Specifications

hide show
Range
TeSys
Product name
TeSys LRD
Product or component type
differential thermal overload relay
Device short name
LRD
Relay application
motor protection
Product compatibility
  • LC1D65A
  • LC1D50A
    • Network type
    • DC
    • AC
      • Thermal protection adjustment range
        48-65 A
        [Ui] rated insulation voltage
      • power circuit: 600 V conforming to CSA
      • power circuit: 600 V conforming to UL
      • power circuit: 690 V conforming to IEC 60947-4-1
        • Network frequency
          0...400 Hz
          Mounting support
        • plate, with specific accessories
        • rail, with specific accessories
        • under contactor
          • Tripping threshold
            1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
            [Ith] conventional free air thermal current
            5 A for signalling circuit
            Permissible current
          • 0.95 A at 380 V AC-15 for signalling circuit
          • 0.06 A at 440 V DC-13 for signalling circuit
            • [Ue] rated operational voltage
              690 V AC 0...400 Hz
              [Uimp] rated impulse withstand voltage
              Phase failure sensitivity
              tripping current 130 % of Ir on two phase, the last one at 0
              Control type
            • red push-button: stop
            • blue push-button: reset
              • Temperature compensation
                -20-60 °C
                Connections - terminals
              • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible with cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² solid without cable end
              • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm² flexible without cable end
              • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm² flexible with cable end
              • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm² solid without cable end
                • Tightening torque
                • control circuit: 1.7 N.m - on screw clamp terminals
                • power circuit: 5 N.m - on EverLink BTR screw connectors
                  • Height
                    70 mm
                    Width
                    55 mm
                    Depth
                    123 mm
                    Net weight
                    0.375 kg
                    Compatibility code
                    LRD
                    Protective treatment
                    TH conforming to IEC 60068
                    IP degree of protection
                    IP20 conforming to IEC 60529
                    Ambient air temperature for operation
                    -20-60 °C without derating conforming to IEC 60947-4-1
                    Ambient air temperature for storage
                    -60-70 °C
                    Flame retardance
                    V1 conforming to UL 94
                    Mechanical robustness
                  • shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
                  • vibrations: 4 gn conforming to IEC 60068-2-6
                    • Dielectric strength
                      6 kV at 50 Hz conforming to IEC 60255-5
                      Standards
                    • IEC 60947-4-1
                    • CSA C22.2 No 14
                    • EN 60947-4-1
                    • ATEX D 94/9/CE
                    • EN 60947-5-1
                    • IEC 60947-5-1
                    • UL 508
                      • Product certifications
                      • RINA
                      • GOST
                      • LROS (Lloyds register of shipping)
                      • ATEX INERIS
                      • UL
                      • BV
                      • DNV
                      • CSA
                      • CCC
                      • GL
                        • Sustainable offer status
                          Green Premium product
                          REACh Regulation
                          Free of Substances of Very High Concern above the threshold
                          REACh free of SVHC
                          Yes
                          EU RoHS Directive
                          Compliant
                          Toxic heavy metal free
                          Yes
                          Mercury free
                          Yes
                          RoHS exemption information
                          Yes
                          China RoHS Regulation
                          X
                          Environmental Disclosure
                          ENVPEP080405EN
                          Circularity Profile
                          ENVEOLI0804005_V1
                          California proposition 65
                          WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                          Warranty
                          18 months

                          Documents & downloads

                          hide show
                          Filter items
                          • All

                          • CAD Files and Packs

                          • Product Brochures

                          • Movies

                          • Technical Data Catalogues

                          • Technical Leaflet

                          • Handout

                          • End of Life Manual

                          • Product Environmental

                          • Installation Instruction

                          • Data Bulletin

                          • Operating Manuals

                          • Certificates (MSDS)

                          • Declaration of Conformity

                          • White Paper

                          • Marine Certificate

                          Frequently Asked Questions

                          hide show

                          What are the wiring terminals on the IEC LRD* overload relays?

                          Product Line:
                          Tesys D line Overload Relays
                           
                          Resolution:
                          The normally closed overload contact are terminals 95 & 96; and the normally open overload contact are terminals 97 & 98.
                          T1 T2 and T3 are the load terminals. 

                          The normally closed control circuit contact will open when there is a fault, this contact is typically used in series with the control circuit. 

                          The normally open trip signal contact closes when a fault occurs which is typically used to control a pilot light, or alarm. 

                           

                          What overload can be used with an LC1D65AU7?

                          You can use the Everlink range which is LRD313 - LRD365

                          What is the replacement for the old thermal overload relay LR2D3359?

                          The part number is as follows: LRD365

                          What overload to suit LC1D95U7 need to be 80-104A

                           Part code for the overload LRD3365

                          What is the difference between the LA7D305 and LAD7305, remote control reset mechanism by flexible cable?

                          Issue:
                          Identifying differences between two similar part numbers.

                          Product Line:
                          IEC contactors and starters

                          Environment:
                          Products sold and used in the United States

                          Cause:
                          Choosing the correct part number

                          Resolution:
                          LAD7305 is for use on LRD01 to LRD35 , LR3D01 to LR3D35, and LRD313 to LRD365.
                          LA7D305 is for use on all other relays (except LRD01 to LRD35 and LR3D01 to LR3D35).

                           

                          What is the Din rail terminal block to suit the LRD12?

                          The LAD7B106 fits the LRD01 to LRD35 range.
                           

                          What is the Overload for LC1D50AU7 range is 37..50 Amps?

                          LRD350

                          What is the part number for a class 20 version of the LRD340

                           The part code LRD340L

                          What is the setting range for an LRD350

                           The setting range is  37 - 50A

                          Can the LRD01 to LRD35 range be put back to manual from automatic.

                          This LRD range cannot be put back to Manual reset, once the overlaod has been changed from Manual (factory default) to Automatic.

                          Will the LR3D325 overload relay fit a LC1D65G7 contactor?

                          Issue:
                          Will the LC1D65G7 mount to the LR3D325 overload relay?

                          Product Line:
                          IEC contactors and starters

                          Environment:
                          Products sold and used in the United States

                          Cause:
                          Identifying product compatibility

                          Resolution:
                          No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


                          CTA-ID : 2050461

                          What is the difference between LAD703 and LA7D03

                          Issue:
                          Identifying differences between two similar part numbers

                          Product Line:
                          IEC contactors and starters

                          Environment:
                          Products sold and used in the United States

                          Cause:
                          Identifying differences between two similar part numbers

                          Resolution:
                          Both will remotely stop (trip) or electrically reset the overload, however;
                          LAD703 is used on Tesys overload LRD01 through LRD35 and LR3D01 to LR3D35.
                          LA7D03 is used on all other LR*D overload relays other than LRD01 to LRD35 and LR3D01 to LR3D35.


                           

                          How Can the LC1D50AU7 Contactor be mounted?

                          Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                          See the attached datasheet for further information.

                          What is difference between LC1D50U7 and LC1D50AU7?

                          Following are the differences between the LC1D50U7 and the LC1D50AU7:

                          LC1D50AU7 has everlink terminals.
                          LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                          Whereas
                          LC1D50U7 contactors accommodate LRD33XX overloads.

                           

                          What is the part number of a 23A -32A overload to fit LC1D40U7 contactor?

                          LRD3353 is a 23A -32A overload to fit LC1D40U7 contactor. 
                          For further information, please visit https://www.schneider-electric.com/en/product/LRD3353/tesys-lrd-thermal-overload-relays---23...32-a---class-10a



                           

                          Is there a LE1M35N705 alternative or can coil be swapped out

                           The part codes you need is LE1D12N7 + LRD06

                          What is the alternative for the PDL Thermal Overload 56T9092 ?

                           The alternative is LRD05 (Note - these are not direct replacements)

                          What is the part code for a Thermal Overload 9-13A

                          The part code is LRD16 overload

                          What is the part code for a DOL 1P 240V AC Coil 4kW 9A, with 10-12A overload

                          Use a PDL56DOL9LOBGY and a LRD16 overload.

                          What is the reference for the separate mounting kit for LRD4369 overload relay

                          The LRD43xx type of thermal overload relays are directly mounted to the contactors LC1D115 & LC1D150 only. There is no separate mounting kit for the LRD43xx.

                          If a separate mounting is required for the contactors LC1D115 or LC1D150 type, then LRD336xx shall be selected as these range of overload relays have indepentdent mounting and have similar setting range and are of Class 10A.

                          What D-line overload relays use the LA7D3064 separate mounting kit?

                          Issue
                          What D-line overload relays use the LA7D3064 separate mounting kit?

                          Product Line
                          Overload relay

                          Environment
                          Tesys and Pre Tesys D-line

                          Cause
                          Fit, compatibility, and product features 

                          Resolution
                          The LRD3***   LR3D3**, LR2D35** D-line overload relays.

                          What is the overload to suit LE3D12N7 star delta starter?

                          Overload to suit LE3D12N7 will be either LRD12, LRD14 or LRD16 depending on application.

                          What is the alternative for PDL56T9120 overload?

                          The alternative is LRD16 but this will not fit the contactor in the 56 series starter as it is for the LC1D range of contactors. The PDL56T9120 is no longer available.
                          The new range of 56 series starters, 56DOL, have LC1D contactors and LRD overloads (not fitted).

                          What is the replacement for a Clipsal 6CTR38/15?

                          This is part of the old Clipsal 6 series contactors which are no longer available .It is an old Clipsal overload, which would need to be changed over to a Schneider LC1D range contactor with overload to suit . Over load to use is either LRD21 for 12-18A or LRD16 for 9-13A

                          For correct selection of contactor and overload required please call Schneider Electric on 1300 369 233