TeSys LE Enclosed DOL Starter, 25A, 380VAC Coil

TeSys LE Enclosed DOL Starter, 25A, 380VAC Coil

TeSys LE Enclosed DOL Starter, 25A, 380VAC Coil

Item Number: LE1D25Q7

Retail
$1,071.84
RRP (Inc. GST)

Product Dimensions

Width icon

Width101 mm

Height icon

Height201 mm

Depth icon

Depth153.5 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

enclosed DOL starter

Device application

standard

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Control type

  • push-button start green I
  • push-button stop/reset red O
    • [Ie] rated operational current

      25 A AC-3

      Width

      101 mm

      Height

      201 mm

      Depth

      153.5 mm

      Net weight

      1.015 kg

      IP degree of protection

      IP65 conforming to IEC 60529

      IK degree of protection

      IK07 conforming to IEC 60529

      Standards

      IEC 60947-4-1

      Ambient air temperature for operation

      -5-40 °C

      Environmental characteristic

      standard environment

      REACh free of SVHC

      Yes

      EU RoHS Directive

      Compliant

      Toxic heavy metal free

      Yes

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      X

      Environmental Disclosure

      ENVPEP111273EN

      Material

      Device composition

    • thermal overload relay ordered separately
    • contactor
      • Material

        polycarbonate

        Others

        Product name

        TeSys LE

        Device short name

        LE1D

        Utilisation category

        AC-3

        Motor power kW

      • 11 kW at 380/400 V AC 50/60 Hz
      • 11 kW at 415 V AC 50/60 Hz
      • 11 kW at 440 V AC 50/60 Hz
      • 15 kW at 500 V AC 50/60 Hz
      • 15 kW at 660/690 V AC 50/60 Hz
      • 5.5 kW at 220/230 V AC 50/60 Hz
        • [Ithe] conventional enclosed thermal current

          25 A

          [Uc] control circuit voltage

          380 V AC 50/60 Hz

          Cable entry number

        • 2 ISO20 top
        • 2 ISO20 bottom
        • 2 Pg 16 bottom
        • 2 ISO25 top
        • 2 Pg 21 bottom
        • 2 ISO25 bottom
          • Compatibility code

            LE1D

            Unit Type of Package 1

            PCE

            Number of Units in Package 1

            1

            Package 1 Weight

            1.224 kg

            Package 1 Height

            18.5 cm

            Package 1 width

            20.5 cm

            Package 1 Length

            26 cm

            Unit Type of Package 2

            P06

            Number of Units in Package 2

            22

            Package 2 Weight

            40.26 kg

            Package 2 Height

            80 cm

            Package 2 width

            80 cm

            Package 2 Length

            60 cm

            WEEE

            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            Show all specifications

            Documents & downloads

            hide show
            Filter items
            • All

            • CAD Files and Packs

            • Product Brochures

            • Technical Data Catalogues

            • Product Environmental

            Frequently Asked Questions

            hide show

            What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

            Issue:
            Identifying replacement coils for tesys D non-reversing and reversing conactors

            Product Line:
            IEC Contactors and Starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement coil is needed

            Resolution:
            DC replacement coils are not available.
            AC Coils are 50/60 hertz for voltages as listed below:

            Volts - Part Number
            12 ____ LXD1J7
            21 ____ LXD1Z7
            24 ____ LXD1B7
            32 ____ LXD1C7
            36 ____ LXD1CC7
            42 ____ LXD1D7
            48 ____ LXD1E7
            60 ____ LXD1EE7
            100 ___ LXD1K7 ( never brought to North America )
            110 ___ LXD1F7
            115 ___ LXD1FE7
            120 ___ LXD1G7
            127 ___ LXD1FC7
            200 ___ LXD1L7
            208 ___ LXD1LE7
            220 ___ LXD1M7
            230 ___ LXD1P7
            240 ___ LXD1U7
            277 ___ LXD1W7
            380 ___ LXD1Q7
            400 ___ LXD1V7
            415 ___ LXD1N7
            440 ___ LXD1R7
            480 ___ LXD1T7
            575 ___ LXD1SC7
            600 ___ LXD1X7
            690 ___ LXD1Y7


            Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

            Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

            Issue:
            Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

            Product Line: 
            Tesys D Contactors

            Environment:
            IEC contactors

            Resolution:
            The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
             

            What is the altitude derating for a TeSys D-Line contactor?

            Issue:​
            What is the altitude derating for a TeSys D-Line contactor?

            Product Line:
            Digest 177 Section 18 : Contactors and Starters, IEC

            Environment:
            North American Products

            Resolution:
            The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

            Voltage
            3500m x 0.90
            4000m x 0.80
            4500m x 0.70
            5000m x 0.60

            Current
            3500m x 0.92
            4000m x 0.90
            4500m x 0.88
            5000m x 0.86

            For example, an LC1D80 at 5000 meters:
            - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
            - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



             

            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

            Issue:
            Identifying maximum voltage of an LC1D contactor

            Product Line:
            TeSys D Contactors

            Environment:
            IEC contactors and starters used in North America

            Cause:
            n/a

            Resolution:
            IThe maximum voltage per UL and CSA is 600VAC. 
             

            Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

            Issue:  
            Tesys D enclosed starter with a DC control 

            Product Line:
             Enclosed Tesys D line starters

            Environment:
            North American Products
             
            Cause:
            DC control circuit 
             
            Resolution:
            Yes but limited to 24 VDC.

            What is the coil consumption or burden for the Tesys LC*D** contactors?

            * 1 or 2
            ** 09 through 38

            Issue:
            Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

            Product Line: 
            Contactors and Starters - IEC

            Environment:
            North American Products

            Resolution:
            All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

            Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

            Issue:
            Mounting adaptor for GV2 and LC1D contactor

            Product Line:
            Motor Starters and Protectors

            Environment:
            TeSys GV Manual Starter and Protectors
            Tesys D Contactors
             
            Resolution:
            The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

            what is the replacement for an LC1D2510 contactor with 240v coil ?

            The replacement is an LC1D25U7

            What is the difference between the LC1D25E7 and LC1D258E7?

            The LC1D25E7 is a 3 Poles 25 Amps (AC-3) Contactor

            Where as

            The LC1D258E7 is a 4 Pole (2NO + 2NC) 25 Amps (AC-3) Contactor

            https://www.schneider-electric.com.au/en/search/LC1D25E7

            Can I still purchase a LE1D405N7 and a LE1D405U7 in NZ

            These are obsolete no longer available

            What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

            Issue:
            Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

            Product Line:
            NEMA combination starters

            Environment:
            Products sold and used in the United States

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
            stranded cable w/cable end: One or Two #18-10 AWG per terminal.
            solid cable: One or Two #18-8 AWG per terminal.

            What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

            Issue:
            Identifying power terminal lug data for the D2 style contactors

            Product Line:
            Tesys D line contactors

            Environment:
            Products sold and used in the United States

            Cause:
            Power terminal lug data required

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
            stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
            solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.
            Show More