TeSys D reversing contactor-3P-AC3 440V 18A 48-130V  ACDC coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 18A, 48 - 130V ACDC Coil

Catalogue Number: LC2D18EHE
TeSys D reversing contactor-3P-AC3 440V 18A 48-130V  ACDC coil
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D Green
Product or component type
reversing contactor
Device short name
LC2D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-3
    • AC-1
      • Device presentation
        preassembled with reversing power busbar
        Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
        power circuit: <= 690 V AC 25...400 Hz
        [Ie] rated operational current
      • 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      • 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
        • Motor power kW
        • 4 kW at 220...230 V AC 50 Hz
        • 7.5 kW at 380...400 V AC 50 Hz
        • 9 kW at 415 V AC 50 Hz
        • 9 kW at 440 V AC 50 Hz
        • 10 kW at 500 V AC 50 Hz
        • 10 kW at 660...690 V AC 50 Hz
          • Motor power hp
          • 1 hp at 115 V AC 60 Hz for 1 phase motors
          • 3 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 5 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 5 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 10 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 15 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Control circuit type
            • AC at 50/60 Hz AC/DC electronic
            • DC AC/DC electronic
              • [Uc] control circuit voltage
              • 48...130 V AC 50/60 Hz
              • 48...130 V DC
                • Auxiliary contact composition
                  1 NO + 1 NC
                  [Uimp] rated impulse withstand voltage
                  6 kV conforming to IEC 60947
                  Overvoltage category
                  III
                  [Ith] conventional free air thermal current
                • 32 A (at 60 °C) for power circuit
                • 10 A (at 60 °C) for signalling circuit
                  • Irms rated making capacity
                  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                  • 300 A at 440 V for power circuit conforming to IEC 60947
                    • Rated breaking capacity
                      300 A at 440 V for power circuit conforming to IEC 60947
                      [Icw] rated short-time withstand current
                    • 40 A 40 °C - 10 min for power circuit
                    • 84 A 40 °C - 1 min for power circuit
                    • 145 A 40 °C - 10 s for power circuit
                    • 240 A 40 °C - 1 s for power circuit
                    • 100 A - 1 s for signalling circuit
                    • 120 A - 500 ms for signalling circuit
                    • 140 A - 100 ms for signalling circuit
                      • Associated fuse rating
                      • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                      • 50 A gG at <= 690 V coordination type 1 for power circuit
                      • 35 A gG at <= 690 V coordination type 2 for power circuit
                        • Average impedance
                          2.5 mOhm - Ith 32 A 50 Hz for power circuit
                          [Ui] rated insulation voltage
                        • power circuit: 690 V conforming to IEC 60947-4-1
                        • signalling circuit: 690 V conforming to IEC 60947-1
                          • Electrical durability
                          • 2.2 Mcycles 15 A AC-3 at Ue <= 440 V
                          • 0.9 Mcycles 32 A AC-1 at Ue <= 440 V
                            • Power dissipation per pole
                            • 2.5 W AC-1
                            • 0.8 W AC-3
                              • Protective cover
                                with
                                Interlocking type
                                mechanical
                                Mounting support
                              • plate
                              • rail
                                • Standards
                                • EN/IEC 60947-4-1
                                • EN/IEC 60947-5-1
                                • UL 60947-4-1
                                • CSA C22.2 No 60947-4-1
                                  • Product certifications
                                  • CCC
                                  • CSA
                                  • EAC
                                  • UL
                                  • KC
                                  • DNV-GL
                                  • LROS (Lloyds register of shipping)
                                    • Connections - terminals
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
                                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
                                    • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²flexible without cable end
                                    • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible without cable end
                                    • power circuit: screw clamp terminals 1 cable(s) 1-6 mm²flexible with cable end
                                    • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end
                                    • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²solid
                                    • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²solid
                                      • Tightening torque
                                      • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                        • Operating time
                                        • 45...55 ms closing
                                        • 20...90 ms opening
                                          • Safety reliability level
                                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                            • Mechanical durability
                                              15 Mcycles
                                              Maximum operating rate
                                              3600 cyc/h 60 °C
                                              Coil technology
                                              built-in bidirectional peak limiting
                                              Control circuit voltage limits
                                            • drop-out: <= 0.1 Uc (at 60 °C)
                                            • operational: 0.85...1.1 Uc (at 60 °C)
                                              • Inrush power in VA
                                                25-25 VA 50/60 Hz (at 20 °C)
                                                Inrush power in W
                                                24-24 W at 20 °C
                                                Hold-in power consumption in VA
                                                1.3-1.3 VA (at 20 °C) 50/60 Hz
                                                Hold-in power consumption in W
                                                0.8-0.8 W at 20 °C
                                                Heat dissipation
                                                0.8-0.8 W at 50/60 Hz
                                                Auxiliary contacts type
                                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                • Signalling circuit frequency
                                                  25...400 Hz
                                                  Minimum switching current
                                                  5 mA for signalling circuit
                                                  Minimum switching voltage
                                                  17 V for signalling circuit
                                                  Non-overlap time
                                                • 1.5 ms on de-energisation between NC and NO contact
                                                • 1.5 ms on energisation between NC and NO contact
                                                  • Insulation resistance
                                                    > 10 MOhm for signalling circuit
                                                    Compatibility code
                                                    LC2D
                                                    IP degree of protection
                                                    IP20 front face conforming to IEC 60529
                                                    Protective treatment
                                                    TH conforming to IEC 60068-2-30
                                                    Pollution degree
                                                    3
                                                    Ambient air temperature for operation
                                                    -25-60 °C
                                                    Ambient air temperature for storage
                                                    -60-80 °C
                                                    Permissible ambient air temperature around the device
                                                    -40-70 °C at Uc
                                                    Operating altitude
                                                    3000 m without
                                                    Fire resistance
                                                    850 °C conforming to IEC 60695-2-1
                                                    Flame retardance
                                                    V1 conforming to UL 94
                                                    Mechanical robustness
                                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                  • shocks contactor open: 10 Gn for 11 ms
                                                  • shocks contactor closed: 15 Gn for 11 ms
                                                    • Height
                                                      77 mm
                                                      Width
                                                      90 mm
                                                      Depth
                                                      86 mm
                                                      Net weight
                                                      0.803 kg
                                                      Sustainable offer status
                                                      Green Premium product
                                                      EU RoHS Directive
                                                      Compliant
                                                      Mercury free
                                                      Yes
                                                      RoHS exemption information
                                                      Yes
                                                      China RoHS Regulation
                                                      Product out of China RoHS scope. Substance declaration for your information
                                                      Environmental Disclosure
                                                      ENVPEP1609001EN
                                                      Circularity Profile
                                                      ENVEOLI1609001EN
                                                      WEEE
                                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                      Halogen content performance
                                                      Halogen free plastic parts & cables product
                                                      Warranty
                                                      18 months

                                                      Documents & downloads

                                                      hide show
                                                      Filter items
                                                      • All

                                                      • Product Brochures

                                                      • CAD Files and Packs

                                                      • Technical Data Catalogues

                                                      • Product Environmental

                                                      • End of Life Manual

                                                      • Installation Instruction

                                                      • Declaration of Conformity

                                                      Frequently Asked Questions

                                                      hide show

                                                      Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                      Issue:
                                                      Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                      Product Line: 
                                                      Tesys D Contactors

                                                      Environment:
                                                      IEC contactors

                                                      Resolution:
                                                      The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                       

                                                      Are 48 volt AC replacement control coils available for LC2D1801?

                                                      Issue:
                                                      Checking if a 48 volt AC replacement coil is available for an LC2D1801.

                                                      Product Line:
                                                      Tesys D Contactors

                                                      Environment:
                                                      LC1D1810

                                                      Resolution:
                                                      This coil is obsolete. Replace the contactor with the new TeSys product, LC2D18E7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.
                                                       

                                                      What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                      Issue:
                                                      Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                      Product Line:
                                                      IEC Contactors and Starters

                                                      Environment:
                                                      Products sold and used in the United States

                                                      Cause:
                                                      Replacement coil is needed

                                                      Resolution:
                                                      DC replacement coils are not available.
                                                      AC Coils are 50/60 hertz for voltages as listed below:

                                                      Volts - Part Number
                                                      12 ____ LXD1J7
                                                      21 ____ LXD1Z7
                                                      24 ____ LXD1B7
                                                      32 ____ LXD1C7
                                                      36 ____ LXD1CC7
                                                      42 ____ LXD1D7
                                                      48 ____ LXD1E7
                                                      60 ____ LXD1EE7
                                                      100 ___ LXD1K7 ( never brought to North America )
                                                      110 ___ LXD1F7
                                                      115 ___ LXD1FE7
                                                      120 ___ LXD1G7
                                                      127 ___ LXD1FC7
                                                      200 ___ LXD1L7
                                                      208 ___ LXD1LE7
                                                      220 ___ LXD1M7
                                                      230 ___ LXD1P7
                                                      240 ___ LXD1U7
                                                      277 ___ LXD1W7
                                                      380 ___ LXD1Q7
                                                      400 ___ LXD1V7
                                                      415 ___ LXD1N7
                                                      440 ___ LXD1R7
                                                      480 ___ LXD1T7
                                                      575 ___ LXD1SC7
                                                      600 ___ LXD1X7
                                                      690 ___ LXD1Y7


                                                      Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                      Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

                                                      Issue:  
                                                      Tesys D enclosed starter with a DC control 

                                                      Product Line:
                                                       Enclosed Tesys D line starters

                                                      Environment:
                                                      North American Products
                                                       
                                                      Cause:
                                                      DC control circuit 
                                                       
                                                      Resolution:
                                                      Yes but limited to 24 VDC.

                                                      What is the altitude derating for a TeSys D-Line contactor?

                                                      Issue:​
                                                      What is the altitude derating for a TeSys D-Line contactor?

                                                      Product Line:
                                                      Digest 177 Section 18 : Contactors and Starters, IEC

                                                      Environment:
                                                      North American Products

                                                      Resolution:
                                                      The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                      Voltage
                                                      3500m x 0.90
                                                      4000m x 0.80
                                                      4500m x 0.70
                                                      5000m x 0.60

                                                      Current
                                                      3500m x 0.92
                                                      4000m x 0.90
                                                      4500m x 0.88
                                                      5000m x 0.86

                                                      For example, an LC1D80 at 5000 meters:
                                                      - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                      - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                       

                                                      What is the coil consumption or burden for the Tesys LC*D** contactors?

                                                      * 1 or 2
                                                      ** 09 through 38

                                                      Issue:
                                                      Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

                                                      Product Line: 
                                                      Contactors and Starters - IEC

                                                      Environment:
                                                      North American Products

                                                      Resolution:
                                                      All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

                                                      What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                      Issue:
                                                      Identifying maximum voltage of an LC1D contactor

                                                      Product Line:
                                                      TeSys D Contactors

                                                      Environment:
                                                      IEC contactors and starters used in North America

                                                      Cause:
                                                      n/a

                                                      Resolution:
                                                      IThe maximum voltage per UL and CSA is 600VAC. 
                                                       

                                                      What is the AC3 rating of the LC1D18***

                                                       The rating is 18A

                                                      Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                      Issue:
                                                      Mounting adaptor for GV2 and LC1D contactor

                                                      Product Line:
                                                      Motor Starters and Protectors

                                                      Environment:
                                                      TeSys GV Manual Starter and Protectors
                                                      Tesys D Contactors
                                                       
                                                      Resolution:
                                                      The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                      Prewiring for LC2D reversing contactors

                                                      Issue:
                                                      Are LC2D 3 pole contactors prewired for reversing applications?

                                                      Product Line:
                                                      LC2D contactors

                                                      Environment:
                                                      US product

                                                      Cause:
                                                      Customers need to know whther additional components are necessary with these contactors

                                                      Resolution:
                                                      The 3 pole LC2D contactors are prewired for reversing applications on line and load side.

                                                       

                                                      Can a side mounted auxiliary be fitted to LC1D18BD?

                                                      No a side mounted auxiliary cannot be fitted to LC1D18BD.

                                                       

                                                      Are 600 volt replacement control coils available for LC2D1211?

                                                      Issue:
                                                      Looking for an LC2D1211 replacement control coils.

                                                      Product Line:
                                                      Tesys D Contactors

                                                      Environment:
                                                      LC2D1211

                                                      Resolution:
                                                      This coil is obsolete. Replace the contactor with the new TeSys product, LC2D12X7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.
                                                       

                                                      What is the part number for an 12-18amp overload to go with the LC1D18U7?

                                                      The part number for an 12-18amp overload suitable for use with contactors LC1D18...38  is  LRD21.

                                                      For further information , visit link below:-

                                                      https://www.se.com/au/en/search/LRD21

                                                       

                                                      What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                                      Issue:
                                                      Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                                      Product Line:
                                                      Contactors and Starters IEC

                                                      Environment:
                                                      Tesys D contactors and GV manual starters

                                                      Cause:
                                                      Spacer required

                                                      Resolution:
                                                      Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                                                      What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

                                                      Issue:
                                                      LC*D09-38 coil consumption

                                                      Product Line:
                                                      Contactors and Overload Relays

                                                      Environment:
                                                      TeSys™ D Contactors and Overload Relays

                                                      Resolution:
                                                      The standard DC coil is 5.4 watts of consumption.

                                                      What is the color scheme of the Tesys D-Line contactors?

                                                      Issue:
                                                      Looking for different color scheme of the Tesys D-Line contactors.

                                                      Product Line:
                                                      Tesys D Contactors

                                                      Environment:
                                                      LC1D contactors

                                                      Resolution:
                                                      Beige and dark gray.
                                                       

                                                      Are the D-Line contactors rated to break DC voltages?

                                                      Issue: 
                                                      Can the TeSys D line be used to control DC loads? 

                                                      Product Line:
                                                      Tesys D contactors

                                                      Environment:
                                                      Products sold and used in the United States
                                                       
                                                      Cause:
                                                       DC power circuit
                                                       
                                                      Resolution:
                                                       
                                                      Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                      Devices are suitable but not UL Listed for DC applications.

                                                      More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                       

                                                      What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                      Issue:
                                                      Tesys D SCCR

                                                      Product Line:
                                                      Contactors and Overload Relays

                                                      Environment:
                                                      TeSys™ D Contactors and Overload Relays
                                                       
                                                      Resolution:
                                                      The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                      They are as follows:
                                                      Horsepower SCCR (A)

                                                      0 thru 1 1,000
                                                      1 thru 50 5,000
                                                      51 thru 200 10,000
                                                      201 thru 400 18,000
                                                      401 thru 600 30,000
                                                      601 thru 900 42,000
                                                      901 thru 1600 85,000
                                                      1601+ 100,000

                                                      What is the Tesys D-Line maximum frequency for Power Poles?

                                                      Issue:
                                                      Checking on the maximum Hz voltage that can be applied to the Tesys D-line contactors.

                                                      Product Line:
                                                      Tesys D Contactors

                                                      Environment:
                                                      IEC Contactors and Starters

                                                      Cause:
                                                      Product Characteristics

                                                      Resolution:
                                                      These units have been tested for frequencies 25Hz to 400hz within the operational current of the device .  No testing has been done beyond this frequency.

                                                      What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

                                                      Issue:
                                                      What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

                                                      Product Line:
                                                      IEC Contactors

                                                      Environment:
                                                      Ordering

                                                      Cause:
                                                      Selection

                                                      Resolution:
                                                      The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                                                      AC Volts ___Code     AC Volts ___Code
                                                      12 ___ J7                   208 ___ LE7
                                                      21 ___ Z7                   220 ___ M7
                                                      24 ___ B7                  230 ___ P7
                                                      32 ___ C7                  240 ___ U7
                                                      36 ___ CC7               277 ___ W7
                                                      42 ___ D7                  380 ___ Q7
                                                      48 ___ E7                   400 ___ V7
                                                      60 ___ EE7                415 ___ N7
                                                      100 ___ K7                440 ___ R7
                                                      110 ___ F7                480 ___ T7
                                                      115 ___ FE7              575 ___ SC7
                                                      120 ___ G7                600 ___ X7
                                                      127 ___ FC7              690 ___ Y7
                                                      200 ___ L7                
                                                                     
                                                      Standard Coil                Low Consumption
                                                      DC Volts ___Code          DC Volts ___Code
                                                      12 ___ JD                           5 ___ AL
                                                      24 ___ BD                         12 ___ JL
                                                      36 ___ CD                         20 ___ ZL
                                                      48 ___ ED                         24 ___ BL
                                                      60 ___ ND                         48 ___ EL
                                                      72 ___ SD                         72 ___ SL
                                                      110 ___ FD                       96 ___ DL
                                                      125 ___ GD                     110 ___ FL
                                                      220 ___ MD                    220 ___ ML
                                                      250 ___ UD                     250 ___ UL
                                                      440 ___ RD