TeSys Star Delta Starter, 3 x 3P (3 NO), 12A, 24VAC Coil

TeSys Star Delta Starter, 3 x 3P (3 NO), 12A, 24VAC Coil

TeSys Star Delta Starter, 3 x 3P (3 NO), 12A, 24VAC Coil

Item Number: LC3D12AB7

Retail
$1,980.40
RRP (Inc. GST)

Product Dimensions

Width icon

Width143 mm

Height icon

Height124 mm

Depth icon

Depth143 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

star delta starter

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Device presentation

pre-wired

[Ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit

Electrical durability

2 Mcycles 12 A AC-3 at Ue <= 440 V

Provided equipment

protective cover

Mounting support

plate

Standards

  • IEC 60947-4-1
  • EN 60947-4-1
  • CSA C22.2 No 14
  • IEC 60947-5-1
  • UL 508
  • EN 60947-5-1
    • Product certifications

    • GOST
    • UL
    • BV
    • CCC
    • GL
    • CSA
    • LROS (Lloyds register of shipping)
    • DNV
    • RINA
      • Connections - terminals

      • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
      • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
      • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
      • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
      • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
      • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
      • power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
      • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
      • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
      • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
      • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
      • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
        • Mechanical durability

          15 Mcycles

          Width

          143 mm

          Height

          124 mm

          Depth

          143 mm

          Net weight

          1.53 kg

          Insulation resistance

          > 10 MOhm for signalling circuit

          IP degree of protection

          IP20 front face conforming to IEC 60529

          Ambient air temperature for storage

          -60-80 °C

          Ambient air temperature for operation

          -40-70 °C at Uc

          REACh free of SVHC

          Yes

          EU RoHS Directive

          Compliant

          Toxic heavy metal free

          Yes

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

           Pro-active China RoHS declaration (out of China RoHS legal scope)

          Environmental Disclosure

          ENVPEP080208EN

          Circularity Profile

          ENVEOLI100418

          Others

          Product name

          TeSys D

          Device short name

          LC3D

          Contactor application

          motor control

          Utilisation category

          AC-3

          Poles description

          3 x 3P

          Pole contact composition

          3 x 3 NO

          Motor power kW

        • 11 kW at 380/400 V AC 50/60 Hz
        • 11 kW at 415 V AC 50/60 Hz
        • 11 kW at 440 V AC 50/60 Hz
        • 5.5 kW at 220/230 V AC 50/60 Hz
          • Control circuit type

            AC at 50/60 Hz

            [Uc] control circuit voltage

            24 V AC 50/60 Hz

            Auxiliary contact composition

            1 NC for KM1 star contactor

            [Uimp] rated impulse withstand voltage

            6 kV conforming to IEC 60947

            Overvoltage category

            III

            [Ui] rated insulation voltage

          • power circuit: 690 V conforming to IEC 60947-4-1
          • power circuit: 600 V CSA certified
          • power circuit: 600 V UL certified
          • signalling circuit: 690 V conforming to IEC 60947-1
          • signalling circuit: 600 V CSA certified
          • signalling circuit: 600 V UL certified
            • Interlocking type

              mechanical

              Tightening torque

            • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
            • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
              • Maximum operating rate

                30 cyc/h 60 °C

                Starting time

                30 s

                Coil technology

                without built-in suppressor module

                Control circuit voltage limits

              • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
              • operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
              • operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
                • Inrush power in VA

                • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
                • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
                  • Hold-in power consumption in VA

                  • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
                  • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
                    • Heat dissipation

                      2-3 W at 50/60 Hz

                      Auxiliary contacts type

                    • mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC
                    • mirror contact conforming to IEC 60947-4-1 3 x 1 NC
                      • Signalling circuit frequency

                        25...400 Hz

                        Minimum switching current

                        5 mA for signalling circuit

                        Switching voltage

                        17 V for signalling circuit

                        Non-overlap time

                      • 1.5 ms on de-energisation between NC and NO contact
                      • 1.5 ms on energisation between NC and NO contact
                        • Power range

                        • 4-6 kW at 200-240 V 3 phases
                        • 7-11 kW at 380-440 V 3 phases
                          • Motor starter type

                            star delta starter

                            Contactor coil voltage

                            24 V AC standard

                            Protective treatment

                            TH conforming to IEC 60068-2-30

                            Pollution degree

                            3

                            Operating altitude

                            3000 m without derating

                            Fire resistance

                            850 °C conforming to IEC 60695-2-1

                            Flame retardance

                            V1 conforming to UL 94

                            Mechanical robustness

                          • vibrations contactor open: 2 Gn, 5...300 Hz
                          • vibrations contactor closed: 4 Gn, 5...300 Hz
                          • shocks contactor open: 10 Gn for 11 ms
                          • shocks contactor closed: 15 Gn for 11 ms
                            • Package 1 Weight

                              1.59 kg

                              Package 1 Height

                              1.95 dm

                              Package 1 width

                              1.95 dm

                              Package 1 Length

                              2.6 dm

                              WEEE

                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                              PVC free

                              Yes
                              Show all specifications

                              Documents & downloads

                              hide show

                              Frequently Asked Questions

                              hide show

                              Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                              Issue:
                              Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                              Product Line: 
                              Tesys D Contactors

                              Environment:
                              IEC contactors

                              Resolution:
                              The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                               

                              What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                              Issue:
                              Identifying replacement coils for tesys D non-reversing and reversing conactors

                              Product Line:
                              IEC Contactors and Starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Replacement coil is needed

                              Resolution:
                              DC replacement coils are not available.
                              AC Coils are 50/60 hertz for voltages as listed below:

                              Volts - Part Number
                              12 ____ LXD1J7
                              21 ____ LXD1Z7
                              24 ____ LXD1B7
                              32 ____ LXD1C7
                              36 ____ LXD1CC7
                              42 ____ LXD1D7
                              48 ____ LXD1E7
                              60 ____ LXD1EE7
                              100 ___ LXD1K7 ( never brought to North America )
                              110 ___ LXD1F7
                              115 ___ LXD1FE7
                              120 ___ LXD1G7
                              127 ___ LXD1FC7
                              200 ___ LXD1L7
                              208 ___ LXD1LE7
                              220 ___ LXD1M7
                              230 ___ LXD1P7
                              240 ___ LXD1U7
                              277 ___ LXD1W7
                              380 ___ LXD1Q7
                              400 ___ LXD1V7
                              415 ___ LXD1N7
                              440 ___ LXD1R7
                              480 ___ LXD1T7
                              575 ___ LXD1SC7
                              600 ___ LXD1X7
                              690 ___ LXD1Y7


                              Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                              What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                              Issue:
                              Identifying maximum voltage of an LC1D contactor

                              Product Line:
                              TeSys D Contactors

                              Environment:
                              IEC contactors and starters used in North America

                              Cause:
                              n/a

                              Resolution:
                              IThe maximum voltage per UL and CSA is 600VAC. 
                               

                              What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                              Issue:
                              Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                              Product Line:
                              NEMA combination starters

                              Environment:
                              Products sold and used in the United States

                              Resolution:
                              For contactors with screw clamp terminals:
                              stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                              stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                              solid cable: One or Two #18-8 AWG per terminal.

                              What is the altitude derating for a TeSys D-Line contactor?

                              Issue:​
                              What is the altitude derating for a TeSys D-Line contactor?

                              Product Line:
                              Digest 177 Section 18 : Contactors and Starters, IEC

                              Environment:
                              North American Products

                              Resolution:
                              The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                              Voltage
                              3500m x 0.90
                              4000m x 0.80
                              4500m x 0.70
                              5000m x 0.60

                              Current
                              3500m x 0.92
                              4000m x 0.90
                              4500m x 0.88
                              5000m x 0.86

                              For example, an LC1D80 at 5000 meters:
                              - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                              - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                               

                              Do the Everlink reversing contactors come with electrical interlocking?

                              Issue:
                              Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                              Product line:
                              Tesys D LC1D40A, LC1D50A, LC1D65A

                              Environment:
                              Everlink, all voltage codes

                              Cause:
                              Old D2 version offered an electrical interlock kit

                              Resolution:
                              The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                              Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

                              Issue:  
                              Tesys D enclosed starter with a DC control 

                              Product Line:
                               Enclosed Tesys D line starters

                              Environment:
                              North American Products
                               
                              Cause:
                              DC control circuit 
                               
                              Resolution:
                              Yes but limited to 24 VDC.

                              What does the (3) designate in the part number LC1D123G7?

                              For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                              CTA-ID : 2053127

                              Is part number LE3D12N7 available with latching on button?

                              No part number LE3D12N7 does not have latching push button.

                              What is the replacement for a LP1D1210BD

                              You can use a LC1D12BD or for low consumption a LC1D12BL.

                              What is the part code for a 4P AC-1 rated 20Amp 24V ac coil contactor

                               The part code is LC1DT20B7

                              What is the code for a 24vac coil to suit LC1D18B7 Contactor ?

                              24V AC Coil =  LXD1B7
                              Show More