3P TM-D NSX100B- Compact circuit breaker
3P TM-D NSX160B- Compact circuit breaker
3P TM-D NSX160B- Compact circuit breaker
3P TM-D NSX100B- Compact circuit breaker
3P TM-D NSX160B- Compact circuit breaker
3P TM-D NSX160B- Compact circuit breaker

Compact NSX Circuit Breaker, TMD, 160A, 3 Poles 3d

Catalogue Number: LV430310
3P TM-D NSX100B- Compact circuit breaker
3P TM-D NSX160B- Compact circuit breaker
3P TM-D NSX160B- Compact circuit breaker
3P TM-D NSX100B- Compact circuit breaker
3P TM-D NSX160B- Compact circuit breaker
3P TM-D NSX160B- Compact circuit breaker
Retail
$2,082.31
RRP (Inc. GST)

Specifications

hide show
Range
Compact
Range of product
NSX100...250
Product name
Compact NSX
Product or component type
circuit breaker
Device short name
Compact NSX160B
Device application
distribution
Poles description
3P
Protected poles description
3t
Network type
AC
Network frequency
50/60 Hz
[In] rated current
160 A at 40 °C
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ue] rated operational voltage
690 V AC 50/60 Hz
Breaking capacity code
B 25 kA 415 V AC
Breaking capacity
  • 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
  • 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    • [Ics] rated service breaking capacity
    • 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    • 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    • 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    • 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
      • Suitability for isolation
      • yes conforming to EN 60947-2
      • yes conforming to IEC 60947-2
        • Utilisation category
          category A
          Trip unit name
          TM-D
          Trip unit technology
          thermal-magnetic
          Trip unit protection functions
          LI
          Pollution degree
          3 conforming to IEC 60664-1
          Control type
          toggle
          Mounting mode
          fixed
          Mounting support
          backplate
          Upside connection
          front
          Downside connection
          front
          Mechanical durability
          40000 cycles
          Electrical durability
        • 10000 cycles 440 V In/2 conforming to IEC 60947-2
        • 15000 cycles 690 V In/2 conforming to IEC 60947-2
        • 20000 cycles 440 V In conforming to IEC 60947-2
        • 7500 cycles 690 V In conforming to IEC 60947-2
          • Connection pitch
            35 mm
            Local signalling
            positive contact indication
            Protection type
          • L : for overload protection (thermal)
          • I : for short-circuit protection (magnetic)
            • Trip unit rating
              160-160 A at 40 °C
              Long time pick-up adjustment type Ir
              adjustable
              Long time pick-up adjustment range
              0.7...1 x In
              Long time delay adjustment type
              fixed
              [tr] long-time delay adjustment range
            • 120-400 s at 1.5 x In
            • 15-15 s at 6 x Ir
              • Short-time pick-up adjustment type Isd
                fixed
                [Isd] short-time pick-up adjustment range
                1250 A
                Short-time delay adjustment type
                fixed
                Height
                161 mm
                Width
                105 mm
                Depth
                86 mm
                Net weight
                2.2 kg
                Compatibility code
                NSX160
                Overvoltage category
                class II
                Electrical shock protection class
                class II
                Standards
                EN/IEC 60947
                Product certifications
              • EAC
              • Marine
              • CCC
                • IP degree of protection
                  IP40 conforming to IEC 60529
                  IK degree of protection
                  IK07 conforming to IEC 62262
                  Ambient air temperature for operation
                  -35-70 °C
                  Ambient air temperature for storage
                  -55-85 °C
                  Sustainable offer status
                  Green Premium product
                  REACh Regulation
                  Free of Substances of Very High Concern above the threshold
                  EU RoHS Directive
                  Compliant
                  Mercury free
                  Yes
                  RoHS exemption information
                  Yes
                  China RoHS Regulation
                  Product out of China RoHS scope. Substance declaration for your information
                  Environmental Disclosure
                  ENVPEP120606EN
                  Circularity Profile
                  ENVEOLI120604EN
                  WEEE
                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                  California proposition 65
                  WARNING: This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
                  Warranty
                  18 months

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Technical Data Catalogues

                  • Installation Instruction

                  • Operating Manuals

                  • Marine Certificate

                  • Declaration of Conformity

                  Frequently Asked Questions

                  hide show

                  Will the Compact NSX breaker be for sale in the USA or Canada?

                  Issue:
                  Where can I buy a Compact NSX breaker?

                  Product Line:
                  Circuit Breakers

                  Cause:
                  This breaker is popular overseas and there is interest in the US

                  Resolution:
                  There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

                  If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

                  For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
                  https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page

                  Are EasyPact CVS circuit breakers for sale in the USA or Canada?

                  Product Line:
                  EasyPact CVS circuit breakers

                  Cause:
                  This breaker is popular overseas and there is interest in the US

                  Resolution:
                  There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.

                  What is the motor trip unit needed for a LV430403 frame, 150A

                  Use a LV430500

                  will the LV429338 fit the LV430631 and the LV431630?

                              YES            ! The LV429338.....Extended rotary handle will fit the LV430631 or the LV431630 circuit breakers
                  see data sheet...
                  https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lv429338

                  What is the part code for 160A 36kA MCB

                   You can use LV430403 + Lv430430 + phase barriers / terminal shield

                  ETSNZ What is the IFE Model with Modbus Connection

                  The modbus equipped module is LV434011 as opposed to the ULP only  type = LV434010

                  What is a 3P 50kA MCCB with 125A trip unit and vigi block, would also need a 125Amp RCBO

                  Use a LV430406 - 160Amp frame + LV430431 125Amp trip unit + LV429211 Vigi module + LV431536 connector = 125Amp RCBO

                  What is part number for the overload , 112amp - 160amp , to suit LV430630?

                  The part number for the overload only with trip range of 112amp - 160amp for a NSX160F part number - LV430630 is a LV431432.

                  For further information and also other trip ranges for the NSX160F , please go to below link:

                  https://www.schneider-electric.com.au/en/search/LV431432User-added image

                  Can I discover and view Modbus devices when using the LV434010?

                  No, you will need to use the LV434011 to be able to discover and view dashboards on the modbus devices.

                  What is the replacement for NS160N with TM160D trip unit?

                  Replacement is NSX160F with TM160D trip unit # LV430630

                  Can LV432631 be locked in ON position?

                  Part number LV432631 can be locked in ON or OFF position.

                  What are the Parts required to make up an NSX250F Breaker with Micrologic 2.2 Trip Unit 160 Amps?

                  We can make it up with following two items:

                  Part number LV431403 - NSX250F Basic Frame
                  Part number LV430470 - Micrologic 2.2 Trip Unit 160 Amps

                   
                  Show More