TeSys d 4-pole contactor 80A, EverLink, control connection by screw clamp terminals

Contactor

Catalogue Number: LC1DT80AS7
TeSys d 4-pole contactor 80A, EverLink, control connection by screw clamp terminals
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
4 NO
[Ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current
      80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      AC at 50/60 Hz
      [Uc] control circuit voltage
      500 V AC 50/60 Hz
      Auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
    • 10 A (at 60 °C) for signalling circuit
    • 80 A (at 60 °C) for power circuit
      • Irms rated making capacity
      • 140 A AC for signalling circuit conforming to IEC 60947-5-1
      • 250 A DC for signalling circuit conforming to IEC 60947-5-1
      • 1000 A at 440 V for power circuit conforming to IEC 60947
        • Rated breaking capacity
          1000 A at 440 V for power circuit conforming to IEC 60947
          [Icw] rated short-time withstand current
        • 520 A 40 °C - 10 s for power circuit
        • 900 A 40 °C - 1 s for power circuit
        • 110 A 40 °C - 10 min for power circuit
        • 260 A 40 °C - 1 min for power circuit
        • 100 A - 1 s for signalling circuit
        • 120 A - 500 ms for signalling circuit
        • 140 A - 100 ms for signalling circuit
          • Associated fuse rating
          • 10 A gG for signalling circuit conforming to IEC 60947-5-1
          • 125 A gG at <= 690 V coordination type 1 for power circuit
          • 125 A gG at <= 690 V coordination type 2 for power circuit
            • Average impedance
              1.6 mOhm - Ith 80 A 50 Hz for power circuit
              [Ui] rated insulation voltage
            • power circuit: 600 V CSA certified
            • power circuit: 600 V UL certified
            • signalling circuit: 690 V conforming to IEC 60947-1
            • signalling circuit: 600 V CSA certified
            • signalling circuit: 600 V UL certified
            • power circuit: 690 V conforming to IEC 60947-4-1
              • Electrical durability
                1.4 Mcycles 80 A AC-1 at Ue <= 440 V
                Power dissipation per pole
                10.2 W AC-1
                Protective cover
                with
                Mounting support
              • rail
              • plate
                • Standards
                • CSA C22.2 No 14
                • EN 60947-4-1
                • EN 60947-5-1
                • IEC 60947-4-1
                • IEC 60947-5-1
                • UL 508
                  • Product certifications
                  • UL
                  • LROS (Lloyds register of shipping)
                  • CCC
                  • RINA
                  • BV
                  • GL
                  • CSA
                  • GOST
                  • DNV
                    • Connections - terminals
                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end
                      • Tightening torque
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                      • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
                      • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
                        • Operating time
                        • 4...19 ms opening
                        • 12...26 ms closing
                          • Safety reliability level
                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                            • Mechanical durability
                              6 Mcycles
                              Maximum operating rate
                              3600 cyc/h 60 °C
                              Coil technology
                              without built-in suppressor module
                              Control circuit voltage limits
                            • drop-out: 0.3...0.6 Uc AC 50/60 Hz (at 60 °C)
                            • operational: 0.8...1.1 Uc AC 50 Hz (at 60 °C)
                            • operational: 0.85...1.1 Uc AC 60 Hz (at 60 °C)
                              • Inrush power in VA
                              • 140-140 VA 60 Hz cos phi 0.75 (at 20 °C)
                              • 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
                                • Hold-in power consumption in VA
                                • 13-13 VA 60 Hz cos phi 0.3 (at 20 °C)
                                • 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
                                  • Heat dissipation
                                    4-5 W at 50/60 Hz
                                    Auxiliary contacts type
                                  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                  • type mirror contact 1 NC conforming to IEC 60947-4-1
                                    • Signalling circuit frequency
                                      25...400 Hz
                                      Minimum switching current
                                      5 mA for signalling circuit
                                      Minimum switching voltage
                                      17 V for signalling circuit
                                      Non-overlap time
                                    • 1.5 ms on de-energisation between NC and NO contact
                                    • 1.5 ms on energisation between NC and NO contact
                                      • Insulation resistance
                                        > 10 MOhm for signalling circuit
                                        Contact compatibility
                                        M6
                                        Compatibility code
                                        LC1D
                                        IP degree of protection
                                        IP20 front face conforming to IEC 60529
                                        Protective treatment
                                        TH conforming to IEC 60068-2-30
                                        Pollution degree
                                        3
                                        Ambient air temperature for operation
                                        -5-60 °C
                                        Ambient air temperature for storage
                                        -60-80 °C
                                        Permissible ambient air temperature around the device
                                        -40-70 °C at Uc
                                        Operating altitude
                                        3000 m without
                                        Fire resistance
                                        850 °C conforming to IEC 60695-2-1
                                        Flame retardance
                                        V1 conforming to UL 94
                                        Mechanical robustness
                                      • vibrations contactor open: 2 Gn, 5...300 Hz
                                      • vibrations contactor closed: 4 Gn, 5...300 Hz
                                      • shocks contactor closed: 15 Gn for 11 ms
                                      • shocks contactor open: 10 Gn for 11 ms
                                        • Height
                                          122 mm
                                          Width
                                          70 mm
                                          Depth
                                          120 mm
                                          Net weight
                                          1.15 kg
                                          Sustainable offer status
                                          Green Premium product
                                          REACh Regulation
                                          Free of Substances of Very High Concern above the threshold
                                          REACh free of SVHC
                                          Yes
                                          EU RoHS Directive
                                          Compliant
                                          Toxic heavy metal free
                                          Yes
                                          Mercury free
                                          Yes
                                          RoHS exemption information
                                          Yes
                                          China RoHS Regulation
                                          X
                                          Environmental Disclosure
                                          ENVPEP110205EN
                                          WEEE
                                          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                          California proposition 65
                                          WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                          Warranty
                                          18 months

                                          Documents & downloads

                                          hide show
                                          Filter items
                                          • All

                                          • CAD Files and Packs

                                          • Product Brochures

                                          • Product Environmental

                                          • Installation Instruction

                                          • Data Bulletin

                                          • Certificates (MSDS)

                                          • Declaration of Conformity

                                          Frequently Asked Questions

                                          hide show

                                          What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                          Issue:
                                          Identifying replacement coils for tesys D non-reversing and reversing conactors

                                          Product Line:
                                          IEC Contactors and Starters

                                          Environment:
                                          Products sold and used in the United States

                                          Cause:
                                          Replacement coil is needed

                                          Resolution:
                                          DC replacement coils are not available.
                                          AC Coils are 50/60 hertz for voltages as listed below:

                                          Volts - Part Number
                                          12 ____ LXD1J7
                                          21 ____ LXD1Z7
                                          24 ____ LXD1B7
                                          32 ____ LXD1C7
                                          36 ____ LXD1CC7
                                          42 ____ LXD1D7
                                          48 ____ LXD1E7
                                          60 ____ LXD1EE7
                                          100 ___ LXD1K7 ( never brought to North America )
                                          110 ___ LXD1F7
                                          115 ___ LXD1FE7
                                          120 ___ LXD1G7
                                          127 ___ LXD1FC7
                                          200 ___ LXD1L7
                                          208 ___ LXD1LE7
                                          220 ___ LXD1M7
                                          230 ___ LXD1P7
                                          240 ___ LXD1U7
                                          277 ___ LXD1W7
                                          380 ___ LXD1Q7
                                          400 ___ LXD1V7
                                          415 ___ LXD1N7
                                          440 ___ LXD1R7
                                          480 ___ LXD1T7
                                          575 ___ LXD1SC7
                                          600 ___ LXD1X7
                                          690 ___ LXD1Y7


                                          Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                          What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                          Issue:
                                          Identifying maximum power voltage of an LC1D contactor

                                          Product Line:
                                          Digest 177 Section 18: IEC Contactors

                                          Environment:
                                          Products sold and used in the United States

                                          Cause:
                                          Identifying ratings per UL and CSA

                                          Resolution:
                                          It is 600Vac.


                                           

                                          What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                          Issue:
                                          Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                          Product Line:
                                          NEMA combination starters

                                          Environment:
                                          Products sold and used in the United States

                                          Resolution:
                                          For contactors with screw clamp terminals:
                                          stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                          stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                          solid cable: One or Two #18-8 AWG per terminal.

                                          What is the replacement contactor for the LC1D65004F5?

                                          The new code is LC1DT80AF7 which is made to order.

                                          What is the altitude derating for a TeSys D-Line contactor?

                                          Issue:​
                                          What is the altitude derating for a TeSys D-Line contactor?

                                          Product Line:
                                          Digest 177 Section 18 : Contactors and Starters, IEC

                                          Environment:
                                          North American Products

                                          Resolution:
                                          The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                          Voltage
                                          3500m x 0.90
                                          4000m x 0.80
                                          4500m x 0.70
                                          5000m x 0.60

                                          Current
                                          3500m x 0.92
                                          4000m x 0.90
                                          4500m x 0.88
                                          5000m x 0.86

                                          For example, an LC1D80 at 5000 meters:
                                          - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                          - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                           

                                          Looking for a LC1D50A.. with a 240v coil

                                           Part code is LC1D50AU7

                                          What does the T indicate in the LC1DT contactor catalog number?

                                          Issue:
                                          LC1D with T suffix

                                          Product Line:
                                           Tesys D line Contactors

                                          Environment:
                                          North American Products

                                          Resolution:
                                           The T indicates that the device is a 4 pole, all normally open, and has resisitive contact (AC-1) ratings.

                                          How Can the LC1D50AU7 Contactor be mounted?

                                          Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                                          See the attached datasheet for further information.

                                          What is the code for a 40A 110VAC contactor ?

                                          LC1D40AF7

                                          What is difference between LC1D50U7 and LC1D50AU7?

                                          Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                          LC1D50AU7 has everlink terminals.
                                          LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                          Whereas
                                          LC1D50U7 contactors accommodate LRD33XX overloads.

                                           

                                          What is the Overload for LC1D50AU7 range is 37..50 Amps?

                                          LRD350

                                          Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                          No, correct kit is a LAD9R3.

                                          What replaces LC1D1801U5

                                           Part code LC1D18U7

                                          What is the difference between the LC1D1506N7 and the LC1D150N7?

                                          The LC1D1506N7 can accept 5X25mm Bars aswell as Lugs or ring terminals. The LC1D150N7 only accepts cable lugs upto 120mm2.

                                          What is the code for the newer version of the LC1D40U7

                                          That has been replaced with the Everlink LC1D40AU7

                                          What is the part code for a 4P AC-1 rated 20Amp 24V ac coil contactor

                                           The part code is LC1DT20B7

                                          What are the dimensions of LC1D40AB7 ?

                                          Height 122 mm
                                          Width 55 mm
                                          Depth 120 mm
                                          Product weight 1.4 kg

                                          What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                                          The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                                          What is the 230V Coil for the Everlink Contactor LC1DT60A ?

                                          240V coil =  LXD3U7

                                          What mechanical interlock should I use with the LC1D50A••?

                                          The mechanical interlock LAD4CM is the correct one for use with the LC1D50A••.

                                          See attached datasheet for futher information on the LAD4CM.

                                          Is there a contactor 80A 3p which will operate on 42V AC

                                           There is - part code LC1D80E7

                                          What is the part number for an overload for LC1D80U7 contactor , with 37-50amp range?

                                          The part number for an overload for LC1D80U7 contactor , with 37-50amp range is - LRD3357

                                          For further information , visit link below:-
                                          https://www.schneider-electric.com.au/en/search/LRD3357
                                           

                                          What replaces LC1D50BD

                                          Replacement LC1D50ABD

                                          What is the part number for 4 pole, 415V Coil contactor and 3A overload?

                                          The part number for 4 pole, 415V Coil contactor and 3A overload is LC1DT20N7 and LRD08



                                          For more information on either item refer to:
                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1DT20N7
                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD08

                                          What are the part numbers of contactors in LE3AC075N7*

                                          Part no LE3AC075N7 consists  Two  of LC1D80U7 and one of LC1D50U7 contactors.

                                          What does the (3) designate in the part number LC1D123G7?

                                          For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                                          CTA-ID : 2053127

                                          What is the part number for a 30kw 4 pole 24vac contactor?

                                          What is the part number for a 30kw 4 pole 24vac contactor the part number is LC1DT80AB7
                                          Please go to following link for more infomation https://www.schneider-electric.com.au/en/search/LC1DT80AB7

                                          What is the 240V coil needed for a LC1D80008 contactor

                                           The coil is a LX1D6U7

                                          What is the part number for 4 pole contactor , reversing for 5.5KW , 40A Single phase motor?

                                          The part number for 4 pole contactor , reversing for 5.5KW , 40A Single phase motor are LC1DT60A X 2 + LAD4CM
                                              LAD4CM

                                          LC1DT60AU7                                                                                                                                                                        D40A to D65A Mechanical Interlock
                                          TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 60 A - 240 V AC 50/60 Hz coil

                                          For further information see:
                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1DT60AU7
                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD4CM

                                           

                                          Does LC1D65AB7 3P (3 NO) TeSys Model D contactor have a normally opened and normally closed auxiliary contact?

                                          What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                                          17-25 Amps = LRD325
                                          23-32 Amps =LRD332

                                          Are contactors LC1D38.. and LC1D40A.. the same size?

                                          No the two contactor are not the same size, LC1D40A.. is bigger.

                                          LC1D38N7
                                          TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 38 A - 415 V AC 50/60 Hz coil     LC1D40AN7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 415 V AC 50/60 Hz coil

                                          For more information see:
                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D38N7;
                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D40AN7




                                           

                                          What is the part number for the red safety cover to go on the LC1D contactors?

                                          The LC1D09-65 take the LAD9ET1S
                                          The LC1D80-95 take the LAD9ET3S 
                                          The LC1D115-150 take the LAD9ET4S

                                          Can the D range AC contactor be mounted on the ceiling ?

                                          The AC contactor mounted horizontally as follows - Not recommended practice

                                          For contactors with AC coil, when the contactor is mounted in horizontal position, the speed for making and breaking is impacted :
                                          Floor mounted : the opening is slower.
                                          Ceiling mounted : the closing is slower.
                                          Then when mounted in horizontal position, the following recommendations shall apply :
                                          Use on fix machines only (no vertical shocks allowed),
                                          Additives forbidden,
                                          Electrical durability not guaranteed (derating probably in the order of 0,70 but no existing confirmation tests)
                                          AC1 current derated at 80% of the catalogue values,
                                           
                                          Inrush voltage for contactors mounted on the floor:
                                          CAD/LC1D09/12/18          89%
                                          LC1D25/32/38                    84%
                                          LC1D40/50/65                    86%
                                          LC1D80/95                          84%
                                           Drop-out voltage for contactors mounted on the floor:
                                          CAD/LC1D09/12/18          96%
                                          LC1D25/32/38                    94%
                                          LC1D40/50/65                    97%
                                          LC1D80/95                          94%

                                          Inrush voltage for contactors mounted on the ceiling:
                                           CAD/LC1D09/12/18         114%
                                          LC1D25/32/38                    114%
                                          LC1D40/50/65                    111%
                                          LC1D80/95                          111%
                                          Drop-out voltage for contactors mounted on the ceiling:
                                          CAD/LC1D09/12/18          108%
                                          LC1D25/32/38                    106%
                                          LC1D40/50/65                    107%
                                          LC1D80/95                          105%
                                           
                                          For example, for LC1D32* fitted:
                                          in normal position, the drop out control voltage limits is 0,3 to 0,6 Uc,
                                          on floor position, the drop out control voltage limits is 0,28 to 0,56 Uc (0,3x0,94 and 0,6x0,94).

                                          Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

                                          ISSUE
                                          Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?
                                          PRODUCT LINE
                                          Auxiliary contacts for the Tesys D line
                                          ENVIRONMENT
                                          Tesys D-Line and Tesys F
                                          CAUSE
                                          Fit
                                          RESOLUTION
                                          These contacts will only fit on the following contactors:
                                          Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
                                          Left side mount only to LC1F contactors
                                          CTA-ID : 2002751

                                          Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                          Issue:
                                          Can new accessories be used on older style contactors

                                          Product Line:
                                          IEC contactors and starters

                                          Environment:
                                          Products sold and used in the United States

                                          Cause:
                                          Identifying product compatibility

                                          Resolution:
                                          Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                           

                                          What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                          Issue:
                                          Identifying power terminal lug data for the D2 style contactors

                                          Product Line:
                                          Tesys D line contactors

                                          Environment:
                                          Products sold and used in the United States

                                          Cause:
                                          Power terminal lug data required

                                          Resolution:
                                          For contactors with screw clamp terminals:
                                          stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                          stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                          solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                          What is the part number for 60A contactor with 240V/415V coil?

                                          What is the difference between a LC1D65A3U7 and LC1D65AU7?

                                          The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                                          see data sheets for comparrisons...
                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                                          User-added image.................User-added image

                                          Are the D-Line contactors rated to break DC voltages?

                                          Issue: 
                                          Can the TeSys D line be used to control DC loads? 

                                          Product Line:
                                          Tesys D contactors

                                          Environment:
                                          Products sold and used in the United States
                                           
                                          Cause:
                                           DC power circuit
                                           
                                          Resolution:
                                           
                                          Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                          Devices are suitable but not UL Listed for DC applications.

                                          More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                           

                                          What are the stand alone short circuit current ratings on the LC1D** contactors?

                                          Issue:
                                          Tesys D SCCR

                                          Product Line:
                                          Contactors and Overload Relays

                                          Environment:
                                          TeSys™ D Contactors and Overload Relays
                                           
                                          Resolution:
                                          The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                          They are as follows:
                                          Horsepower SCCR (A)

                                          0 thru 1 1,000
                                          1 thru 50 5,000
                                          51 thru 200 10,000
                                          201 thru 400 18,000
                                          401 thru 600 30,000
                                          601 thru 900 42,000
                                          901 thru 1600 85,000
                                          1601+ 100,000

                                          Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                          Issue:
                                          Auxiliary contact modules for the LC1D and LC2D contactors

                                          Product Line: 
                                          Contactor and Starters - IEC

                                          Environment:
                                          North American Products

                                          Resolution:
                                          Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                          Front Mounting; maximum of 1 block per contactor:

                                          N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                          --1-----------1---------LADN11-----------LA1DN11
                                          --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                          --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                          --2-----------0---------LADN20-----------LA1DN20
                                          --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                          --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                          --0-----------2---------LADN02-----------LA1DN02
                                          --2-----------2---------LADN22-----------LA1DN22
                                          --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                          --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                          --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                          --3-----------1---------LADN31------------LA1DN31
                                          --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                          --1-----------3---------LADN13------------LA1DN13
                                          --4-----------0---------LADN40------------LA1DN40
                                          --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                          --0-----------4---------LADN04------------LA1DN04




                                          Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                          N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                          --1-----------0--------LADN10----------LA1DN10
                                          --0-----------1--------LADN01----------LA1DN01

                                          Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                          (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                          N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                          --1-----------1--------LAD8N11----------LA8DN11
                                          --2-----------0--------LAD8N20----------LA8DN20
                                          --0-----------2--------LAD8N02----------N/A

                                          Footnotes:
                                          {1} EN50 012 Machine Tool Terminal Markings
                                          {2} (2) NO Sealed Dust Tight Contacts
                                          {3} Gold Flash Contacts
                                          {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                          {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                          {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                          What is the coil consumption or burden for the Tesys LC*D** contactors?

                                          * 1 or 2
                                          ** 09 through 38

                                          Issue:
                                          Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

                                          Product Line: 
                                          Contactors and Starters - IEC

                                          Environment:
                                          North American Products

                                          Resolution:
                                          All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

                                          What is the heat dissipated by the LC1D09 contactor?

                                          Issue:
                                          Contactors dissipate heat

                                          Product Line:
                                          Tesys D Contactors

                                          Environment:
                                          IEC Contactors and Starters

                                          Resolution:
                                          Total heat dissipation is 3.60 watts maximum; .20 watts dissipated across each power pole and 2 to 3 watts dissipated by the AC control coil.