Specifications

hide show
Range
TeSys
Product name
TeSys LE
Device short name
LE1M
Product or component type
enclosed DOL starter
Device application
standard
Utilisation category
AC-3
Device composition
  • contactor
  • earth terminal
  • neutral terminal
  • thermal overload relay
    • Thermal protection adjustment range
      3.7-5.5 A
      Motor power kW
    • 0.75 kW at 240 V AC 50/60 Hz
    • 2.2 kW at 415 V AC 50/60 Hz
    • 1.1 kW at 220/230 V AC 50/60 Hz
    • 2.2 kW at 380/400 V AC 50/60 Hz
      • [Uc] control circuit voltage
        415 V AC 50/60 Hz
        Control type
      • push-button start green I
      • push-button stop/reset red O
        • Local signalling
          operating: LED (yellow)
          Cable entry number
        • 2 ISO20 top
        • 2 Pg 16 bottom
        • 2 ISO25 top
        • 2 Pg 13 top
        • 2 Pg 21 top
        • 2 ISO20 bottom
        • 2 ISO25 bottom
        • 2 Pg 13 bottom
        • 2 Pg 21 bottom
        • 2 Pg 16 top
          • Width
            78 mm
            Height
            160 mm
            Depth
            108 mm
            Net weight
            0.6 kg
            Compatibility code
            LE1M
            Material
            ABS (acrylonitrile butadiene-styrene)
            IP degree of protection
            IP65 conforming to IEC 60529
            Standards
            IEC 60947-4-1
            Ambient air temperature for operation
            -5-40 °C
            Environmental characteristic
            standard environment
            Unit Type of Package 1
            PCE
            Number of Units in Package 1
            1
            Package 1 Weight
            589 g
            Package 1 Height
            8.5 cm
            Package 1 width
            11.5 cm
            Package 1 Length
            16.5 cm
            Unit Type of Package 2
            S02
            Number of Units in Package 2
            6
            Package 2 Weight
            3.75 kg
            Package 2 Height
            15 cm
            Package 2 width
            30 cm
            Package 2 Length
            40 cm
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Compliant
            Toxic heavy metal free
            Yes
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
            X
            WEEE
            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            Warranty
            18 months

            Documents & downloads

            hide show
            Filter items
            • All

            • CAD Files and Packs

            • Product Brochures

            • Technical Data Catalogues

            • Installation Instruction

            • Declaration of Conformity

            Frequently Asked Questions

            hide show

            What is the part number for an replacement overload , 3.7-5.5amp , for the LE1M35N712?

            The part number for an replacement overload , 3.7-5.5amp , for the LE1M35N712 is - LR2K0312
            For further information visit link below:-
            https://www.schneider-electric.com.au/en/search/LR2K0312
             

            What is the part code for a DOL Starter 1P 2.2kW 12-16A Overload

             Use a LE1M35U722 starter

            Is there a LE1M35N705 alternative or can coil be swapped out

             The part codes you need is LE1D12N7 + LRD06

            What is the DOL to suit the thermal overload LR2K0321?

            The DOL To suit the thermal overloadLR2K0321 is:
            LE1M35U721 for a 240V application or LE1M35N721 for a 440V application.

            What is the weight of a LE1M35U705

             0.6 kg

            What is the LE1M35U705 made of

            self extinguishing ABS

            What is the IP rating of a LE1M35U705

            The rating is  IP 65

            What are the dimensions for a Model K DOL non reversing starter - LE1M35U7?

            The dimensions for a Model K DOL non reversing starter - LE1M35U7 are - W78mm x H160mm x D108mm

            For further information , visit link below:-
            https://www.schneider-electric.com.au/en/search/LE1M35U5
            User-added image

             

            What is the operational Temperature for a LE1M35U705

             The operational temperature is  -5 to 40° Degrees celsius

            What are the dimensions of a LE1M35U705

             160 x 78 x 108mm (H x W x D)

            Can I get spare parts for LE1M35****

             No spare parts available

            What is the part number for a 3 phase DOL starter for 2.2kW load with overload 4 amps and 415VAC coil??

            The part number for a 3 phase DOL starter with 415VAC coil and overload to cover 4amps is - LE1M35N712

            See attachment.

             