TeSys Star Delta Starter, 3 x 3P (3 NO), 12A, 240VAC Coil

TeSys Star Delta Starter, 3 x 3P (3 NO), 12A, 240VAC Coil

TeSys Star Delta Starter, 3 x 3P (3 NO), 12A, 240VAC Coil

Item Number: LC3D12AU7

Retail
$1,980.40
RRP (Inc. GST)

Product Dimensions

Width icon

Width143 mm

Height icon

Height124 mm

Depth icon

Depth143 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

star delta starter

Warranty

18 months

Physical

Device presentation

pre-wired

[Ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit

Electrical durability

2 Mcycles 12 A AC-3 at Ue <= 440 V

Provided equipment

protective cover

Mounting support

plate

Standards

  • IEC 60947-5-1
  • CSA C22.2 No 14
  • UL 508
  • EN 60947-4-1
  • IEC 60947-4-1
  • EN 60947-5-1
    • Product certifications

    • GOST
    • BV
    • LROS (Lloyds register of shipping)
    • CCC
    • GL
    • DNV
    • UL
    • CSA
    • RINA
      • Connections - terminals

      • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
      • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
      • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
      • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
      • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
      • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
      • power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
      • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
      • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
      • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
      • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
      • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
        • Mechanical durability

          15 Mcycles

          Width

          143 mm

          Height

          124 mm

          Depth

          143 mm

          Net weight

          1.53 kg

          Insulation resistance

          > 10 MOhm for signalling circuit

          IP degree of protection

          IP20 front face conforming to IEC 60529

          Ambient air temperature for storage

          -60-80 °C

          Ambient air temperature for operation

          -40-70 °C at Uc

          REACh free of SVHC

          Yes

          EU RoHS Directive

          Compliant

          Toxic heavy metal free

          Yes

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

           Pro-active China RoHS declaration (out of China RoHS legal scope)

          Others

          Product name

          TeSys D

          Device short name

          LC3D

          Contactor application

          motor control

          Utilisation category

          AC-3

          Poles description

          3 x 3P

          Pole contact composition

          3 x 3 NO

          Motor power kW

        • 11 kW at 380/400 V AC 50/60 Hz
        • 11 kW at 415 V AC 50/60 Hz
        • 11 kW at 440 V AC 50/60 Hz
        • 5.5 kW at 220/230 V AC 50/60 Hz
          • Control circuit type

            AC at 50/60 Hz

            [Uc] control circuit voltage

            240 V AC 50/60 Hz

            Auxiliary contact composition

            1 NC for KM1 star contactor

            [Uimp] rated impulse withstand voltage

            6 kV conforming to IEC 60947

            Overvoltage category

            III

            [Ui] rated insulation voltage

          • power circuit: 690 V conforming to IEC 60947-4-1
          • power circuit: 600 V CSA certified
          • power circuit: 600 V UL certified
          • signalling circuit: 690 V conforming to IEC 60947-1
          • signalling circuit: 600 V CSA certified
          • signalling circuit: 600 V UL certified
            • Interlocking type

              mechanical

              Tightening torque

            • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
            • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
              • Maximum operating rate

                30 cyc/h 60 °C

                Starting time

                30 s

                Coil technology

                without built-in suppressor module

                Control circuit voltage limits

              • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
              • operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
              • operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
                • Inrush power in VA

                • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
                • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
                  • Hold-in power consumption in VA

                  • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
                  • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
                    • Heat dissipation

                      2-3 W at 50/60 Hz

                      Auxiliary contacts type

                    • mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC
                    • mirror contact conforming to IEC 60947-4-1 3 x 1 NC
                      • Signalling circuit frequency

                        25...400 Hz

                        Minimum switching current

                        5 mA for signalling circuit

                        Switching voltage

                        17 V for signalling circuit

                        Non-overlap time

                      • 1.5 ms on de-energisation between NC and NO contact
                      • 1.5 ms on energisation between NC and NO contact
                        • Power range

                        • 1.1-2 kW at 100-120 V 3 phases
                        • 7-11 kW at 525-690 V 3 phases
                        • 4-6 kW at 380-440 V 3 phases
                        • 4-6 kW at 480-500 V 3 phases
                        • 2.2-3 kW at 200-240 V 3 phases
                          • Motor starter type

                            star delta starter

                            Protective treatment

                            TH conforming to IEC 60068-2-30

                            Pollution degree

                            3

                            Operating altitude

                            3000 m without derating

                            Fire resistance

                            850 °C conforming to IEC 60695-2-1

                            Flame retardance

                            V1 conforming to UL 94

                            Mechanical robustness

                          • vibrations contactor open: 2 Gn, 5...300 Hz
                          • vibrations contactor closed: 4 Gn, 5...300 Hz
                          • shocks contactor open: 10 Gn for 11 ms
                          • shocks contactor closed: 15 Gn for 11 ms
                            • Unit Type of Package 1

                              PCE

                              Number of Units in Package 1

                              1

                              Package 1 Weight

                              1.53 kg

                              Package 1 Height

                              18 cm

                              Package 1 width

                              16 cm

                              Package 1 Length

                              23.5 cm

                              WEEE

                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                              PVC free

                              Yes
                              Show all specifications

                              Documents & downloads

                              hide show
                              Filter items
                              • All

                              • Technical Data Catalogues

                              • End of Life Manual