Specifications

hide show
Range
TeSys
Product name
TeSys LE
Device short name
LE1D
Product or component type
enclosed DOL starter
Device application
standard
Utilisation category
AC-3
Device composition
  • thermal overload relay ordered separately
  • contactor
    • Control type
    • push-button start green I
    • push-button stop/reset red O
      • [Ie] rated operational current
        18 A AC-3
        Motor power kW
      • 10 kW at 500 V AC 50/60 Hz
      • 10 kW at 660/690 V AC 50/60 Hz
      • 4 kW at 220/230 V AC 50/60 Hz
      • 9 kW at 415 V AC 50/60 Hz
      • 9 kW at 440 V AC 50/60 Hz
      • 7.5 kW at 380/400 V AC 50/60 Hz
        • [Ithe] conventional enclosed thermal current
          18 A
          [Uc] control circuit voltage
          220 V AC 50/60 Hz
          Cable entry number
        • 2 ISO20 top
        • 2 ISO20 bottom
        • 2 Pg 16 bottom
        • 2 ISO25 top
        • 2 Pg 21 bottom
        • 2 ISO25 bottom
          • Width
            101 mm
            Height
            201 mm
            Depth
            153.5 mm
            Net weight
            1.015 kg
            Compatibility code
            LE1D
            Material
            polycarbonate
            IP degree of protection
            IP65 conforming to IEC 60529
            IK degree of protection
            IK07 conforming to IEC 60529
            Standards
            IEC 60947-4-1
            Ambient air temperature for operation
            -5-40 °C
            Environmental characteristic
            standard environment
            Unit Type of Package 1
            PCE
            Number of Units in Package 1
            1
            Package 1 Weight
            1.161 kg
            Package 1 Height
            16.6 cm
            Package 1 width
            20 cm
            Package 1 Length
            25.2 cm
            Unit Type of Package 2
            CAR
            Number of Units in Package 2
            1
            Package 2 Weight
            1.161 kg
            Package 2 Height
            19.5 cm
            Package 2 width
            16 cm
            Package 2 Length
            24.8 cm
            Unit Type of Package 3
            P06
            Number of Units in Package 3
            22
            Package 3 Weight
            38.63 kg
            Package 3 Height
            80 cm
            Package 3 width
            80 cm
            Package 3 Length
            60 cm
            Sustainable offer status
            Green Premium product
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Compliant
            Toxic heavy metal free
            Yes
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
            X
            Environmental Disclosure
            ENVPEP111273EN
            WEEE
            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            California proposition 65
            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
            Warranty
            18 months

            Documents & downloads

            hide show
            Filter items
            • All

            • CAD Files and Packs

            • Product Brochures

            • Technical Data Catalogues

            • Product Environmental

            • Installation Instruction

            Frequently Asked Questions

            hide show

            Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

            Issue:
            Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

            Product Line: 
            Tesys D Contactors

            Environment:
            IEC contactors

            Resolution:
            The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
             

            What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

            Issue:
            Identifying replacement coils for tesys D non-reversing and reversing conactors

            Product Line:
            IEC Contactors and Starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement coil is needed

            Resolution:
            DC replacement coils are not available.
            AC Coils are 50/60 hertz for voltages as listed below:

            Volts - Part Number
            12 ____ LXD1J7
            21 ____ LXD1Z7
            24 ____ LXD1B7
            32 ____ LXD1C7
            36 ____ LXD1CC7
            42 ____ LXD1D7
            48 ____ LXD1E7
            60 ____ LXD1EE7
            100 ___ LXD1K7 ( never brought to North America )
            110 ___ LXD1F7
            115 ___ LXD1FE7
            120 ___ LXD1G7
            127 ___ LXD1FC7
            200 ___ LXD1L7
            208 ___ LXD1LE7
            220 ___ LXD1M7
            230 ___ LXD1P7
            240 ___ LXD1U7
            277 ___ LXD1W7
            380 ___ LXD1Q7
            400 ___ LXD1V7
            415 ___ LXD1N7
            440 ___ LXD1R7
            480 ___ LXD1T7
            575 ___ LXD1SC7
            600 ___ LXD1X7
            690 ___ LXD1Y7


            Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

            Issue:
            Identifying maximum voltage of an LC1D contactor

            Product Line:
            TeSys D Contactors

            Environment:
            IEC contactors and starters used in North America

            Cause:
            n/a

            Resolution:
            IThe maximum voltage per UL and CSA is 600VAC. 
             

            What is the altitude derating for a TeSys D-Line contactor?

            Issue:​
            What is the altitude derating for a TeSys D-Line contactor?

            Product Line:
            Digest 177 Section 18 : Contactors and Starters, IEC

            Environment:
            North American Products

            Resolution:
            The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

            Voltage
            3500m x 0.90
            4000m x 0.80
            4500m x 0.70
            5000m x 0.60

            Current
            3500m x 0.92
            4000m x 0.90
            4500m x 0.88
            5000m x 0.86

            For example, an LC1D80 at 5000 meters:
            - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
            - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



             

            What replaces a LC1D18M7

            Use the LC1D18U7

            Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

            Issue:  
            Tesys D enclosed starter with a DC control 

            Product Line:
             Enclosed Tesys D line starters

            Environment:
            North American Products
             
            Cause:
            DC control circuit 
             
            Resolution:
            Yes but limited to 24 VDC.

            Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

            Issue:
            Mounting adaptor for GV2 and LC1D contactor

            Product Line:
            Motor Starters and Protectors

            Environment:
            TeSys GV Manual Starter and Protectors
            Tesys D Contactors
             
            Resolution:
            The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

            What is the plastic arm for LE1D18U7 stop button

            Part code LAD91810

            What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

            Issue:
            Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

            Product Line:
            NEMA combination starters

            Environment:
            Products sold and used in the United States

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
            stranded cable w/cable end: One or Two #18-10 AWG per terminal.
            solid cable: One or Two #18-8 AWG per terminal.

            What is the coil consumption or burden for the Tesys LC*D** contactors?

            * 1 or 2
            ** 09 through 38

            Issue:
            Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

            Product Line: 
            Contactors and Starters - IEC

            Environment:
            North American Products

            Resolution:
            All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

            Contactor LE1D18N7 does it come with overload ?

             No - Overloads can be ordered separatly depending on the current rating required
             

            What replaces LC1D1801U5

             Part code LC1D18U7
            Show More