TeSys D Reversing Contactor-3 Pole AC3 <= 440V 40A, 48 - 130V ACDC Coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 40A, 48 - 130V ACDC Coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 40A, 48 - 130V ACDC Coil

Item Number: LC2D40AEHE

Retail
$4,055.62
RRP (Inc. GST)

Product Dimensions

Width icon

Width119 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

reversing contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Device presentation

preassembled with reversing power busbar

[Ue] rated operational voltage

power circuit: 690 V AC 25...400 Hz

[Ie] rated operational current

  • 60 A (at <60 °C) at <= 440 V AC-1 for power circuit
  • 40 A (at <60 °C) at <= 440 V AC-3 for power circuit
    • Electrical durability

    • 2 Mcycles 35 A AC-3 at Ue <= 440 V
    • 0.7 Mcycles 60 A AC-1 at Ue <= 440 V
      • Mounting support

      • rail
      • plate
        • Standards

        • EN/IEC 60947-4-1
        • EN/IEC 60947-5-1
        • UL 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • CCC
          • CSA
          • EAC
          • UL
          • KC
          • DNV-GL
          • LROS (Lloyds register of shipping)
            • Connections - terminals

            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
              • Mechanical durability

                6 Mcycles

                Insulation resistance

                > 10 MOhm for signalling circuit

                IP degree of protection

                IP20 front face conforming to IEC 60529

                Ambient air temperature for operation

              • -40-60 °C
              • 60-70 °C with derating
                • Ambient air temperature for storage

                  -60-80 °C

                  Height

                  122 mm

                  Width

                  119 mm

                  Depth

                  120 mm

                  Net weight

                  2.154 kg

                  EU RoHS Directive

                  Compliant

                  Mercury free

                  Yes

                  RoHS exemption information

                  Yes

                  China RoHS Regulation

                  Product out of China RoHS scope. Substance declaration for your information

                  Environmental Disclosure

                  ENVPEP1607010EN

                  Circularity Profile

                  ENVEOLI1607010EN

                  Others

                  Product name

                  TeSys D Green

                  Device short name

                  LC2D

                  Contactor application

                • motor control
                • resistive load
                  • Utilisation category

                  • AC-1
                  • AC-3
                    • Poles description

                      3P

                      Pole contact composition

                      3 NO

                      Motor power kW

                    • 11 kW at 220...230 V AC 50 Hz
                    • 18.5 kW at 380...400 V AC 50 Hz
                    • 22 kW at 415 V AC 50 Hz
                    • 22 kW at 440 V AC 50 Hz
                    • 22 kW at 500 V AC 50 Hz
                    • 30 kW at 660...690 V AC 50 Hz
                      • Motor power hp

                      • 3 hp at 115 V AC 60 Hz for 1 phase motors
                      • 5 hp at 230/240 V AC 60 Hz for 1 phase motors
                      • 10 hp at 200/208 V AC 60 Hz for 3 phases motors
                      • 10 hp at 230/240 V AC 60 Hz for 3 phases motors
                      • 30 hp at 460/480 V AC 60 Hz for 3 phases motors
                      • 30 hp at 575/600 V AC 60 Hz for 3 phases motors
                        • Control circuit type

                        • AC at 50/60 Hz AC/DC electronic
                        • DC AC/DC electronic
                          • [Uc] control circuit voltage

                          • 48...130 V AC 50/60 Hz
                          • 48...130 V DC
                            • Auxiliary contact composition

                              1 NO + 1 NC

                              [Uimp] rated impulse withstand voltage

                              6 kV conforming to IEC 60947

                              Overvoltage category

                              III

                              [Ith] conventional free air thermal current

                            • 10 A (at 60 °C) for signalling circuit
                            • 60 A (at 60 °C) for power circuit
                              • Irms rated making capacity

                              • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                              • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                              • 800 A at 440 V for power circuit conforming to IEC 60947
                                • Rated breaking capacity

                                  800 A at 440 V for power circuit conforming to IEC 60947

                                  [Icw] rated short-time withstand current

                                • 100 A - 1 s for signalling circuit
                                • 120 A - 500 ms for signalling circuit
                                • 140 A - 100 ms for signalling circuit
                                • 320 A 40 °C - 10 s for power circuit
                                • 720 A 40 °C - 1 s for power circuit
                                • 72 A 40 °C - 10 min for power circuit
                                • 165 A 40 °C - 1 min for power circuit
                                  • Associated fuse rating

                                  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                                  • 80 A gG at <= 690 V coordination type 1 for power circuit
                                  • 80 A gG at <= 690 V coordination type 2 for power circuit
                                    • Average impedance

                                      1.5 mOhm - Ith 60 A 50 Hz for power circuit

                                      [Ui] rated insulation voltage

                                    • power circuit: 690 V conforming to IEC 60947-4-1
                                    • signalling circuit: 690 V conforming to IEC 60947-1
                                      • Power dissipation per pole

                                      • 2.4 W AC-3
                                      • 5.4 W AC-1
                                        • Protective cover

                                          with

                                          Interlocking type

                                          mechanical

                                          Tightening torque

                                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                        • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                        • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                          • Operating time

                                          • 55...65 ms closing
                                          • 20...120 ms opening (date code >= 17221)
                                          • 20...80 ms opening (date code >= 18011)
                                            • Safety reliability level

                                            • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                            • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                              • Maximum operating rate

                                                3600 cyc/h 60 °C

                                                Coil technology

                                                built-in bidirectional peak limiting

                                                Control circuit voltage limits

                                              • <= 0.1 Uc (-40-70 °C):drop-out AC/DC
                                              • 0.85...1.1 Uc (-40-60 °C):operational AC/DC
                                              • 1...1.1 Uc (60-70 °C):operational AC/DC
                                                • Inrush power in VA

                                                  23-23 VA 50/60 Hz (at 20 °C)

                                                  Inrush power in W

                                                  19-19 W at 20 °C

                                                  Hold-in power consumption in VA

                                                  1.4-1.4 VA (at 20 °C) 50/60 Hz

                                                  Hold-in power consumption in W

                                                  0.9-0.9 W at 20 °C

                                                  Heat dissipation

                                                  0.9-0.9 W at 50/60 Hz

                                                  Auxiliary contacts type

                                                • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                                • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                  • Signalling circuit frequency

                                                    25...400 Hz

                                                    Minimum switching current

                                                    5 mA for signalling circuit

                                                    Minimum switching voltage

                                                    17 V for signalling circuit

                                                    Non-overlap time

                                                  • 1.5 ms on de-energisation between NC and NO contact
                                                  • 1.5 ms on energisation between NC and NO contact
                                                    • Compatibility code

                                                      LC2D

                                                      Protective treatment

                                                      TH conforming to IEC 60068-2-30

                                                      Pollution degree

                                                      3

                                                      Operating altitude

                                                      0...3000 m

                                                      Fire resistance

                                                      850 °C conforming to IEC 60695-2-1

                                                      Flame retardance

                                                      V1 conforming to UL 94

                                                      Mechanical robustness

                                                    • vibrations contactor open: 2 Gn, 5...300 Hz
                                                    • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                    • shocks contactor open: 10 Gn for 11 ms
                                                    • shocks contactor closed: 15 Gn for 11 ms
                                                      • Package 1 Weight

                                                        2.154 kg

                                                        Package 1 Height

                                                        1.4 dm

                                                        Package 1 width

                                                        1.62 dm

                                                        Package 1 Length

                                                        1.98 dm

                                                        WEEE

                                                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                        Halogen content performance

                                                        Halogen free plastic parts & cables product
                                                        Show all specifications

                                                        Documents & downloads

                                                        hide show
                                                        Filter items
                                                        • All

                                                        • Product Brochures

                                                        • CAD Files and Packs

                                                        • Technical Data Catalogues

                                                        • Product Environmental

                                                        • End of Life Manual

                                                        • Installation Instruction

                                                        • Declaration of Conformity

                                                        Frequently Asked Questions

                                                        hide show

                                                        Are 21 volt replacement control coils available for LC2D4011?

                                                        Issue:
                                                        LC2D4011 replacement coil

                                                        Prodcut Line:
                                                        IEC Contactors and Starters

                                                        Product Line:
                                                        TeSys™ D Contactors 

                                                        Resolution:
                                                        21VAC coils are not an option on these reversing change over contactors.
                                                        We do offer the B6 or B7 which is 24VAC.  The tolerance on the 24V coil is 85 to 110%.  So the 24VAC coil will work down to 20.4VAC. 

                                                        Note the LC2D4011 series is obsolete.

                                                        What is the code for a 40A 110VAC contactor ?

                                                        LC1D40AF7

                                                        Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                                        No, correct kit is a LAD9R3.

                                                        What is the code for the newer version of the LC1D40U7

                                                        That has been replaced with the Everlink LC1D40AU7

                                                        Do the Everlink reversing contactors come with electrical interlocking?

                                                        Issue:
                                                        Electrical interlock kit for the LC1D65A Everlnk contactors.

                                                        Product line:
                                                        Tesys D LC1D40A, LC1D50A, LC1D65A

                                                        Environment:
                                                        Everlink, all voltage codes

                                                        Cause:
                                                        Old D2 version offered an electrical interlock kit

                                                        Resolution:
                                                        The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                        What is the color scheme of the Tesys D-Line contactors?

                                                        Issue:
                                                        Looking for different color scheme of the Tesys D-Line contactors.

                                                        Product Line:
                                                        Tesys D Contactors

                                                        Environment:
                                                        LC1D contactors

                                                        Resolution:
                                                        Beige and dark gray.
                                                         
                                                        Show More