Differential thermal overload relay LRD4 for TeSys D connection by screw clamp terminals or connectors, 3 poles, 80A to 140A, class 10A

TeSys LRD Thermal Overload Relays, 110...140A Class, 10A

Catalogue Number: LRD4369
Differential thermal overload relay LRD4 for TeSys D connection by screw clamp terminals or connectors, 3 poles, 80A to 140A, class 10A
Retail
$2,141.36
RRP (Inc. GST)

Specifications

hide show
Range
TeSys
Product name
TeSys LRD
Product or component type
differential thermal overload relay
Device short name
LRD
Relay application
motor protection
Product compatibility
LC1D150
Network type
  • DC
  • AC
    • Thermal protection adjustment range
      110-140 A
      [Ui] rated insulation voltage
      power circuit: 1000 V conforming to IEC 60947-4-1
      Network frequency
      0...400 Hz
      Mounting support
    • plate, with specific accessories
    • rail, with specific accessories
    • under contactor
      • Tripping threshold
        1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
        [Ith] conventional free air thermal current
        5 A for signalling circuit
        Permissible current
      • 0.06 A at 440 V DC-13 for signalling circuit
      • 0.12 A at 600 V AC-15 for signalling circuit
        • [Ue] rated operational voltage
          690 V AC 0...400 Hz
          [Uimp] rated impulse withstand voltage
          Phase failure sensitivity
          tripping current 130 % of Ir on two phase, the last one at 0
          Control type
        • red push-button: stop
        • blue push-button: reset
          • Temperature compensation
            -20-60 °C
            Connections - terminals
          • power circuit: screw clamp terminals 1 cable(s) 4-35 mm² flexible with cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible with cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² solid without cable end
          • power circuit: screw clamp terminals 1 cable(s) 4-50 mm² flexible without cable end
          • power circuit: screw clamp terminals 1 cable(s) 4-50 mm² solid without cable end
            • Tightening torque
            • control circuit: 1.7 N.m - on screw clamp terminals
            • power circuit: 9 N.m - on screw clamp terminals
              • Depth
                132 mm
                Net weight
                0.9 kg
                Compatibility code
                LRD
                Protective treatment
                TH conforming to IEC 60068
                IP degree of protection
                IP20 conforming to IEC 60529
                Ambient air temperature for operation
                -20-60 °C without derating conforming to IEC 60947-4-1
                Ambient air temperature for storage
                -60-70 °C
                Flame retardance
                V1 conforming to UL 94
                Mechanical robustness
              • vibrations: 6 Gn conforming to IEC 60068-2-6
              • shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
                • Dielectric strength
                  6 kV at 50 Hz conforming to IEC 60255-5
                  Standards
                • UL 508
                • CSA C22.2 No 14
                • ATEX D 94/9/CE
                • IEC 60947-4-1
                • EN 60947-4-1
                • IEC 60947-5-1
                • EN 60947-5-1
                  • Product certifications
                  • RINA
                  • LROS (Lloyds register of shipping)
                  • BV
                  • GOST
                  • DNV
                  • ATEX INERIS
                  • CCC
                  • GL
                    • Unit Type of Package 1
                      PCE
                      Number of Units in Package 1
                      1
                      Package 1 Weight
                      844 g
                      Package 1 Height
                      11 cm
                      Package 1 width
                      13.5 cm
                      Package 1 Length
                      15.5 cm
                      Sustainable offer status
                      Green Premium product
                      REACh free of SVHC
                      Yes
                      EU RoHS Directive
                      Compliant
                      Toxic heavy metal free
                      Yes
                      Mercury free
                      Yes
                      RoHS exemption information
                      Yes
                      China RoHS Regulation
                       Pro-active China RoHS declaration (out of China RoHS legal scope)
                      Environmental Disclosure
                      ENVPEP110101EN
                      Circularity Profile
                      ENVEOLI1101001EN
                      Warranty
                      18 months

                      Documents & downloads

                      hide show
                      Filter items
                      • All

                      • Product Brochures

                      • CAD Files and Packs

                      • Technical Data Catalogues

                      • Installation Instruction

                      • End of Life Manual

                      • Product Environmental

                      • Certificates (MSDS)

                      • Declaration of Conformity

                      Frequently Asked Questions

                      hide show

                      What are the wiring terminals on the IEC LRD* overload relays?

                      Product Line:
                      Tesys D line Overload Relays
                       
                      Resolution:
                      The normally closed overload contact are terminals 95 & 96; and the normally open overload contact are terminals 97 & 98.
                      T1 T2 and T3 are the load terminals. 

                      The normally closed control circuit contact will open when there is a fault, this contact is typically used in series with the control circuit. 

                      The normally open trip signal contact closes when a fault occurs which is typically used to control a pilot light, or alarm. 

                       

                      Is the LR9D5369 overload still available

                       Yes it is

                      What is the reference for the separate mounting kit for LRD4369 overload relay

                      The LRD43xx type of thermal overload relays are directly mounted to the contactors LC1D115 & LC1D150 only. There is no separate mounting kit for the LRD43xx.

                      If a separate mounting is required for the contactors LC1D115 or LC1D150 type, then LRD336xx shall be selected as these range of overload relays have indepentdent mounting and have similar setting range and are of Class 10A.

                      What overload to suit LC1D95U7 need to be 80-104A

                       Part code for the overload LRD3365

                      How to use LRD01…35 LRD33•• & LRD43•• and LRD33** as an indepentent relay?

                      The LRD relays has a solid tag to be used with LC1D** contactors. If you are not using LC1D contactors then using the following accessories you can terminate cable directly.

                      For LRD01…35 use the following part: LAD7B106
                      For LRD33•• & LRD43•• (3) use the following part: LA7D3064

                      What overload can be used with an LC1D65AU7?

                      You can use the Everlink range which is LRD313 - LRD365

                      What is the replacement for the old thermal overload relay LR2D3359?

                      The part number is as follows: LRD365

                      What is the overload for the LR2D Everlink range 23-32 Amps?

                      The correct code is LRD332.

                      How Can the LC1D50AU7 Contactor be mounted?

                      Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                      See the attached datasheet for further information.

                      What is difference between LC1D50U7 and LC1D50AU7?

                      Following are the differences between the LC1D50U7 and the LC1D50AU7:

                      LC1D50AU7 has everlink terminals.
                      LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                      Whereas
                      LC1D50U7 contactors accommodate LRD33XX overloads.

                       

                      Will the Compact NSX breaker be for sale in the USA or Canada?

                      Issue:
                      Where can I buy a Compact NSX breaker?

                      Product Line:
                      Circuit Breakers

                      Cause:
                      This breaker is popular overseas and there is interest in the US

                      Resolution:
                      There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

                      If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

                      For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
                      https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page

                      What is the part number of a 23A -32A overload to fit LC1D40U7 contactor?

                      LRD3353 is a 23A -32A overload to fit LC1D40U7 contactor. 
                      For further information, please visit https://www.schneider-electric.com/en/product/LRD3353/tesys-lrd-thermal-overload-relays---23...32-a---class-10a



                       