Star-delta starter LC3D09 to LC3D18 for motor control

TeSys Star Delta Starter, 3 x 3P (3 NO), 12A, 415VAC Coil

Catalogue Number: LC3D12AN7
Star-delta starter LC3D09 to LC3D18 for motor control
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
star delta starter
Device short name
LC3D
Contactor application
motor control
Utilisation category
AC-3
Device presentation
pre-wired
Poles description
3 x 3P
Pole contact composition
3 x 3 NO
[Ue] rated operational voltage
power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW
  • 11 kW at 380/400 V AC 50/60 Hz
  • 11 kW at 415 V AC 50/60 Hz
  • 11 kW at 440 V AC 50/60 Hz
  • 5.5 kW at 220/230 V AC 50/60 Hz
    • Control circuit type
      AC at 50/60 Hz
      [Uc] control circuit voltage
      415 V AC 50/60 Hz
      Auxiliary contact composition
      1 NC for KM1 star contactor
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ui] rated insulation voltage
    • power circuit: 690 V conforming to IEC 60947-4-1
    • power circuit: 600 V CSA certified
    • power circuit: 600 V UL certified
    • signalling circuit: 690 V conforming to IEC 60947-1
    • signalling circuit: 600 V CSA certified
    • signalling circuit: 600 V UL certified
      • Electrical durability
        2 Mcycles 12 A AC-3 at Ue <= 440 V
        Provided equipment
        protective cover
        Interlocking type
        mechanical
        Mounting support
        plate
        Standards
      • IEC 60947-4-1
      • EN 60947-4-1
      • UL 508
      • IEC 60947-5-1
      • CSA C22.2 No 14
      • EN 60947-5-1
        • Product certifications
        • DNV
        • LROS (Lloyds register of shipping)
        • CCC
        • BV
        • GL
        • UL
        • CSA
        • RINA
        • GOST
          • Connections - terminals
          • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
          • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
          • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
          • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
          • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
          • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
          • power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
          • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
          • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
          • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
          • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
          • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
            • Tightening torque
            • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
            • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
              • Mechanical durability
                15 Mcycles
                Maximum operating rate
                30 cyc/h 60 °C
                Starting time
                30 s
                Coil technology
                without built-in suppressor module
                Control circuit voltage limits
              • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
              • operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
              • operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
                • Inrush power in VA
                • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
                • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
                  • Hold-in power consumption in VA
                  • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
                  • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
                    • Heat dissipation
                      2-3 W at 50/60 Hz
                      Auxiliary contacts type
                    • mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC
                    • mirror contact conforming to IEC 60947-4-1 3 x 1 NC
                      • Signalling circuit frequency
                        25...400 Hz
                        Minimum switching current
                        5 mA for signalling circuit
                        Switching voltage
                        17 V for signalling circuit
                        Non-overlap time
                      • 1.5 ms on de-energisation between NC and NO contact
                      • 1.5 ms on energisation between NC and NO contact
                        • Width
                          143 mm
                          Height
                          124 mm
                          Depth
                          143 mm
                          Net weight
                          1.53 kg
                          Power range
                        • 1.1-2 kW at 100-120 V 3 phases
                        • 7-11 kW at 525-690 V 3 phases
                        • 4-6 kW at 380-440 V 3 phases
                        • 4-6 kW at 480-500 V 3 phases
                        • 2.2-3 kW at 200-240 V 3 phases
                          • Motor starter type
                            star delta starter
                            Insulation resistance
                            > 10 MOhm for signalling circuit
                            IP degree of protection
                            IP20 front face conforming to IEC 60529
                            Protective treatment
                            TH conforming to IEC 60068-2-30
                            Pollution degree
                            3
                            Ambient air temperature for storage
                            -60-80 °C
                            Ambient air temperature for operation
                            -40-70 °C at Uc
                            Operating altitude
                            3000 m without
                            Fire resistance
                            850 °C conforming to IEC 60695-2-1
                            Flame retardance
                            V1 conforming to UL 94
                            Mechanical robustness
                          • vibrations contactor open: 2 Gn, 5...300 Hz
                          • vibrations contactor closed: 4 Gn, 5...300 Hz
                          • shocks contactor open: 10 Gn for 11 ms
                          • shocks contactor closed: 15 Gn for 11 ms
                            • Sustainable offer status
                              Green Premium product
                              REACh Regulation
                              Free of Substances of Very High Concern above the threshold
                              REACh free of SVHC
                              Yes
                              EU RoHS Directive
                              Compliant
                              Toxic heavy metal free
                              Yes
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              X
                              Environmental Disclosure
                              ENVPEP080208EN
                              Circularity Profile
                              ENVEOLI100418
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              Warranty
                              18 months

                              Documents & downloads

                              hide show
                              Filter items
                              • All

                              • Technical Data Catalogues

                              • End of Life Manual

                              • Product Environmental

                              Frequently Asked Questions

                              hide show

                              What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                              Issue:
                              Identifying replacement coils for tesys D non-reversing and reversing conactors

                              Product Line:
                              IEC Contactors and Starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Replacement coil is needed

                              Resolution:
                              DC replacement coils are not available.
                              AC Coils are 50/60 hertz for voltages as listed below:

                              Volts - Part Number
                              12 ____ LXD1J7
                              21 ____ LXD1Z7
                              24 ____ LXD1B7
                              32 ____ LXD1C7
                              36 ____ LXD1CC7
                              42 ____ LXD1D7
                              48 ____ LXD1E7
                              60 ____ LXD1EE7
                              100 ___ LXD1K7 ( never brought to North America )
                              110 ___ LXD1F7
                              115 ___ LXD1FE7
                              120 ___ LXD1G7
                              127 ___ LXD1FC7
                              200 ___ LXD1L7
                              208 ___ LXD1LE7
                              220 ___ LXD1M7
                              230 ___ LXD1P7
                              240 ___ LXD1U7
                              277 ___ LXD1W7
                              380 ___ LXD1Q7
                              400 ___ LXD1V7
                              415 ___ LXD1N7
                              440 ___ LXD1R7
                              480 ___ LXD1T7
                              575 ___ LXD1SC7
                              600 ___ LXD1X7
                              690 ___ LXD1Y7


                              Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                              Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                              Issue:
                              Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                              Product Line: 
                              Tesys D Contactors

                              Environment:
                              IEC contactors

                              Resolution:
                              The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                               

                              What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                              Issue:
                              Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                              Product Line:
                              NEMA combination starters

                              Environment:
                              Products sold and used in the United States

                              Resolution:
                              For contactors with screw clamp terminals:
                              stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                              stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                              solid cable: One or Two #18-8 AWG per terminal.

                              What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                              Issue:
                              Identifying maximum voltage of an LC1D contactor

                              Product Line:
                              TeSys D Contactors

                              Environment:
                              IEC contactors and starters used in North America

                              Cause:
                              n/a

                              Resolution:
                              IThe maximum voltage per UL and CSA is 600VAC. 
                               

                              Is part number LE3D12N7 available with latching on button?

                              No part number LE3D12N7 does not have latching push button.

                              What is the overload to suit LE3D12N7 star delta starter?

                              Overload to suit LE3D12N7 will be either LRD12, LRD14 or LRD16 depending on application.

                              What is the altitude derating for a TeSys D-Line contactor?

                              Issue:​
                              What is the altitude derating for a TeSys D-Line contactor?

                              Product Line:
                              Digest 177 Section 18 : Contactors and Starters, IEC

                              Environment:
                              North American Products

                              Resolution:
                              The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                              Voltage
                              3500m x 0.90
                              4000m x 0.80
                              4500m x 0.70
                              5000m x 0.60

                              Current
                              3500m x 0.92
                              4000m x 0.90
                              4500m x 0.88
                              5000m x 0.86

                              For example, an LC1D80 at 5000 meters:
                              - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                              - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                               

                              What is the difference between the LC1D1506N7 and the LC1D150N7?

                              The LC1D1506N7 can accept 5X25mm Bars aswell as Lugs or ring terminals. The LC1D150N7 only accepts cable lugs upto 120mm2.

                              What does the (3) designate in the part number LC1D123G7?

                              For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                              CTA-ID : 2053127

                              What is the part number for the replacement contactor for the LC1D1210N7?

                              The part number for the replacement contactor for the LC1D1210N7 is - LC1D12N7

                              For further information, visit the link below:-
                              https://www.schneider-electric.com.au/en/search/LC1D12N7
                              User-added image

                              Do the Everlink reversing contactors come with electrical interlocking?

                              Issue:
                              Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                              Product line:
                              Tesys D LC1D40A, LC1D50A, LC1D65A

                              Environment:
                              Everlink, all voltage codes

                              Cause:
                              Old D2 version offered an electrical interlock kit

                              Resolution:
                              The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                              What is the replacement base for a LE1D12N7

                              The base is not available on it's own but a replacement enclosure including base is a DE1DS1

                              Will the LC1D12U7 contactor go with the LADR2 timer?

                              Yes it will. the LADR2 timer slides on the top of the LC1D12U7 contactor.

                              what coil voltage is the LC1D25N7 TeSys D?

                              it is 415v a.c.

                               

                              What is the mechanical durability of a LC1D12U7 contactor

                               It is 15 Million cycles

                              Will a LC1D12F7 operate on 60V DC as a control voltage

                              No it will not

                              Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

                              Issue:  
                              Tesys D enclosed starter with a DC control 

                              Product Line:
                               Enclosed Tesys D line starters

                              Environment:
                              North American Products
                               
                              Cause:
                              DC control circuit 
                               
                              Resolution:
                              Yes but limited to 24 VDC.

                              What is the rating of auxiliaries on standard LC1D12U7 contactor

                               Rated at 10A thermal.

                              What is the Mechanical Interlock for the LC1D12F7 ?

                              LAD9R1V Is the code for the Mechanical and Electrical Interlock kit.

                              What is the part number for 4 pole, 415V Coil contactor and 3A overload?

                              The part number for 4 pole, 415V Coil contactor and 3A overload is LC1DT20N7 and LRD08



                              For more information on either item refer to:
                              https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1DT20N7
                              https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD08

                              Are contactors LC1D09U7 and LC1D12U7 the same size?

                              Contactors LC1D09 , LC1D12 Aand LC1D18 are all exactly the same physical size with AC coils.
                              Height = 77mm
                              Width = 45mm
                              Depth = 86mm

                              How Can the LC1D50AU7 Contactor be mounted?

                              Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                              See the attached datasheet for further information.

                              Need a LC2D323U7 reversing contactor

                              Use 2 x LC1D32U7 with a LAD9R1V reversing wiring kit

                              What is the code for a 40A 110VAC contactor ?

                              LC1D40AF7

                              What is the part number for a 3 pole 32amp 415VAC coil contactor and overload?

                              The part number for a 3 pole 32amp 415VAC coil contactor and overload is - LC1D32N7 & LRD32

                              For further information , visit links below:-
                              https://www.schneider-electric.com.au/en/search/LC1D32N7
                              https://www.schneider-electric.com.au/en/search/LRD32

                              User-added image

                              Looking for a LC1D50A.. with a 240v coil

                               Part code is LC1D50AU7

                              What is the Overload for LC1D50AU7 range is 37..50 Amps?

                              LRD350

                              Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                              No, correct kit is a LAD9R3.

                              What is the code for the 240VAC Coil for the LC1D32 Contactor ?

                              Part Code = LXD1U7 
                              The LXD1U7 also fits the LC1D09 - D38 Contactors

                              What is the replacement for a LP1D1210BD

                              You can use a LC1D12BD or for low consumption a LC1D12BL.

                              Are 600 volt replacement control coils available for LC2D1211?

                              Issue:
                              Looking for an LC2D1211 replacement control coils.

                              Product Line:
                              Tesys D Contactors

                              Environment:
                              LC2D1211

                              Resolution:
                              This coil is obsolete. Replace the contactor with the new TeSys product, LC2D12X7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.
                               

                              What does the 7 indicate before the coil voltage code on the LC1K****7** or LP1K****7** contactors?

                              Issue:
                              Suffix number 7 on the part number

                              Product Line:
                              Contactors and Overload Relays

                              Environment:
                              TeSys K Miniature Contactors and Overload Relays

                              Resolution:
                              The 7 indicates slip-on terminal connections instead of the standard screw clamp

                              What is the part number for LC1D32 contactor with 380V AC Coil?

                              The part number for LC1D32 contactor with 380V AC Coil is LC1D32N7.
                              Even though the LC1D32N7 has a 415V AC coil the coil has + or -  10% rating making the coil range 373.5 - 456.5V AC which is suitable for 380V AC.

                              For more information see:
                              https://www.schneider-electric.com/en/product-range-selector/664-tesys-d/?p_url=http%3A%2F%2Fwww.ops-ecat.schneider-electric.com%2Fecatalogue%2Fbrowse.do%3Fel_typ%3Dproduct%26cat_id%3DBU_POW_664_L3%26prd_id%3DLC1D32N7%26scp_id%3DZ000

                              What is the coil consumption or burden for the Tesys LC*D** contactors?

                              * 1 or 2
                              ** 09 through 38

                              Issue:
                              Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

                              Product Line: 
                              Contactors and Starters - IEC

                              Environment:
                              North American Products

                              Resolution:
                              All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

                              What is the code for the newer version of the LC1D40U7

                              That has been replaced with the Everlink LC1D40AU7

                              What is the part code for a 4P AC-1 rated 20Amp 24V ac coil contactor

                               The part code is LC1DT20B7

                              Does LC1D65AB7 3P (3 NO) TeSys Model D contactor have a normally opened and normally closed auxiliary contact?

                              What is the part number for the mechanical interlock to suit the LC1D12U7?

                              The part number for the mechanical interlock to suit the LC1D12U7 is "LAD9V2"

                              https://www.schneider-electric.com.au/en/search/LAD9V2



                               

                              What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                              17-25 Amps = LRD325
                              23-32 Amps =LRD332

                              What are the dimensions of LC1D40AB7 ?

                              Height 122 mm
                              Width 55 mm
                              Depth 120 mm
                              Product weight 1.4 kg

                              What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                              The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                              What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                              Issue:
                              Identifying the difference between LAD4TB and LAD4TBDL

                              Product Line:
                              IEC contactors and starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Identifying the difference between two similar part numbers

                              Resolution:
                              The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                               

                              What mechanical interlock should I use with the LC1D50A••?

                              The mechanical interlock LAD4CM is the correct one for use with the LC1D50A••.

                              See attached datasheet for futher information on the LAD4CM.

                              Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                              Issue:
                              Can new accessories be used on older style contactors

                              Product Line:
                              IEC contactors and starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Identifying product compatibility

                              Resolution:
                              Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                               

                              What is difference between LC1D50U7 and LC1D50AU7?

                              Following are the differences between the LC1D50U7 and the LC1D50AU7:

                              LC1D50AU7 has everlink terminals.
                              LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                              Whereas
                              LC1D50U7 contactors accommodate LRD33XX overloads.

                               

                              What is the part number for 60A contactor with 240V/415V coil?

                              What is the difference between a LC1D65A3U7 and LC1D65AU7?

                              The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                              see data sheets for comparrisons...
                              https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                              https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                              User-added image.................User-added image

                              Can the LC1D12BD be changed from a DC operated device to AC operation by changing the coil?

                              Issue:
                              Is it possible to swap AC coil to DC coil and vice versa on an LC1D12BD?

                              Product Line:
                              Tesys D Contactors

                              Environment:
                              LC1D12BD

                              Resolution:
                              No, the coil assemblies are not compatible nor can you replace the DC coils.
                               

                              What is the largest amperage D Line IEC contactor that can accomodate spring terminals, using a ``3`` after the amperage in the part number, such as an LC1D123G7?

                              The ``3`` form for spring terminals is available on 65A and below IEC contactors. On the 40, 50 and 65 amp devices the spring terminals are on the control circuit only. It is not available on 80A, 115A or 150A D Line contactors.


                              CTA-ID : 2053331

                              Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                              Issue:
                              Auxiliary contact modules for the LC1D and LC2D contactors

                              Product Line: 
                              Contactor and Starters - IEC

                              Environment:
                              North American Products

                              Resolution:
                              Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                              Front Mounting; maximum of 1 block per contactor:

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------1---------LADN11-----------LA1DN11
                              --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                              --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                              --2-----------0---------LADN20-----------LA1DN20
                              --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                              --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                              --0-----------2---------LADN02-----------LA1DN02
                              --2-----------2---------LADN22-----------LA1DN22
                              --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                              --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                              --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                              --3-----------1---------LADN31------------LA1DN31
                              --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                              --1-----------3---------LADN13------------LA1DN13
                              --4-----------0---------LADN40------------LA1DN40
                              --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                              --0-----------4---------LADN04------------LA1DN04




                              Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------0--------LADN10----------LA1DN10
                              --0-----------1--------LADN01----------LA1DN01

                              Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                              (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------1--------LAD8N11----------LA8DN11
                              --2-----------0--------LAD8N20----------LA8DN20
                              --0-----------2--------LAD8N02----------N/A

                              Footnotes:
                              {1} EN50 012 Machine Tool Terminal Markings
                              {2} (2) NO Sealed Dust Tight Contacts
                              {3} Gold Flash Contacts
                              {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                              {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                              {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts
                              Show More