Specifications

hide show
Sustainable offer status
Green Premium product
REACh Regulation
Free of Substances of Very High Concern above the threshold
REACh free of SVHC
Yes
EU RoHS Directive
Compliant
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
X
Environmental Disclosure
ENVPEP111273EN
Circularity Profile
N/A
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Documents & downloads

hide show
Filter items
  • All

  • Product Environmental

Frequently Asked Questions

hide show

How do you wire up an LE1D12U7S48.

Remove the signal supply wire from L3 and connect a supply wire, from an external source, to the upstream "line side" of the electrical contact block on the back of the "start" pushbutton.
Then the downstream "load side" of the same "start" pushbutton electrical contact will normally be connected to terminal number "A1" on the coil of the contactor.
Also, because of the geographical layout of the LE1D12U7S48 starter unit, then the normally closed (N/C) electrical contact inside the thermal overload unit will be connected between the neutral and terminal number "A2"
on the same contactor.

What is the replacement for a LE1D12N7R05

The above part is no longer available like this, but is made up of LE1D12N7S48 + LRD05
3 Pole Reversing and Non Reversing DOL Starters
Model D DOL Non-Reversing Starters with Overload Purchased Separately
IP65 Polycarbonate Enclosure (4)
3-phase 415V AC3 kW: 0.37
Overload Range A: 0.63 to 1.0
Overload*: LRD05
Starter(1)
*For overload pricing please refer to the Overload Relays section in Power Control and Protection 

What is the part number for a DOL non reversing starter for 13amp 3 phase load ?

The part number for a DOL non reversing starter for 13amp 3 phase load  - LE1D12N7S48 & LRD16

For further information , visit link below:-
https://www.schneider-electric.com.au/en/search/LE1D12N7S48
https://www.schneider-electric.com.au/en/search/LRD16
User-added image

What is the part name for the DOL starter with Estop in Tesys D range?

LE1D12U7S48EM is an example part# for the teyss D DOl with the latching E-stop.
"EM" at the end of the part# for LE1D12*****

What is the replacement part number for the old DOL motor starter LE1D12N7R12?

The replacement part number for the old DOL motor starter LE1D12N7R12 is - ​LE1D12N7S48

For further information , visit link below:-
https://www.schneider-electric.com.au/en/search/LE1D12N7S48


 

Is there a replacemnet for the old DOL motor starters like LE1D12U7R10?

All of the LE1D12U7R** parts have now been Divide into two parts enclosed starter and thermal overload see table for the new part numbers/ format:
 
Old Part Numbers Enclosed Starter Thermal Overload
LE1D12U7R10 LE1D12U7S48 plus LRD10
LE1D12U7R12 LE1D12U7S48 plus LRD12
LE1D12U7R14 LE1D12U7S48 plus LRD14
LE1D12U7R16 LE1D12U7S48 plus LRD16

For further information please visit https://www.clipsal.com/Trade

 

What is the coil consumption or burden for the Tesys LC*D** contactors?

* 1 or 2
** 09 through 38

Issue:
Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

Product Line: 
Contactors and Starters - IEC

Environment:
North American Products

Resolution:
All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

What is the part number for a DOL reversing starter for 3.7kW load?

The part number for a DOL reversing starter for 3.7kW load is - LE2D12N7

For further information , visit link below:-
https://www.schneider-electric.com.au/en/search/LE2D12N7

What is the part number for the replacement contactor for the LC1D1210N7?

The part number for the replacement contactor for the LC1D1210N7 is - LC1D12N7

For further information, visit the link below:-
https://www.schneider-electric.com.au/en/search/LC1D12N7
User-added image

What is the part number for a 25amp contactor 3 pole 240VAC coil?

The part number for a 25amp contactor 3 pole 240VAC coil is - LC1D12U7

For further information visit link below:-
https://www.schneider-electric.com.au/en/search/LC1D12U7
User-added image

What is the part number for a 3 pole 12amp contactor with a 240VAC coil ?

The part number for a 3 pole 12amp contactor with a 240VAC coil is - LC1D12U7

For further information , visit link below:-
https://www.schneider-electric.com.au/en/search/LC1D12U7
User-added image

What is the part number for a 3 pole 32amp contactor with 1 N/O & 1 N/C auxiliary contact and 24VAC coil?

The part number for a 3 pole 32amp contactor with 1 N/O & 1 N/C auxiliary contact and 24VAC coil is - LC1D32B7

For further information , visit link below:-
https://www.schneider-electric.com.au/en/search/LC1D32B7
User-added image

What is the part number for 5.5KW contactor with 12V AC Coil ?

The part number for 5.5KW contactor with 12V AC Coil is LC1D12J7


For further information refer to:
https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D12J7