4P Contactor

Product Dimensions

Width icon

Width96 mm

Height icon

Height127 mm

Depth icon

Depth196 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 1000 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

      125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

      Electrical durability

      0.8 Mcycles 125 A AC-1 at Ue <= 440 V

      Mounting support

    • rail
    • plate
      • Standards

      • CSA C22.2 No 14
      • EN 60947-4-1
      • EN 60947-5-1
      • IEC 60947-4-1
      • IEC 60947-5-1
      • UL 508
        • Product certifications

        • BV
        • CCC
        • CSA
        • DNV
        • EAC
        • GL
        • LROS (Lloyds register of shipping)
        • UL
          • Connections - terminals

          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
          • power circuit: connector 1 cable(s) 4-50 mm²flexible without cable end
          • power circuit: connector 2 cable(s) 4-25 mm²flexible without cable end
          • power circuit: connector 1 cable(s) 4-50 mm²flexible with cable end
          • power circuit: connector 2 cable(s) 4-16 mm²flexible with cable end
          • power circuit: connector 1 cable(s) 4-50 mm²solid
          • power circuit: connector 2 cable(s) 4-25 mm²solid
          • control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
            • Mechanical durability

              4 Mcycles

              IP degree of protection

              IP20 front face conforming to IEC 60529

              Ambient air temperature for operation

            • -40-60 °C
            • 60-70 °C with derating
              • Ambient air temperature for storage

                -60-80 °C

                Height

                127 mm

                Width

                96 mm

                Depth

                196 mm

                Net weight

                2.91 kg

                REACh free of SVHC

                Yes

                EU RoHS Directive

                Compliant

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                 Pro-active China RoHS declaration (out of China RoHS legal scope)

                Environmental Disclosure

                ENVPEP110205EN

                Others

                Product name

                TeSys D

                Device short name

                LP1D

                Contactor application

                resistive load

                Utilisation category

                AC-1

                Poles description

                4P

                Pole contact composition

                2 NO + 2 NC

                Control circuit type

                DC wide range

                [Uc] control circuit voltage

                48 V DC

                Coil type

                wide range

                [Uimp] rated impulse withstand voltage

                8 kV conforming to IEC 60947

                Overvoltage category

                III

                [Ith] conventional free air thermal current

                125 A (at 60 °C) for power circuit

                Irms rated making capacity

                1100 A at 440 V for power circuit conforming to IEC 60947

                Rated breaking capacity

                1100 A at 440 V for power circuit conforming to IEC 60947

                [Icw] rated short-time withstand current

              • 135 A 40 °C - 10 min for power circuit
              • 320 A 40 °C - 1 min for power circuit
              • 640 A 40 °C - 10 s for power circuit
              • 990 A 40 °C - 1 s for power circuit
                • Associated fuse rating

                • 200 A gG at <= 690 V coordination type 1 for power circuit
                • 160 A gG at <= 690 V coordination type 2 for power circuit
                  • Average impedance

                    0.8 mOhm - Ith 125 A 50 Hz for power circuit

                    [Ui] rated insulation voltage

                  • power circuit: 600 V CSA certified
                  • power circuit: 600 V UL certified
                  • power circuit: 1000 V conforming to IEC 60947-4-1
                    • Power dissipation per pole

                      12.5 W AC-1

                      Protective cover

                      without

                      Tightening torque

                    • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                    • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
                    • power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
                    • power circuit: 12 N.m - on connector hexagonal screw head 4 mm
                      • Operating time

                      • 6...20 ms opening
                      • 20...35 ms closing
                        • Safety reliability level

                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                          • Maximum operating rate

                            3600 cyc/h 60 °C

                            Coil technology

                            without built-in suppressor module

                            Control circuit voltage limits

                          • 0.1...0.3 Uc (-40-70 °C):drop-out DC
                          • 0.75...1.2 Uc (-40-55 °C):operational DC
                          • 1...1.2 Uc (55-70 °C):operational DC
                            • Time constant

                              75 ms

                              Inrush power in W

                              22-22 W at 20 °C

                              Hold-in power consumption in W

                              22-22 W at 20 °C

                              Contact compatibility

                              M4

                              Compatibility code

                              LP1D

                              Protective treatment

                              TH conforming to IEC 60068-2-30

                              Pollution degree

                              3

                              Operating altitude

                              0...3000 m

                              Fire resistance

                              850 °C conforming to IEC 60695-2-1

                              Flame retardance

                              V1 conforming to UL 94

                              Mechanical robustness

                            • vibrations contactor open: 2 Gn, 5...300 Hz
                            • vibrations contactor closed: 3 Gn, 5...300 Hz
                            • shocks contactor open: 8 Gn for 11 ms
                            • shocks contactor closed: 10 Gn for 11 ms
                              • Package 1 Weight

                                2.857 kg

                                Package 1 Height

                                1.4 dm

                                Package 1 width

                                1.1 dm

                                Package 1 Length

                                2.05 dm

                                WEEE

                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                PVC free

                                Yes
                                Show all specifications

                                Documents & downloads

                                hide show
                                Filter items
                                • All

                                • Product Brochures

                                • Technical Data Catalogues

                                • Product Environmental

                                • Certificates (MSDS)

                                • Declaration of Conformity

                                Frequently Asked Questions

                                hide show

                                What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                Issue:
                                Identifying power terminal lug data for the D2 style contactors

                                Product Line:
                                IEC Contactors and Starters

                                Environment:
                                Tesys D line contactors

                                Cause:
                                Power terminal lug data required

                                Resolution:
                                For contactors with screw clamp terminals:
                                stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                Issue:
                                Identifying maximum voltage of an LC1D contactor

                                Product Line:
                                TeSys D Contactors

                                Environment:
                                IEC contactors and starters used in North America

                                Cause:
                                n/a

                                Resolution:
                                IThe maximum voltage per UL and CSA is 600VAC. 
                                 

                                Are the D-Line contactors rated to break DC voltages?

                                Issue: 
                                Can the TeSys D line be used to control DC loads? 

                                Product Line:
                                Tesys D contactors

                                Environment:
                                Products sold and used in the United States
                                 
                                Cause:
                                 DC power circuit
                                 
                                Resolution:
                                 
                                Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                Devices are suitable but not UL Listed for DC applications.

                                More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                 

                                Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                Issue:
                                Auxiliary contact modules for the LC1D and LC2D contactors

                                Product Line: 
                                Contactor and Starters - IEC

                                Environment:
                                North American Products

                                Resolution:
                                Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                Front Mounting; maximum of 1 block per contactor:

                                N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                --1-----------1---------LADN11-----------LA1DN11
                                --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                --2-----------0---------LADN20-----------LA1DN20
                                --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                --0-----------2---------LADN02-----------LA1DN02
                                --2-----------2---------LADN22-----------LA1DN22
                                --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                --3-----------1---------LADN31------------LA1DN31
                                --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                --1-----------3---------LADN13------------LA1DN13
                                --4-----------0---------LADN40------------LA1DN40
                                --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                --0-----------4---------LADN04------------LA1DN04




                                Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                --1-----------0--------LADN10----------LA1DN10
                                --0-----------1--------LADN01----------LA1DN01

                                Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                --1-----------1--------LAD8N11----------LA8DN11
                                --2-----------0--------LAD8N20----------LA8DN20
                                --0-----------2--------LAD8N02----------N/A

                                Footnotes:
                                {1} EN50 012 Machine Tool Terminal Markings
                                {2} (2) NO Sealed Dust Tight Contacts
                                {3} Gold Flash Contacts
                                {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                What is the color scheme of the Tesys D-Line contactors?

                                Issue:
                                Looking for different color scheme of the Tesys D-Line contactors.

                                Product Line:
                                Tesys D Contactors

                                Environment:
                                LC1D contactors

                                Resolution:
                                Beige and dark gray.
                                 

                                What are the stand alone short circuit current ratings on the LC1D** contactors?

                                Issue:
                                Tesys D SCCR

                                Product Line:
                                Contactors and Overload Relays

                                Environment:
                                TeSys™ D Contactors and Overload Relays
                                 
                                Resolution:
                                The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                They are as follows:
                                Horsepower SCCR (A)

                                0 thru 1 1,000
                                1 thru 50 5,000
                                51 thru 200 10,000
                                201 thru 400 18,000
                                401 thru 600 30,000
                                601 thru 900 42,000
                                901 thru 1600 85,000
                                1601+ 100,000
                                Show More