Quantcast

TeSys LE Enclosed DOL Reversing Starter, 12A, 415VAC, Coil

TeSys LE Enclosed DOL Reversing Starter, 12A, 415VAC, Coil

TeSys LE Enclosed DOL Reversing Starter, 12A, 415VAC, Coil

Item Number: LE2D12N7

Retail
$1,645.02
RRP (Inc. GST)

Product Dimensions

Width icon

Width101 mm

Height icon

Height201 mm

Depth icon

Depth160 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

enclosed DOL reversing starter

Device application

standard

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ie] rated operational current

12 A AC-3

Control type

  • push-button stop/reset red O
  • selector switch 2 positions start I-II
    • Width

      101 mm

      Height

      201 mm

      Depth

      160 mm

      Net weight

      2.1 kg

      IP degree of protection

      IP65 conforming to IEC 60529

      IK degree of protection

      IK07 conforming to IEC 60529

      Standards

      IEC 60947-4-1

      Ambient air temperature for operation

      -5-40 °C

      Environmental characteristic

      standard environment

      REACh Regulation

      Free of Substances of Very High Concern above the threshold

      REACh free of SVHC

      Yes

      EU RoHS Directive

      Compliant

      Toxic heavy metal free

      Yes

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      X

      Environmental Disclosure

      ENVPEP111273EN

      Material

      Device composition

    • thermal overload relay ordered separately
    • reversing contactor
      • Material

        polycarbonate

        Others

        Product name

        TeSys LE

        Device short name

        LE2D

        Utilisation category

        AC-3

        Motor power kW

      • 3 kW at 220/230 V AC 50/60 Hz
      • 7.5 kW at 500 V AC 50/60 Hz
      • 7.5 kW at 660/690 V AC 50/60 Hz
      • 5.5 kW at 380/400 V AC 50/60 Hz
      • 5.5 kW at 415 V AC 50/60 Hz
      • 5.5 kW at 440 V AC 50/60 Hz
        • [Ithe] conventional enclosed thermal current

          12 A

          [Uc] control circuit voltage

          415 V AC 50/60 Hz

          Cable entry number

        • 2 ISO20 top
        • 2 ISO25 top
        • 2 Pg 16 bottom
        • 2 Pg 21 bottom
        • 2 ISO20 bottom
        • 2 ISO25 bottom
          • Compatibility code

            LE2D

            Unit Type of Package 1

            PCE

            Number of Units in Package 1

            1

            Package 1 Weight

            2.1 kg

            Package 1 Height

            26 cm

            Package 1 width

            29 cm

            Package 1 Length

            40 cm

            WEEE

            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            Show all specifications

            Frequently Asked Questions

            hide show

            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

            Issue:
            Identifying maximum voltage of an LC1D contactor

            Product Line:
            TeSys D Contactors

            Environment:
            IEC contactors and starters used in North America

            Cause:
            n/a

            Resolution:
            IThe maximum voltage per UL and CSA is 600VAC. 
             

            What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

            Issue:
            Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

            Product Line:
            IEC Contactors and Starters

            Environment:
            Tesys D Contactors

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
            stranded cable w/cable end: One or Two #18-10 AWG per terminal.
            solid cable: One or Two #18-8 AWG per terminal.

            What is the replacement base for a LE1D12N7

            The base is not available on it's own but a replacement enclosure including base is a DE1DS1

            What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38?

            Issue:
            LC1D09 - LC1D38 Coil tolerance

            Product Line:
            Contactors and Starters, IEC

            Environment:
            Tesys D Contactors

            Cause:
            Needs the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38.

            Resolution:
            AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
            AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
            DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
            DC standard coil for LP1D12 and D25: (-20% / +10%)
            DC wide range coil for LP1D12 and D25 : (-30% to +25%)

            What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

            Issue:
            Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

            Product Line:
            Contactors and Starters IEC

            Environment:
            Tesys D contactors and GV manual starters

            Cause:
            Spacer required

            Resolution:
            Compensation plate catalog number GV1F03, requires 2 pieces snap together.

            What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

            Issue:
            Coil Voltage suffixes for Tesys D contactors LC*D 09/38

            Product Line:
            IEC Contactors and Starters

            Environment:
            Tesys D contactors

            Cause:
            Selection

            Resolution:
            The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

            AC Volts ___Code     AC Volts ___Code
            12 ___ J7                   208 ___ LE7
            21 ___ Z7                   220 ___ M7
            24 ___ B7                  230 ___ P7
            32 ___ C7                  240 ___ U7
            36 ___ CC7               277 ___ W7
            42 ___ D7                  380 ___ Q7
            48 ___ E7                   400 ___ V7
            60 ___ EE7                415 ___ N7
            100 ___ K7                440 ___ R7
            110 ___ F7                480 ___ T7
            115 ___ FE7              575 ___ SC7
            120 ___ G7                600 ___ X7
            127 ___ FC7              690 ___ Y7
            200 ___ L7                
                           
            Standard Coil                Low Consumption
            DC Volts ___Code          DC Volts ___Code
            12 ___ JD                           5 ___ AL
            24 ___ BD                         12 ___ JL
            36 ___ CD                         20 ___ ZL
            48 ___ ED                         24 ___ BL
            60 ___ ND                         48 ___ EL
            72 ___ SD                         72 ___ SL
            110 ___ FD                       96 ___ DL
            125 ___ GD                     110 ___ FL
            220 ___ MD                    220 ___ ML
            250 ___ UD                     250 ___ UL
            440 ___ RD