the Advance Graphic Display VW3A1111?

                  Issue:
                  What is the battery life of the Advance Graphic Display VW3A1111?

                  Environment:
                  Altivar Process, Altivar Machine, ATV600, ATV900, ATV320

                  Product Line:
                  Variable Frequency Drives

                  Cause:
                  What is the battery life of the Advance Graphic Display VW3A1111?

                  Resolutions:
                  The battery life time inside the VW3A1111 is 8 years.

                  Keywords:
                  Altivar Process, Altivar Machine, ATV600, ATV900, ATV320, Battery life, VW3A1111

                  What is the IP rating for VW3A1111?

                  Issue:
                  What is the IP rating for VW3A1111?

                  Product Line:
                  ATV630

                  Environment:
                  All

                  Cause:
                  N/A

                  Resolution:
                  The keypad is rated for IP65.
                   

                  What is the keypad part number for ATV630 and ATV930 drives?

                  Issue:
                  What is the keypad part number for ATV630 and ATV930 drives?

                  Product Line:
                  ATV630
                  ATV930

                  Environment:
                  All

                  Cause:
                  Keypad

                  Resolution:
                  The part number for the keypad is VW3A1111

                  How to upload or download files on ATV630/ATV930 drives using VW3A1111.

                  Issue:
                  How to open/save and transfer file on the VW3A1111 remote keypad for the Altivar Process Drive?

                  Product Line:
                  Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

                  Environment:
                  All serial numbers for Altivar Process Drive

                  Cause:
                  N/A

                  Resolution:
                  Save to HMI (Keypad)

                  From the main menu, Go to [File management] [Transfer config file] [Copy from the Drive]

                  Transfer Back to the Drive From HMI
                  From the main menu, Go to [File management] [Transfer config file] [Copy to the Drive]

                  PC
                  Plug HMI to PC with mini USB connector and open HMI folder and go to (DRVCONF) folder and open .cfg file

                  Can IFE be used as a Modbus gateway for none trip units?

                  Issue
                  Customers are trying to connect PowerLogic and ION meters to an IFE with the expectation that it can act as a Modbus Gateway.

                  Product
                  IFE
                  PowerLogic and ION Meters

                  Environment
                  Communications

                  Resolution
                  Yes, with the LV434002.

                  More Information:
                  The basic IFE, LV434001 (previously LV434010), is only a Modbus TCP gateway for the single circuit breaker connected to its ULP port.  The IFE Switchboard Server, LV434002 (previously LV434011), has the same function, but is also able to be a Modbus RTU gateway for additional devices connected through its stacking connector, such as IFMs. So in order to get the Modbus serial line (RS485) accessible, an IFM is required to be stacked to the IFE-SS through the DIN rail connection which then makes 2-wire Modbus available from the IFM’s top connector.  So if there are multiple circuit breakers, an IFE-SS and enough IFMs can be stacked on the DIN rail to accommodate them, and then Modbus can be daisy chained from the last IFM to a meter or any other Modbus device.

                  Why does the FDM128 (LV434128) V6.1.1 not display values the serial number for some devices?

                  Issue
                  The FDM128 (LV434128) with firmware version 6.1.1 has fields to show the serial numbers of connected equipment.  However, the values are blank or N/A.

                  Product Line/ Environment
                  FDM128 

                  Cause
                  The serial number and firmware version information should be read from the equipment if the equipment has a Modbus register to store the value.  In V6.1.1, the strings were added for some equipment that do not support the field.  For example, FDM121 does not provide the Serial Number.  In addition, the FDM121 and BSCM do not provide the Firmware version over communication. As a result, the fields will be blank or N/A.

                  Resolution
                  Some fields may not be able to display the serial number and/or firmware version information if it is not communicated between the FDM128 and the other device.

                  Are the keypads (HMI's) 'plug-n-play'?

                  Issue:
                  Are the keypads (HMI's) 'plug-and-play'?

                  Product Line:
                  All Altivar drives

                  Environment:
                  All

                  Cause:
                  Would like to know if a drive will automatically detect and use a keypad when connected

                  Resolution:
                  Yes, the currently-used keypads with part numbers VW3A1101 and VW3A1111 are 'plug-n-play'. In other words, when you connect the appropriate keypad to an Altivar drive, the drive should automatically detect the keypad. The keypad's LCD screen should display the drive's information almost immediately when connected. This is whether the keypad is plugged directly into the front of the drive or connected by ModBus cable. 
                   
                         VW3A1101                                                     VW3A1111
                             



                   

                  Are EasyPact EZC or EZD circuit breakers for sale in the USA or Canada?

                  Product Line:
                  EasyPact EZC and EZD circuit breakers

                  Cause:
                  This breaker is popular overseas and there is interest in the US

                  Resolution:
                  There are no plans for a general release of the EasyPact EZC or EZD circuit breaker line in North America.

                  Can you use the M221 PLC's TMH2GDB keypad display on the ATV630 process drive?

                  Issue:
                  Can you use the M221 PLC's TMH2GDB keypad display on the ATV630 process drive?

                  Product Line:
                  Altivar ATV630

                  Environment:
                  All ATV630 drives

                  Cause:
                  Wants to know if the TMH2GD8 keypads will work on the ATV630 drives?

                  Resolution:
                  No the TMH2GDB keypad will not work on the ATV630 or any of the ATV drives.
                  The hardware is the same  as the VW3A1111 keypad but the firmware is not.  The firmware can not be updated either.
                   

                  Do the ATV630 and ATV930 Process Drives come with a keypad?

                  Issue:  
                  Do the ATV630 and ATV930 Process Drives come with a keypad?

                  Product Line:
                   Altivar Process 630, Altivar Process 930

                  Environment:
                   All part numbers

                  Cause:
                   Customer wants to know if the keypad is included or needs to be ordered separately.

                  Resolution:
                  YES, the drives come with a keypad.
                  The keypad can also be ordered separately if needed, part number is VW3A1111.

                  What keypad is compatible with the Altivar 320?

                  Issue:
                  What keypad is compatible with the Altivar 320?

                  Product Line:
                  Altivar 320

                  Environment:
                  All serial numbers for Altivar 320

                  Cause:
                  N/A

                  Resolution:
                  The Altivar 320 drive is compatible with the list of keypads:
                  • VW3A1111 (Altivar Process Drive keypad)
                  • VW3A1101 (Altivar 61/71)
                  • VW3A1006 (ATV312/32 keypad - IP54)
                  • VW3A1007 (ATV312/32 keypad - IP65)
                  The Altivar Process keypad requires mounting kit VW3A1112 (provides IP65).
                  The ATV61/71 keypad requires mounting kit VW3A1102 (provides for IP54, add VW3A1103 for IP65).

                  Cables must be ordered separately 
                  • VW3A1104R10 - 1 Meter Cable
                  • VW3A1104R30 - 3 Meter Cable
                  • VW3A1104R50 - 5 Meter Cable
                  • VW3A1104R100 - 10 Meter Cable

                  Is an MIB file necessary to utilize the SNMP feature available on the Ethernet Gateway (EGX), the Ethernet Communications Card (ECC) or Ethernet interface for Powerpact and Masterpact LV (IFE)?

                  Issue
                  End user would like to know if a MIB file is necessary for SNMP features.

                  Product Line
                  PowerLogic MIB devices
                  EGX100, EGX150, EGX200, EGX300, EGX400, ECC21, PM8ECC, PM556X
                  Enerlin'X Ethernet Interface IFE (LV434011 and LV434010)


                  Environment
                  SNMP enables easy viewing of data from any device in the network using common MIB browsers.  It can also incorporate MIB file data into other software or scripts.

                  Cause
                  SNMP can be use to provide information about the network interface(s) on a device.

                  Resolution
                  *Warning:  Installation and maintenance of these devices should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Failure to follow the instructions / warnings in the Meter Installation Guide can result in permanent damage to the meter, severe injury or death.

                  Certain PowerLogic ethernet gateways (EGX100, EGX150, EGX200, EGX300, EGX400), ethernet communication cards (ECC21) and breaker ethernet interfaces (IFE) only support the industry-standard MIB-II template. A device that supports the MIB-II template does not require an additional MIB file. Information is stored in the devices memory in MIB-II format. Keep in mind that the MIB-II standard does not supply alarming information from downstream devices, it is designed to deliver system information only such as IP address, UDP packet statistics, ICMP errors, etc. After SNMP is enabled,the MIB-II values are available to the SNMP server or requesting device.

                  The PM800 ethernet communication module (PM8ECC) supports SNMP V2 traps. This allows it to supply alarming information from downstream devices. This is the only PowerLogic device that allows for supplying information from downstream devices with SNMP. Once SNMP is enabled, a MIB template must be used to begin using SNMP to get values. The latest MIB template is available for download on
                  https://www.powerlogic.com/downloads.cfm/cs/1

                  The PM556X series supports SNMP supports alarming via traps for real-time notification without the need to poll devices on the network.

                  To start using SNMP, simply enable SNMP and fill-out the SNMP identification fields on the target device.

                  Show More