Quantcast

TeSys LRD Thermal Overload Relays, 48...65A Class, 10A

Product Dimensions

Width icon

Width55 mm

Height icon

Height70 mm

Depth icon

Depth123 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

differential thermal overload relay

Product compatibility

  • LC1D65A
  • LC1D50A
    • Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      Mounting support

    • plate, with specific accessories
    • rail, with specific accessories
    • under contactor
      • [Ue] rated operational voltage

        690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1

        Control type

      • red push-button: stop
      • blue push-button: reset
        • Connections - terminals

        • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible without cable end
        • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible with cable end
        • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² solid without cable end
        • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm² flexible without cable end
        • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm² flexible with cable end
        • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm² solid without cable end
          • Height

            70 mm

            Width

            55 mm

            Depth

            123 mm

            Net weight

            0.375 kg

            IP degree of protection

            IP20 conforming to IEC 60529

            Ambient air temperature for operation

            -20-60 °C without derating conforming to IEC 60947-4-1

            Ambient air temperature for storage

            -60-70 °C

            Standards

          • EN/IEC 60947-4-1
          • EN/IEC 60947-5-1
          • UL 60947-4-1
          • UL 60947-5-1
          • CSA C22.2 No 60947-4-1
          • CSA C22.2 No 60947-5-1
          • GB/T 14048.4
          • GB/T 14048.5
          • EN 50495
            • Product certifications

            • IEC
            • UL
            • CSA
            • CCC
            • EAC
            • DNV-GL
            • RMRS
            • EU-RO MR
            • LROS (Lloyds register of shipping)
            • ATEX INERIS
            • UKCA
              • REACh Regulation

                Free of Substances of Very High Concern above the threshold

                REACh free of SVHC

                Yes

                EU RoHS Directive

                Compliant

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                 Pro-active China RoHS declaration (out of China RoHS legal scope)

                Environmental Disclosure

                ENVPEP080405EN

                Circularity Profile

                ENVEOLI0804005_V1

                California proposition 65

                WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

                Others

                Product name

                TeSys LRD

                Device short name

                LRD

                Relay application

                motor protection

                Network type

              • DC
              • AC
                • Thermal overload class

                  class 10A conforming to IEC 60947-4-1

                  Thermal protection adjustment range

                  48-65 A

                  [Ui] rated insulation voltage

                • power circuit: 600 V conforming to CSA
                • power circuit: 600 V conforming to UL
                • power circuit: 690 V conforming to IEC 60947-4-1
                  • Network frequency

                    0...400 Hz

                    Tripping threshold

                    1.14 +/- 0.06 Ir conforming to IEC 60947-4-1

                    Auxiliary contact composition

                    1 NO + 1 NC

                    [Ith] conventional free air thermal current

                    5 A for signalling circuit

                    Permissible current

                  • 0.95 A at 380 V AC-15 for signalling circuit
                  • 0.06 A at 440 V DC-13 for signalling circuit
                    • Associated fuse rating

                    • 4 A gG for signalling circuit
                    • 4 A BS for signalling circuit
                      • [Uimp] rated impulse withstand voltage

                        Phase failure sensitivity

                        tripping current 130 % of Ir on two phase, the last one at 0

                        Temperature compensation

                        -20-60 °C

                        Tightening torque

                      • control circuit: 1.7 N.m - on screw clamp terminals
                      • power circuit: 5 N.m - on EverLink BTR screw connectors
                        • Compatibility code

                          LRD

                          Protective treatment

                          TH conforming to IEC 60068

                          Flame retardance

                          V1 conforming to UL 94

                          Mechanical robustness

                        • shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
                        • vibrations: 4 gn conforming to IEC 60068-2-6
                          • Dielectric strength

                            1.89 kV at 50 Hz conforming to IEC 60947-1

                            Unit Type of Package 1

                            PCE

                            Number of Units in Package 1

                            1

                            Package 1 Weight

                            394 g

                            Package 1 Height

                            6.2 cm

                            Package 1 width

                            10.4 cm

                            Package 1 Length

                            13.6 cm

                            Unit Type of Package 2

                            S02

                            Number of Units in Package 2

                            13

                            Package 2 Weight

                            5.453 kg

                            Package 2 Height

                            15 cm

                            Package 2 width

                            30 cm

                            Package 2 Length

                            40 cm

                            Unit Type of Package 3

                            P06

                            Number of Units in Package 3

                            208

                            Package 3 Weight

                            97.732 kg

                            Package 3 Height

                            77 cm

                            Package 3 width

                            60 cm

                            Package 3 Length

                            80 cm
                            Show all specifications

                            Documents & downloads

                            hide show
                            Filter items
                            • All

                            • CAD Files and Packs

                            • Product Brochures

                            • Technical Data Catalogues

                            • End of Life Manual

                            • Installation Instruction

                            • Handout

                            • Product Environmental

                            • Certificates (MSDS)

                            • Declaration of Conformity

                            Frequently Asked Questions

                            hide show

                            What is the part code for the contactor and overload that replaced the LR1D63359

                             The part codes are LC1D65A**  +  LRD365
                            where ** refer to coil voltage.

                            What is the difference between the LA7D305 and LAD7305, remote control reset mechanism by flexible cable?

                            Issue:
                             LA7D305 and LAD7305 Difference

                            Product Line:
                            IEC contactors and starters

                            Environment:
                            LRD Accessories

                            Cause:
                            Choosing the correct part number

                            Resolution:
                            LAD7305 is for use on LRD01 to LRD35 , LR3D01 to LR3D35, and LRD313 to LRD365.
                            LA7D305 is for use on all other relays (except LRD01 to LRD35 and LR3D01 to LR3D35).