Star-delta starter LC3D09 to LC3D18 for motor control

TeSys D Star Delta Starter, 3 x 3P (3 NO), 18A, 110VAC Coil

Catalogue Number: LC3D18AF7
Star-delta starter LC3D09 to LC3D18 for motor control
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
star delta starter
Device short name
LC3D
Contactor application
motor control
Utilisation category
AC-3
Device presentation
pre-wired
Poles description
3 x 3P
Pole contact composition
3 x 3 NO
[Ue] rated operational voltage
power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW
  • 11 kW at 220/230 V AC 50/60 Hz
  • 22 kW at 415 V AC 50/60 Hz
  • 22 kW at 440 V AC 50/60 Hz
  • 18.5 kW at 380/400 V AC 50/60 Hz
    • Control circuit type
      AC at 50/60 Hz
      [Uc] control circuit voltage
      110 V AC 50/60 Hz
      Auxiliary contact composition
      1 NC for KM1 star contactor
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ui] rated insulation voltage
    • power circuit: 690 V conforming to IEC 60947-4-1
    • power circuit: 600 V CSA certified
    • power circuit: 600 V UL certified
    • signalling circuit: 690 V conforming to IEC 60947-1
    • signalling circuit: 600 V CSA certified
    • signalling circuit: 600 V UL certified
      • Electrical durability
        1.65 Mcycles 18 A AC-3 at Ue <= 440 V
        Provided equipment
        protective cover
        Interlocking type
        mechanical
        Mounting support
        plate
        Standards
      • EN 60947-5-1
      • EN 60947-4-1
      • UL 508
      • IEC 60947-4-1
      • IEC 60947-5-1
      • CSA C22.2 No 14
        • Product certifications
        • RINA
        • DNV
        • GOST
        • BV
        • LROS (Lloyds register of shipping)
        • GL
        • CSA
        • UL
        • CCC
          • Connections - terminals
          • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
          • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible with cable end
          • power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end
          • power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable end
          • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
          • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
          • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
          • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
          • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
          • power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: flexible without cable end
          • power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible without cable end
          • power circuit: screw clamp terminals 1 1-6 mm² - cable stiffness: flexible with cable end
            • Tightening torque
            • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
            • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
              • Maximum operating rate
                30 cyc/h 60 °C
                Starting time
                30 s
                Coil technology
                without built-in suppressor module
                Control circuit voltage limits
              • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
              • operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
              • operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
                • Inrush power in VA
                • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
                • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
                  • Hold-in power consumption in VA
                  • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
                  • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
                    • Heat dissipation
                      2-3 W at 50/60 Hz
                      Auxiliary contacts type
                    • mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC
                    • mirror contact conforming to IEC 60947-4-1 3 x 1 NC
                      • Signalling circuit frequency
                        25...400 Hz
                        Minimum switching current
                        5 mA for signalling circuit
                        Switching voltage
                        17 V for signalling circuit
                        Non-overlap time
                      • 1.5 ms on de-energisation between NC and NO contact
                      • 1.5 ms on energisation between NC and NO contact
                        • Width
                          144 mm
                          Height
                          124 mm
                          Depth
                          143 mm
                          Net weight
                          1.73 kg
                          Power range
                        • 7-11 kW at 200-240 V 3 phases
                        • 15-25 kW at 380-440 V 3 phases
                          • Motor starter type
                            star delta starter
                            Contactor coil voltage
                            110 V AC standard
                            Insulation resistance
                            > 10 MOhm for signalling circuit
                            IP degree of protection
                            IP20 front face conforming to IEC 60529
                            Protective treatment
                            TH conforming to IEC 60068-2-30
                            Pollution degree
                            3
                            Ambient air temperature for storage
                            -60-80 °C
                            Ambient air temperature for operation
                            -40-70 °C at Uc
                            Operating altitude
                            3000 m without
                            Fire resistance
                            850 °C conforming to IEC 60695-2-1
                            Flame retardance
                            V1 conforming to UL 94
                            Mechanical robustness
                          • vibrations contactor open: 2 Gn, 5...300 Hz
                          • vibrations contactor closed: 4 Gn, 5...300 Hz
                          • shocks contactor open: 10 Gn for 11 ms
                          • shocks contactor closed: 15 Gn for 11 ms
                            • Sustainable offer status
                              Green Premium product
                              REACh Regulation
                              Free of Substances of Very High Concern above the threshold
                              REACh free of SVHC
                              Yes
                              EU RoHS Directive
                              Compliant
                              Toxic heavy metal free
                              Yes
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              X
                              Environmental Disclosure
                              ENVPEP080208EN
                              Circularity Profile
                              ENVEOLI100418
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              Warranty
                              18 months

                              Documents & downloads

                              hide show
                              Filter items
                              • All

                              • Product Brochures

                              • Technical Data Catalogues

                              • End of Life Manual

                              • Product Environmental

                              • eTechPub

                              Frequently Asked Questions

                              hide show

                              Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                              Issue:
                              Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                              Product Line: 
                              Tesys D Contactors

                              Environment:
                              IEC contactors

                              Resolution:
                              The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                               

                              What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                              Issue:
                              Identifying replacement coils for tesys D non-reversing and reversing conactors

                              Product Line:
                              IEC Contactors and Starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Replacement coil is needed

                              Resolution:
                              DC replacement coils are not available.
                              AC Coils are 50/60 hertz for voltages as listed below:

                              Volts - Part Number
                              12 ____ LXD1J7
                              21 ____ LXD1Z7
                              24 ____ LXD1B7
                              32 ____ LXD1C7
                              36 ____ LXD1CC7
                              42 ____ LXD1D7
                              48 ____ LXD1E7
                              60 ____ LXD1EE7
                              100 ___ LXD1K7 ( never brought to North America )
                              110 ___ LXD1F7
                              115 ___ LXD1FE7
                              120 ___ LXD1G7
                              127 ___ LXD1FC7
                              200 ___ LXD1L7
                              208 ___ LXD1LE7
                              220 ___ LXD1M7
                              230 ___ LXD1P7
                              240 ___ LXD1U7
                              277 ___ LXD1W7
                              380 ___ LXD1Q7
                              400 ___ LXD1V7
                              415 ___ LXD1N7
                              440 ___ LXD1R7
                              480 ___ LXD1T7
                              575 ___ LXD1SC7
                              600 ___ LXD1X7
                              690 ___ LXD1Y7


                              Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                              What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                              Issue:
                              Identifying maximum voltage of an LC1D contactor

                              Product Line:
                              TeSys D Contactors

                              Environment:
                              IEC contactors and starters used in North America

                              Cause:
                              n/a

                              Resolution:
                              IThe maximum voltage per UL and CSA is 600VAC. 
                               

                              What is the altitude derating for a TeSys D-Line contactor?

                              Issue:​
                              What is the altitude derating for a TeSys D-Line contactor?

                              Product Line:
                              Digest 177 Section 18 : Contactors and Starters, IEC

                              Environment:
                              North American Products

                              Resolution:
                              The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                              Voltage
                              3500m x 0.90
                              4000m x 0.80
                              4500m x 0.70
                              5000m x 0.60

                              Current
                              3500m x 0.92
                              4000m x 0.90
                              4500m x 0.88
                              5000m x 0.86

                              For example, an LC1D80 at 5000 meters:
                              - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                              - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                               

                              What replaces a LC1D18M7

                              Use the LC1D18U7

                              What is the code for a 40A 110VAC contactor ?

                              LC1D40AF7

                              What is the part name for a spare coil on the LC1D188F7?

                              The part name is LXD1F7

                              What is the replacement contactor for the LC1D65004F5?

                              The new code is LC1DT80AF7 which is made to order.

                              Do the Everlink reversing contactors come with electrical interlocking?

                              Issue:
                              Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                              Product line:
                              Tesys D LC1D40A, LC1D50A, LC1D65A

                              Environment:
                              Everlink, all voltage codes

                              Cause:
                              Old D2 version offered an electrical interlock kit

                              Resolution:
                              The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                              What replaces LC1D1801U5

                               Part code LC1D18U7

                              What is the code for a 24vac coil to suit LC1D18B7 Contactor ?

                              24V AC Coil =  LXD1B7

                              What is the replacement for a LC1D1810U5 contactor

                              The replacement is a LC1D18U7