TeSys D Reversing Contactor-3 Pole AC3 <= 440V 38A, 100 - 250V ACDC Coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 38A, 100 - 250V ACDC Coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 38A, 100 - 250V ACDC Coil

Item Number: LC2D38KUE

Retail
$1,927.17
RRP (Inc. GST)

Product Dimensions

Width icon

Width90 mm

Height icon

Height85 mm

Depth icon

Depth92 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

reversing contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Device presentation

preassembled with reversing power busbar

[Ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

  • 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
    • Electrical durability

    • 1.8 Mcycles 35 A AC-3 at Ue <= 440 V
    • 0.9 Mcycles 50 A AC-1 at Ue <= 440 V
      • Mounting support

      • rail
      • plate
        • Standards

        • EN/IEC 60947-4-1
        • EN/IEC 60947-5-1
        • UL 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • CCC
          • CSA
          • EAC
          • UL
          • KC
          • DNV-GL
          • LROS (Lloyds register of shipping)
            • Connections - terminals

            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
            • power circuit: screw clamp terminals 1 cable(s) 2.5-10 mm²flexible without cable end
            • power circuit: screw clamp terminals 2 cable(s) 2.5-10 mm²flexible without cable end
            • power circuit: screw clamp terminals 1 cable(s) 1-10 mm²flexible with cable end
            • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible with cable end
            • power circuit: screw clamp terminals 1 cable(s) 1.5-10 mm²solid
            • power circuit: screw clamp terminals 2 cable(s) 2.5-10 mm²solid
              • Mechanical durability

                15 Mcycles

                Insulation resistance

                > 10 MOhm for signalling circuit

                IP degree of protection

                IP20 front face conforming to IEC 60529

                Ambient air temperature for operation

              • -40-60 °C
              • 60-70 °C with derating
                • Ambient air temperature for storage

                  -60-80 °C

                  Height

                  85 mm

                  Width

                  90 mm

                  Depth

                  92 mm

                  Net weight

                  0.933 kg

                  EU RoHS Directive

                  Compliant

                  Mercury free

                  Yes

                  RoHS exemption information

                  Yes

                  China RoHS Regulation

                  Product out of China RoHS scope. Substance declaration for your information

                  Environmental Disclosure

                  ENVPEP1609002

                  Circularity Profile

                  ENVEOLI1609002EN

                  Others

                  Product name

                  TeSys D Green

                  Device short name

                  LC2D

                  Contactor application

                • resistive load
                • motor control
                  • Utilisation category

                  • AC-3
                  • AC-1
                    • Poles description

                      3P

                      Pole contact composition

                      3 NO

                      Motor power kW

                    • 9 kW at 220...230 V AC 50 Hz
                    • 18.5 kW at 380...400 V AC 50 Hz
                    • 18.5 kW at 415 V AC 50 Hz
                    • 18.5 kW at 440 V AC 50 Hz
                    • 18.5 kW at 500 V AC 50 Hz
                    • 18.5 kW at 660...690 V AC 50 Hz
                      • Motor power hp

                      • 2 hp at 115 V AC 60 Hz for 1 phase motors
                      • 5 hp at 230/240 V AC 60 Hz for 1 phase motors
                      • 10 hp at 200/208 V AC 60 Hz for 3 phases motors
                      • 10 hp at 230/240 V AC 60 Hz for 3 phases motors
                      • 20 hp at 460/480 V AC 60 Hz for 3 phases motors
                      • 25 hp at 575/600 V AC 60 Hz for 3 phases motors
                        • Control circuit type

                        • AC at 50/60 Hz AC/DC electronic
                        • DC AC/DC electronic
                          • [Uc] control circuit voltage

                          • 100...250 V AC 50/60 Hz
                          • 100...250 V DC
                            • Auxiliary contact composition

                              1 NO + 1 NC

                              [Uimp] rated impulse withstand voltage

                              6 kV conforming to IEC 60947

                              Overvoltage category

                              III

                              [Ith] conventional free air thermal current

                            • 10 A (at 60 °C) for signalling circuit
                            • 50 A (at 60 °C) for power circuit
                              • Irms rated making capacity

                              • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                              • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                              • 550 A at 440 V for power circuit conforming to IEC 60947
                                • Rated breaking capacity

                                  550 A at 440 V for power circuit conforming to IEC 60947

                                  [Icw] rated short-time withstand current

                                • 100 A - 1 s for signalling circuit
                                • 120 A - 500 ms for signalling circuit
                                • 140 A - 100 ms for signalling circuit
                                • 430 A 40 °C - 1 s for power circuit
                                • 60 A 40 °C - 10 min for power circuit
                                • 150 A 40 °C - 1 min for power circuit
                                • 310 A 40 °C - 10 s for power circuit
                                  • Associated fuse rating

                                  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                                  • 63 A gG at <= 690 V coordination type 1 for power circuit
                                  • 63 A gG at <= 690 V coordination type 2 for power circuit
                                    • Average impedance

                                      2 mOhm - Ith 50 A 50 Hz for power circuit

                                      [Ui] rated insulation voltage

                                    • power circuit: 690 V conforming to IEC 60947-4-1
                                    • signalling circuit: 690 V conforming to IEC 60947-1
                                      • Power dissipation per pole

                                      • 5 W AC-1
                                      • 3 W AC-3
                                        • Protective cover

                                          with

                                          Interlocking type

                                          mechanical

                                          Tightening torque

                                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                        • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                        • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                          • Operating time

                                          • 45...55 ms closing
                                          • 20...90 ms opening
                                            • Safety reliability level

                                            • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                            • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                              • Maximum operating rate

                                                3600 cyc/h 60 °C

                                                Coil technology

                                                built-in bidirectional peak limiting

                                                Control circuit voltage limits

                                              • <= 0.1 Uc (-40-70 °C):drop-out AC/DC
                                              • 0.85...1.1 Uc (-40-60 °C):operational AC/DC
                                              • 1...1.1 Uc (60-70 °C):operational AC/DC
                                                • Inrush power in VA

                                                  25-25 VA 50/60 Hz (at 20 °C)

                                                  Inrush power in W

                                                  18-18 W at 20 °C

                                                  Hold-in power consumption in VA

                                                  1.6-1.6 VA (at 20 °C) 50/60 Hz

                                                  Hold-in power consumption in W

                                                  1.1-1.1 W at 20 °C

                                                  Heat dissipation

                                                  1.1-1.1 W at 50/60 Hz

                                                  Auxiliary contacts type

                                                • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                                • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                  • Signalling circuit frequency

                                                    25...400 Hz

                                                    Minimum switching current

                                                    5 mA for signalling circuit

                                                    Minimum switching voltage

                                                    17 V for signalling circuit

                                                    Non-overlap time

                                                  • 1.5 ms on de-energisation between NC and NO contact
                                                  • 1.5 ms on energisation between NC and NO contact
                                                    • Compatibility code

                                                      LC2D

                                                      Protective treatment

                                                      TH conforming to IEC 60068-2-30

                                                      Pollution degree

                                                      3

                                                      Operating altitude

                                                      0...3000 m

                                                      Fire resistance

                                                      850 °C conforming to IEC 60695-2-1

                                                      Flame retardance

                                                      V1 conforming to UL 94

                                                      Mechanical robustness

                                                    • vibrations contactor open: 2 Gn, 5...300 Hz
                                                    • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                    • shocks contactor closed: 15 Gn for 11 ms
                                                    • shocks contactor open: 8 Gn for 11 ms
                                                      • Unit Type of Package 1

                                                        PCE

                                                        Number of Units in Package 1

                                                        1

                                                        Package 1 Weight

                                                        1.019 kg

                                                        Package 1 Height

                                                        11.5 cm

                                                        Package 1 width

                                                        11.3 cm

                                                        Package 1 Length

                                                        14 cm

                                                        Unit Type of Package 2

                                                        S02

                                                        Number of Units in Package 2

                                                        5

                                                        Package 2 Weight

                                                        5.425 kg

                                                        Package 2 Height

                                                        15 cm

                                                        Package 2 width

                                                        30 cm

                                                        Package 2 Length

                                                        40 cm

                                                        WEEE

                                                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                        Halogen content performance

                                                        Halogen free plastic parts & cables product
                                                        Show all specifications

                                                        Documents & downloads

                                                        hide show
                                                        Filter items
                                                        • All

                                                        • Product Brochures

                                                        • CAD Files and Packs

                                                        • Technical Data Catalogues

                                                        • Product Environmental

                                                        • End of Life Manual

                                                        • Installation Instruction

                                                        Frequently Asked Questions

                                                        hide show

                                                        Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                        Issue:
                                                        Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                        Product Line: 
                                                        Tesys D Contactors

                                                        Environment:
                                                        IEC contactors

                                                        Resolution:
                                                        The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                         

                                                        Need a LC2D323U7 reversing contactor

                                                        Use 2 x LC1D32U7 with a LAD9R1V reversing wiring kit

                                                        Are 48 volt AC replacement control coils available for LC2D1801?

                                                        Issue:
                                                        48 VAC replacement control coils for LC2D1801.

                                                        Product Line:
                                                        Tesys D Contactors

                                                        Environment:
                                                        LC1D1810

                                                        Resolution:
                                                        This coil is obsolete. Replace the contactor with the new TeSys product, LC2D18E7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.
                                                         

                                                        What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                        Issue:
                                                        Identifying maximum voltage of an LC1D contactor

                                                        Product Line:
                                                        TeSys D Contactors

                                                        Environment:
                                                        IEC contactors and starters used in North America

                                                        Cause:
                                                        n/a

                                                        Resolution:
                                                        IThe maximum voltage per UL and CSA is 600VAC. 
                                                         

                                                        What is the code for the 240VAC Coil for the LC1D32 Contactor ?

                                                        Part Code = LXD1U7 
                                                        The LXD1U7 also fits the LC1D09 - D38 Contactors

                                                        What is the interlock for LC1D38***

                                                        As the interlock is not sold separate the part number needed is LAD9R1V
                                                        Show More