Quantcast

Contactor

Contactor

Contactor

Item Number: LC1DT60ASD

Retail
$2,309.38
RRP (Inc. GST)

Product Dimensions

Width icon

Width70 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

      60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

      Electrical durability

      0.7 Mcycles 60 A AC-1 at Ue <= 440 V

      Mounting support

    • plate
    • rail
      • Standards

      • CSA C22.2 No 14
      • EN 60947-4-1
      • EN 60947-5-1
      • IEC 60947-4-1
      • IEC 60947-5-1
      • UL 508
        • Product certifications

        • CCC
        • CSA
        • BV
        • UL
        • RINA
        • GL
        • GOST
        • LROS (Lloyds register of shipping)
        • DNV
          • Connections - terminals

          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
          • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
          • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
          • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
          • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
          • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end
          • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end
            • Mechanical durability

              10 Mcycles

              Insulation resistance

              > 10 MOhm for signalling circuit

              IP degree of protection

              IP20 front face conforming to IEC 60529

              Ambient air temperature for operation

            • -40-60 °C
            • 60-70 °C with derating
              • Ambient air temperature for storage

                -60-80 °C

                Height

                122 mm

                Width

                70 mm

                Depth

                120 mm

                Net weight

                1.165 kg

                REACh free of SVHC

                Yes

                EU RoHS Directive

                Compliant

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                 Pro-active China RoHS declaration (out of China RoHS legal scope)

                Environmental Disclosure

                ENVPEP1503009EN

                Circularity Profile

                ENVEOLI1503009EN

                California proposition 65

                WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

                Others

                Product name

                TeSys D

                Device short name

                LC1D

                Contactor application

                resistive load

                Utilisation category

                AC-1

                Poles description

                4P

                Pole contact composition

                4 NO

                Control circuit type

                DC standard

                [Uc] control circuit voltage

                72 V DC

                Auxiliary contact composition

                1 NO + 1 NC

                [Uimp] rated impulse withstand voltage

                6 kV conforming to IEC 60947

                Overvoltage category

                III

                [Ith] conventional free air thermal current

              • 10 A (at 60 °C) for signalling circuit
              • 60 A (at 60 °C) for power circuit
                • Irms rated making capacity

                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 800 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity

                    800 A at 440 V for power circuit conforming to IEC 60947

                    [Icw] rated short-time withstand current

                  • 320 A 40 °C - 10 s for power circuit
                  • 720 A 40 °C - 1 s for power circuit
                  • 72 A 40 °C - 10 min for power circuit
                  • 165 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating

                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 80 A gG at <= 690 V coordination type 1 for power circuit
                    • 80 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance

                        1.6 mOhm - Ith 60 A 50 Hz for power circuit

                        [Ui] rated insulation voltage

                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                      • power circuit: 690 V conforming to IEC 60947-4-1
                        • Power dissipation per pole

                          5.8 W AC-1

                          Protective cover

                          with

                          Tightening torque

                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                        • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
                        • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
                          • Operating time

                          • 42.5...57.5 ms closing
                          • 16...24 ms opening
                            • Safety reliability level

                            • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                            • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                              • Maximum operating rate

                                3600 cyc/h 60 °C

                                Coil technology

                                built-in bidirectional peak limiting diode suppressor

                                Control circuit voltage limits

                              • 0.1...0.3 Uc (-40-70 °C):drop-out DC
                              • 0.75...1.25 Uc (-40-60 °C):operational DC
                              • 1...1.25 Uc (60-70 °C):operational DC
                                • Time constant

                                  34 ms

                                  Inrush power in W

                                  19-19 W (at 20 °C)

                                  Hold-in power consumption in W

                                  7.4-7.4 W at 20 °C

                                  Auxiliary contacts type

                                • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                • type mirror contact 1 NC conforming to IEC 60947-4-1
                                  • Signalling circuit frequency

                                    25...400 Hz

                                    Minimum switching current

                                    5 mA for signalling circuit

                                    Minimum switching voltage

                                    17 V for signalling circuit

                                    Non-overlap time

                                  • 1.5 ms on de-energisation between NC and NO contact
                                  • 1.5 ms on energisation between NC and NO contact
                                    • Contact compatibility

                                      M7

                                      Compatibility code

                                      LC1D

                                      Protective treatment

                                      TH conforming to IEC 60068-2-30

                                      Pollution degree

                                      3

                                      Operating altitude

                                      0...3000 m

                                      Fire resistance

                                      850 °C conforming to IEC 60695-2-1

                                      Flame retardance

                                      V1 conforming to UL 94

                                      Mechanical robustness

                                    • vibrations contactor open: 2 Gn, 5...300 Hz
                                    • vibrations contactor closed: 4 Gn, 5...300 Hz
                                    • shocks contactor closed: 15 Gn for 11 ms
                                    • shocks contactor open: 10 Gn for 11 ms
                                      • Unit Type of Package 1

                                        PCE

                                        Number of Units in Package 1

                                        1

                                        Package 1 Weight

                                        1.1 kg

                                        Package 1 Height

                                        7.5 cm

                                        Package 1 width

                                        14 cm

                                        Package 1 Length

                                        15 cm

                                        WEEE

                                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                        PVC free

                                        Yes
                                        Show all specifications

                                        Documents & downloads

                                        hide show
                                        Filter items
                                        • All

                                        • Product Brochures

                                        • CAD Files and Packs

                                        • Technical Data Catalogues

                                        • Data Bulletin

                                        • Product Environmental

                                        • End of Life Manual

                                        • Installation Instruction

                                        • Declaration of Conformity

                                        • Certificates (MSDS)