Enclosed star-delta starter LE3D without isolating device, with green Start button

TeSys LE Enclosed Star-Delta Starter, 18A, 415VAC Coil

Catalogue Number: LE3D18N7
Enclosed star-delta starter LE3D without isolating device, with green Start button
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
TeSys
Product name
TeSys LE
Device short name
LE3D
Product or component type
enclosed star-delta starter
Device application
standard
Material
polycarbonate
Utilisation category
AC-3
Device composition
  • thermal overload relay ordered separately
  • star-delta contactors
  • mechanical interlock
    • [Ie] rated operational current
      18 A AC-3
      Motor power kW
    • 11 kW at 220 V AC 50/60 Hz
    • 22 kW at 415 V AC 50/60 Hz
    • 22 kW at 440 V AC 50/60 Hz
    • 18.5 kW at 380/400 V AC 50/60 Hz
      • [Uc] control circuit voltage
        415 V AC 50/60 Hz
        Control type
      • push-button start green I
      • push-button stop/reset red O
        • Connections - terminals
        • power circuit: screw clamp terminals
        • control circuit: screw clamp terminals
          • Cable entry number
          • 2 ISO20 top
          • 2 ISO25 top
          • 2 ISO32 top
          • 2 ISO40 top
          • 2 ISO20 bottom
          • 2 ISO25 bottom
          • 2 ISO32 bottom
          • 2 ISO40 bottom
            • Width
              186 mm
              Height
              348 mm
              Depth
              175.5 mm
              Net weight
              3.75 kg
              Compatibility code
              LE3D
              IP degree of protection
              IP65 conforming to IEC 60529
              IK degree of protection
              IK07 conforming to IEC 60529
              Standards
              IEC 60947-4-1
              Ambient air temperature for operation
              -5-40 °C
              Environmental characteristic
              standard environment
              Sustainable offer status
              Green Premium product
              REACh Regulation
              Free of Substances of Very High Concern above the threshold
              REACh free of SVHC
              Yes
              EU RoHS Directive
              Compliant
              Toxic heavy metal free
              Yes
              Mercury free
              Yes
              RoHS exemption information
              Yes
              China RoHS Regulation
              X
              Environmental Disclosure
              ENVPEP111273EN
              WEEE
              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Warranty
              18 months

              Frequently Asked Questions

              hide show

              What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

              Issue:
              Identifying replacement coils for tesys D non-reversing and reversing conactors

              Product Line:
              IEC Contactors and Starters

              Environment:
              Products sold and used in the United States

              Cause:
              Replacement coil is needed

              Resolution:
              DC replacement coils are not available.
              AC Coils are 50/60 hertz for voltages as listed below:

              Volts - Part Number
              12 ____ LXD1J7
              21 ____ LXD1Z7
              24 ____ LXD1B7
              32 ____ LXD1C7
              36 ____ LXD1CC7
              42 ____ LXD1D7
              48 ____ LXD1E7
              60 ____ LXD1EE7
              100 ___ LXD1K7 ( never brought to North America )
              110 ___ LXD1F7
              115 ___ LXD1FE7
              120 ___ LXD1G7
              127 ___ LXD1FC7
              200 ___ LXD1L7
              208 ___ LXD1LE7
              220 ___ LXD1M7
              230 ___ LXD1P7
              240 ___ LXD1U7
              277 ___ LXD1W7
              380 ___ LXD1Q7
              400 ___ LXD1V7
              415 ___ LXD1N7
              440 ___ LXD1R7
              480 ___ LXD1T7
              575 ___ LXD1SC7
              600 ___ LXD1X7
              690 ___ LXD1Y7


              Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

              Is part number LE3D12N7 available with latching on button?

              No part number LE3D12N7 does not have latching push button.

              Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

              Issue:
              Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

              Product Line: 
              Tesys D Contactors

              Environment:
              IEC contactors

              Resolution:
              The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
               

              What is the overload to suit LE3D12N7 star delta starter?

              Overload to suit LE3D12N7 will be either LRD12, LRD14 or LRD16 depending on application.

              What is the plastic arm for LE1D18U7 stop button

              Part code LAD91810

              What replaces a LC1D18M7

              Use the LC1D18U7

              Contactor LE1D18N7 does it come with overload ?

               No - Overloads can be ordered separatly depending on the current rating required
               

              What is the replacement base for a LE1D12N7

              The base is not available on it's own but a replacement enclosure including base is a DE1DS1

              Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

              Issue:  
              Tesys D enclosed starter with a DC control 

              Product Line:
               Enclosed Tesys D line starters

              Environment:
              North American Products
               
              Cause:
              DC control circuit 
               
              Resolution:
              Yes but limited to 24 VDC.

              What is the part number for a DOL starter for 7.5kW load with 415VAC coil and overload for 16amps?

              The part number for a DOL starter for 7.5kW load with overload for 16amps is - LE1D18N7 & LRD21

              For further information , visit link below:-
              https://www.schneider-electric.com.au/en/search/LE1D18N7
              https://www.schneider-electric.com.au/en/search/LRD21
               

              What is the altitude derating for a TeSys D-Line contactor?

              Issue:​
              What is the altitude derating for a TeSys D-Line contactor?

              Product Line:
              Digest 177 Section 18 : Contactors and Starters, IEC

              Environment:
              North American Products

              Resolution:
              The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

              Voltage
              3500m x 0.90
              4000m x 0.80
              4500m x 0.70
              5000m x 0.60

              Current
              3500m x 0.92
              4000m x 0.90
              4500m x 0.88
              5000m x 0.86

              For example, an LC1D80 at 5000 meters:
              - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
              - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



               

              What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

              Issue:
              Identifying maximum voltage of an LC1D contactor

              Product Line:
              TeSys D Contactors

              Environment:
              IEC contactors and starters used in North America

              Cause:
              n/a

              Resolution:
              IThe maximum voltage per UL and CSA is 600VAC. 
               
              Show More