MASTER YOUR CASTLE with your new build or reno project
Enter competition
TeSys d 4-pole contactor 80A, EverLink, control connection by screw clamp terminals

LC1DT80AD7

Contactor

TeSys d 4-pole contactor 80A, EverLink, control connection by screw clamp terminals
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
4 NO
[Ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current
      80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      AC at 50/60 Hz
      [Uc] control circuit voltage
      42 V AC 50/60 Hz
      Auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
    • 10 A (at 60 °C) for signalling circuit
    • 80 A (at 60 °C) for power circuit
      • Irms rated making capacity
      • 140 A AC for signalling circuit conforming to IEC 60947-5-1
      • 250 A DC for signalling circuit conforming to IEC 60947-5-1
      • 1000 A at 440 V for power circuit conforming to IEC 60947
        • Rated breaking capacity
          1000 A at 440 V for power circuit conforming to IEC 60947
          [Icw] rated short-time withstand current
        • 520 A 40 °C - 10 s for power circuit
        • 900 A 40 °C - 1 s for power circuit
        • 110 A 40 °C - 10 min for power circuit
        • 260 A 40 °C - 1 min for power circuit
        • 100 A - 1 s for signalling circuit
        • 120 A - 500 ms for signalling circuit
        • 140 A - 100 ms for signalling circuit
          • Associated fuse rating
          • 10 A gG for signalling circuit conforming to IEC 60947-5-1
          • 125 A gG at <= 690 V coordination type 1 for power circuit
          • 125 A gG at <= 690 V coordination type 2 for power circuit
            • Average impedance
              1.6 mOhm - Ith 80 A 50 Hz for power circuit
              [Ui] rated insulation voltage
            • power circuit: 600 V CSA certified
            • power circuit: 600 V UL certified
            • signalling circuit: 690 V conforming to IEC 60947-1
            • signalling circuit: 600 V CSA certified
            • signalling circuit: 600 V UL certified
            • power circuit: 690 V conforming to IEC 60947-4-1
              • Electrical durability
                1.4 Mcycles 80 A AC-1 at Ue <= 440 V
                Power dissipation per pole
                10.2 W AC-1
                Protective cover
                with
                Mounting support
              • rail
              • plate
                • Standards
                • CSA C22.2 No 14
                • EN 60947-4-1
                • EN 60947-5-1
                • IEC 60947-4-1
                • IEC 60947-5-1
                • UL 508
                  • Product certifications
                  • LROS (Lloyds register of shipping)
                  • DNV
                  • UL
                  • GOST
                  • BV
                  • CCC
                  • CSA
                  • RINA
                  • GL
                    • Connections - terminals
                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                    • power circuit: screw connection 2 cable(s) 1-25 mm²flexible with cable end
                    • power circuit: screw connection 1 cable(s) 1-35 mm²solid without cable end
                    • power circuit: screw connection 2 cable(s) 1-25 mm²solid without cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                    • power circuit: screw connection 1 cable(s) 1-35 mm²flexible without cable end
                    • power circuit: screw connection 2 cable(s) 1-25 mm²flexible without cable end
                    • power circuit: screw connection 1 cable(s) 1-35 mm²flexible with cable end
                      • Tightening torque
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                      • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
                      • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
                        • Operating time
                        • 4...19 ms opening
                        • 12...26 ms closing
                          • Safety reliability level
                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                            • Mechanical durability
                              6 Mcycles
                              Maximum operating rate
                              3600 cyc/h 60 °C
                              Coil technology
                              without built-in suppressor module
                              Control circuit voltage limits
                            • drop-out: 0.3...0.6 Uc AC 50/60 Hz (at 60 °C)
                            • operational: 0.8...1.1 Uc AC 50 Hz (at 60 °C)
                            • operational: 0.85...1.1 Uc AC 60 Hz (at 60 °C)
                              • Inrush power in VA
                              • 140-140 VA 60 Hz cos phi 0.75 (at 20 °C)
                              • 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
                                • Hold-in power consumption in VA
                                • 13-13 VA 60 Hz cos phi 0.3 (at 20 °C)
                                • 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
                                  • Heat dissipation
                                    4-5 W at 50/60 Hz
                                    Auxiliary contacts type
                                  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                  • type mirror contact 1 NC conforming to IEC 60947-4-1
                                    • Signalling circuit frequency
                                      25...400 Hz
                                      Minimum switching current
                                      5 mA for signalling circuit
                                      Minimum switching voltage
                                      17 V for signalling circuit
                                      Non-overlap time
                                    • 1.5 ms on de-energisation between NC and NO contact
                                    • 1.5 ms on energisation between NC and NO contact
                                      • Insulation resistance
                                        > 10 MOhm for signalling circuit
                                        Contact compatibility
                                        M6
                                        Compatibility code
                                        LC1D
                                        IP degree of protection
                                        IP20 front face conforming to IEC 60529
                                        Protective treatment
                                        TH conforming to IEC 60068-2-30
                                        Pollution degree
                                        3
                                        Ambient air temperature for operation
                                        -5-60 °C
                                        Ambient air temperature for storage
                                        -60-80 °C
                                        Permissible ambient air temperature around the device
                                        -40-70 °C at Uc
                                        Operating altitude
                                        3000 m without
                                        Fire resistance
                                        850 °C conforming to IEC 60695-2-1
                                        Flame retardance
                                        V1 conforming to UL 94
                                        Mechanical robustness
                                      • vibrations contactor open: 2 Gn, 5...300 Hz
                                      • vibrations contactor closed: 4 Gn, 5...300 Hz
                                      • shocks contactor closed: 15 Gn for 11 ms
                                      • shocks contactor open: 10 Gn for 11 ms
                                        • Height
                                          122 mm
                                          Width
                                          70 mm
                                          Depth
                                          120 mm
                                          Net weight
                                          1.15 kg
                                          Sustainable offer status
                                          Green Premium product
                                          REACh Regulation
                                          Reference contains Substances of Very High Concern above the threshold
                                          EU RoHS Directive
                                          Pro-active compliance (Product out of EU RoHS legal scope)
                                          Toxic heavy metal free
                                          Yes
                                          Mercury free
                                          Yes
                                          RoHS exemption information
                                          Yes
                                          China RoHS Regulation
                                          X
                                          Environmental Disclosure
                                          ENVPEP110205EN
                                          Circularity Profile
                                          N/A
                                          WEEE
                                          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                          CALIFORNIA PROPOSITION 65
                                          WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.p65warnings.ca.gov
                                          Warranty
                                          18 months

                                          Documents & downloads

                                          hide show
                                          Filter items
                                          • All

                                          • CAD Files and Packs

                                          • Product Brochures

                                          • Movies

                                          • Technical Data Catalogues

                                          • Catalog Page

                                          • Technical Leaflet

                                          • Data Bulletin

                                          • Product Environmental

                                          • Installation Instruction

                                          • End of Life Manual

                                          • Handout

                                          • Operating Manuals

                                          • Application Solutions

                                          • Certificates (MSDS)

                                          • Declaration of Conformity

                                          • White Paper

                                          • eTechPub

                                          • Marine Certificate

                                          • Software - Released