Enclosed Starter

Product Dimensions

Width icon

Width101 mm

Height icon

Height201 mm

Depth icon

Depth160 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

enclosed DOL reversing starter

Device application

standard

Physical

[Ie] rated operational current

35 A AC-3

Control type

  • push-button stop/reset red O
  • selector switch 2 positions start I-II
    • Width

      101 mm

      Height

      201 mm

      Depth

      160 mm

      Net weight

      4.1 kg

      IP degree of protection

      IP65 conforming to IEC 60529

      IK degree of protection

      IK07 conforming to IEC 60529

      Standards

      IEC 60947-4-1

      Ambient air temperature for operation

      -5-40 °C

      Environmental characteristic

      standard environment

      Material

      Device composition

    • thermal overload relay ordered separately
    • reversing contactor
      • Material

        polycarbonate

        Others

        Product name

        TeSys LE

        Device short name

        LE2D

        Utilisation category

        AC-3

        Motor power kW

      • 15 kW at 380/400 V AC 50/60 Hz
      • 15 kW at 415 V AC 50/60 Hz
      • 15 kW at 440 V AC 50/60 Hz
      • 7.5 kW at 220/230 V AC 50/60 Hz
      • 18.5 kW at 500 V AC 50/60 Hz
      • 18.5 kW at 660/690 V AC 50/60 Hz
        • [Ithe] conventional enclosed thermal current

          35 A

          [Uc] control circuit voltage

          110 V AC 50/60 Hz

          Cable entry number

        • 2 ISO20 top
        • 2 ISO25 top
        • 2 Pg 16 bottom
        • 2 Pg 21 bottom
        • 2 ISO20 bottom
        • 2 ISO25 bottom
          • Compatibility code

            LE2D

            Package 1 Weight

            4.1 kg

            Package 1 Height

            2.6 dm

            Package 1 width

            2.9 dm

            Package 1 Length

            4 dm
            Show all specifications

            Documents & downloads

            hide show
            Filter items
            • All

            • Technical Data Catalogues

            • Installation Instruction

            Frequently Asked Questions

            hide show

            Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

            Issue:
            Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

            Product Line: 
            Tesys D Contactors

            Environment:
            IEC contactors

            Resolution:
            The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
             

            Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

            Issue:  
            Tesys D enclosed starter with a DC control 

            Product Line:
             Enclosed Tesys D line starters

            Environment:
            North American Products
             
            Cause:
            DC control circuit 
             
            Resolution:
            Yes but limited to 24 VDC.

            What are the wiring terminals on the IEC LRD* overload relays?

            Product Line:
            Tesys D line Overload Relays
             
            Resolution:
            The normally closed overload contact are terminals 95 & 96; and the normally open overload contact are terminals 97 & 98.
            T1 T2 and T3 are the load terminals. 

            The normally closed control circuit contact will open when there is a fault, this contact is typically used in series with the control circuit. 

            The normally open trip signal contact closes when a fault occurs which is typically used to control a pilot light, or alarm. 

             

            Can you get the lid only for LE1D35U7 DOL Starter?

            Yes, But it comes as a complete empty enclosure, the code is DE1DS2.
             

            What are the dimensions for a Model K DOL non reversing starter - LE1M35U7?

            The dimensions for a Model K DOL non reversing starter - LE1M35U7 are - W78mm x H160mm x D108mm

            For further information , visit link below:-
            https://www.schneider-electric.com.au/en/search/LE1M35U5
            User-added image

             

            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

            Issue:
            Identifying maximum voltage of an LC1D contactor

            Product Line:
            TeSys D Contactors

            Environment:
            IEC contactors and starters used in North America

            Cause:
            n/a

            Resolution:
            IThe maximum voltage per UL and CSA is 600VAC. 
             

            What is the replacement for LR2D3357?

            What is the altitude derating for a TeSys D-Line contactor?

            Issue:​
            What is the altitude derating for a TeSys D-Line contactor?

            Product Line:
            Digest 177 Section 18 : Contactors and Starters, IEC

            Environment:
            North American Products

            Resolution:
            The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

            Voltage
            3500m x 0.90
            4000m x 0.80
            4500m x 0.70
            5000m x 0.60

            Current
            3500m x 0.92
            4000m x 0.90
            4500m x 0.88
            5000m x 0.86

            For example, an LC1D80 at 5000 meters:
            - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
            - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



             

            What is the coil consumption or burden for the Tesys LC*D** contactors?

            * 1 or 2
            ** 09 through 38

            Issue:
            Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

            Product Line: 
            Contactors and Starters - IEC

            Environment:
            North American Products

            Resolution:
            All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

            What D-line overload relays use the LA7D3064 separate mounting kit?

            Issue
            What D-line overload relays use the LA7D3064 separate mounting kit?

            Product Line
            Overload relay

            Environment
            Tesys and Pre Tesys D-line

            Cause
            Fit, compatibility, and product features 

            Resolution
            The LRD3***   LR3D3**, LR2D35** D-line overload relays.

            ETSNZ - Are spare enclosures available for Model D DOL starters?

            For the LE1D12, spare enclosure is part ref DE1DS1
            For LE1D18 - LE1D35, spare enclosure is part ref DE1DS2

            What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

            Issue:
            Identifying replacement coils for tesys D non-reversing and reversing conactors

            Product Line:
            IEC Contactors and Starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement coil is needed

            Resolution:
            DC replacement coils are not available.
            AC Coils are 50/60 hertz for voltages as listed below:

            Volts - Part Number
            12 ____ LXD1J7
            21 ____ LXD1Z7
            24 ____ LXD1B7
            32 ____ LXD1C7
            36 ____ LXD1CC7
            42 ____ LXD1D7
            48 ____ LXD1E7
            60 ____ LXD1EE7
            100 ___ LXD1K7 ( never brought to North America )
            110 ___ LXD1F7
            115 ___ LXD1FE7
            120 ___ LXD1G7
            127 ___ LXD1FC7
            200 ___ LXD1L7
            208 ___ LXD1LE7
            220 ___ LXD1M7
            230 ___ LXD1P7
            240 ___ LXD1U7
            277 ___ LXD1W7
            380 ___ LXD1Q7
            400 ___ LXD1V7
            415 ___ LXD1N7
            440 ___ LXD1R7
            480 ___ LXD1T7
            575 ___ LXD1SC7
            600 ___ LXD1X7
            690 ___ LXD1Y7


            Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 