Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
4 NO
[Ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current
      60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      DC standard
      [Uc] control circuit voltage
      12 V DC
      Auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
    • 10 A (at 60 °C) for signalling circuit
    • 60 A (at 60 °C) for power circuit
      • Irms rated making capacity
      • 140 A AC for signalling circuit conforming to IEC 60947-5-1
      • 250 A DC for signalling circuit conforming to IEC 60947-5-1
      • 800 A at 440 V for power circuit conforming to IEC 60947
        • Rated breaking capacity
          800 A at 440 V for power circuit conforming to IEC 60947
          [Icw] rated short-time withstand current
        • 320 A 40 °C - 10 s for power circuit
        • 720 A 40 °C - 1 s for power circuit
        • 72 A 40 °C - 10 min for power circuit
        • 165 A 40 °C - 1 min for power circuit
        • 100 A - 1 s for signalling circuit
        • 120 A - 500 ms for signalling circuit
        • 140 A - 100 ms for signalling circuit
          • Associated fuse rating
          • 10 A gG for signalling circuit conforming to IEC 60947-5-1
          • 80 A gG at <= 690 V coordination type 1 for power circuit
          • 80 A gG at <= 690 V coordination type 2 for power circuit
            • Average impedance
              1.6 mOhm - Ith 60 A 50 Hz for power circuit
              [Ui] rated insulation voltage
            • power circuit: 600 V CSA certified
            • power circuit: 600 V UL certified
            • signalling circuit: 690 V conforming to IEC 60947-1
            • signalling circuit: 600 V CSA certified
            • signalling circuit: 600 V UL certified
            • power circuit: 690 V conforming to IEC 60947-4-1
              • Electrical durability
                0.7 Mcycles 60 A AC-1 at Ue <= 440 V
                Power dissipation per pole
                5.8 W AC-1
                Protective cover
                with
                Mounting support
              • rail
              • plate
                • Standards
                • CSA C22.2 No 14
                • EN 60947-4-1
                • EN 60947-5-1
                • IEC 60947-4-1
                • IEC 60947-5-1
                • UL 508
                  • Product certifications
                  • UL
                  • GOST
                  • LROS (Lloyds register of shipping)
                  • DNV
                  • CCC
                  • GL
                  • CSA
                  • BV
                  • RINA
                    • Connections - terminals
                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end
                      • Tightening torque
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                      • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
                      • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
                        • Operating time
                        • 42.5...57.5 ms closing
                        • 16...24 ms opening
                          • Safety reliability level
                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                            • Mechanical durability
                              10 Mcycles
                              Maximum operating rate
                              3600 cyc/h 60 °C
                              Coil technology
                              built-in bidirectional peak limiting diode suppressor
                              Control circuit voltage limits
                            • drop-out: 0.1...0.3 Uc DC (at 60 °C)
                            • operational: 0.75...1.25 Uc DC (at 60 °C)
                              • Time constant
                                34 ms
                                Inrush power in W
                                19-19 W (at 20 °C)
                                Hold-in power consumption in W
                                7.4-7.4 W at 20 °C
                                Auxiliary contacts type
                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                • Signalling circuit frequency
                                  25...400 Hz
                                  Minimum switching current
                                  5 mA for signalling circuit
                                  Minimum switching voltage
                                  17 V for signalling circuit
                                  Non-overlap time
                                • 1.5 ms on de-energisation between NC and NO contact
                                • 1.5 ms on energisation between NC and NO contact
                                  • Insulation resistance
                                    > 10 MOhm for signalling circuit
                                    Contact compatibility
                                    M7
                                    Compatibility code
                                    LC1D
                                    IP degree of protection
                                    IP20 front face conforming to IEC 60529
                                    Protective treatment
                                    TH conforming to IEC 60068-2-30
                                    Pollution degree
                                    3
                                    Ambient air temperature for operation
                                    -5-60 °C
                                    Ambient air temperature for storage
                                    -60-80 °C
                                    Permissible ambient air temperature around the device
                                    -40-70 °C at Uc
                                    Operating altitude
                                    3000 m without
                                    Fire resistance
                                    850 °C conforming to IEC 60695-2-1
                                    Flame retardance
                                    V1 conforming to UL 94
                                    Mechanical robustness
                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                  • shocks contactor closed: 15 Gn for 11 ms
                                  • shocks contactor open: 10 Gn for 11 ms
                                    • Height
                                      122 mm
                                      Width
                                      70 mm
                                      Depth
                                      120 mm
                                      Net weight
                                      1.165 kg
                                      Sustainable offer status
                                      Green Premium product
                                      REACh Regulation
                                      Free of Substances of Very High Concern above the threshold
                                      REACh free of SVHC
                                      Yes
                                      EU RoHS Directive
                                      Compliant
                                      Toxic heavy metal free
                                      Yes
                                      Mercury free
                                      Yes
                                      RoHS exemption information
                                      Yes
                                      China RoHS Regulation
                                      X
                                      Environmental Disclosure
                                      ENVPEP1503009EN
                                      Circularity Profile
                                      ENVEOLI1503009EN
                                      WEEE
                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                      California proposition 65
                                      WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                      Warranty
                                      18 months

                                      Documents & downloads

                                      hide show
                                      Filter items
                                      • All

                                      • CAD Files and Packs

                                      • Product Brochures

                                      • Technical Data Catalogues

                                      • Installation Instruction

                                      • Data Bulletin

                                      • Product Environmental

                                      • End of Life Manual

                                      • Certificates (MSDS)

                                      • Declaration of Conformity

                                      Frequently Asked Questions

                                      hide show

                                      What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                      Issue:
                                      Identifying replacement coils for tesys D non-reversing and reversing conactors

                                      Product Line:
                                      IEC Contactors and Starters

                                      Environment:
                                      Products sold and used in the United States

                                      Cause:
                                      Replacement coil is needed

                                      Resolution:
                                      DC replacement coils are not available.
                                      AC Coils are 50/60 hertz for voltages as listed below:

                                      Volts - Part Number
                                      12 ____ LXD1J7
                                      21 ____ LXD1Z7
                                      24 ____ LXD1B7
                                      32 ____ LXD1C7
                                      36 ____ LXD1CC7
                                      42 ____ LXD1D7
                                      48 ____ LXD1E7
                                      60 ____ LXD1EE7
                                      100 ___ LXD1K7 ( never brought to North America )
                                      110 ___ LXD1F7
                                      115 ___ LXD1FE7
                                      120 ___ LXD1G7
                                      127 ___ LXD1FC7
                                      200 ___ LXD1L7
                                      208 ___ LXD1LE7
                                      220 ___ LXD1M7
                                      230 ___ LXD1P7
                                      240 ___ LXD1U7
                                      277 ___ LXD1W7
                                      380 ___ LXD1Q7
                                      400 ___ LXD1V7
                                      415 ___ LXD1N7
                                      440 ___ LXD1R7
                                      480 ___ LXD1T7
                                      575 ___ LXD1SC7
                                      600 ___ LXD1X7
                                      690 ___ LXD1Y7


                                      Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                      What replaces LC1D50BD

                                      Replacement LC1D50ABD

                                      What does the T indicate in the LC1DT contactor catalog number?

                                      Issue:
                                      LC1DT catalog numbers

                                      Product Line:
                                      Tesys D line Contactors

                                      Environment:
                                      North American Products

                                      Resolution:
                                      The T indicates that the device is a 4 poles with all normally open poles.  4 pole units only have resistive (AC-1) power contact ratings.

                                      What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                      Issue:
                                      Identifying maximum voltage of an LC1D contactor

                                      Product Line:
                                      TeSys D Contactors

                                      Environment:
                                      IEC contactors and starters used in North America

                                      Cause:
                                      n/a

                                      Resolution:
                                      IThe maximum voltage per UL and CSA is 600VAC. 
                                       

                                      What is the mechanical interlock for a 4 Pole contactor LC1DT80A__?

                                      Issue:
                                      Part number for the mechanical interlock for a 4 Pole contactor LC1DT80A__?

                                      Product Line: 
                                       Contactors and Starters - IEC

                                      Environment:
                                      LC1DT80A

                                      Cause:
                                      Needs the mechanical interlock for a 4 Pole contactor LC1DT80A__.

                                      Resolution:
                                      LAD4CM

                                      What is the 230V Coil for the Everlink Contactor LC1DT60A ?

                                      240V coil =  LXD3U7

                                      Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                      Issue:
                                      Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                      Product Line: 
                                      Tesys D Contactors

                                      Environment:
                                      IEC contactors

                                      Resolution:
                                      The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                       

                                      What is the replacement contactor for the LC1D65004F5?

                                      The new code is LC1DT80AF7 which is made to order.

                                      What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                      Issue:
                                      Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                      Product Line:
                                      NEMA combination starters

                                      Environment:
                                      Products sold and used in the United States

                                      Resolution:
                                      For contactors with screw clamp terminals:
                                      stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                      stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                      solid cable: One or Two #18-8 AWG per terminal.

                                      Do the Everlink reversing contactors come with electrical interlocking?

                                      Issue:
                                      Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                      Product line:
                                      Tesys D LC1D40A, LC1D50A, LC1D65A

                                      Environment:
                                      Everlink, all voltage codes

                                      Cause:
                                      Old D2 version offered an electrical interlock kit

                                      Resolution:
                                      The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                      Looking for a LC1D50A.. with a 240v coil

                                       Part code is LC1D50AU7

                                      What is the part number for 4 pole contactor , reversing for 5.5KW , 40A Single phase motor?

                                      The part number for 4 pole contactor , reversing for 5.5KW , 40A Single phase motor are LC1DT60A X 2 + LAD4CM
                                          LAD4CM

                                      LC1DT60AU7                                                                                                                                                                        D40A to D65A Mechanical Interlock
                                      TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 60 A - 240 V AC 50/60 Hz coil

                                      For further information see:
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1DT60AU7
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD4CM

                                       

                                      How Can the LC1D50AU7 Contactor be mounted?

                                      Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                                      See the attached datasheet for further information.

                                      What is the code for a 40A 110VAC contactor ?

                                      LC1D40AF7

                                      What is the Overload for LC1D50AU7 range is 37..50 Amps?

                                      LRD350

                                      Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                      No, correct kit is a LAD9R3.

                                      What is the code for the newer version of the LC1D40U7

                                      That has been replaced with the Everlink LC1D40AU7

                                      What is the part code for a 4P AC-1 rated 20Amp 24V ac coil contactor

                                       The part code is LC1DT20B7

                                      Does LC1D65AB7 3P (3 NO) TeSys Model D contactor have a normally opened and normally closed auxiliary contact?

                                      What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                                      17-25 Amps = LRD325
                                      23-32 Amps =LRD332

                                      What are the dimensions of LC1D40AB7 ?

                                      Height 122 mm
                                      Width 55 mm
                                      Depth 120 mm
                                      Product weight 1.4 kg

                                      What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                                      The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                                      Are contactors LC1D38.. and LC1D40A.. the same size?

                                      No the two contactor are not the same size, LC1D40A.. is bigger.

                                      LC1D38N7
                                      TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 38 A - 415 V AC 50/60 Hz coil     LC1D40AN7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 415 V AC 50/60 Hz coil

                                      For more information see:
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D38N7;
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D40AN7




                                       

                                      What mechanical interlock should I use with the LC1D50A••?

                                      The mechanical interlock LAD4CM is the correct one for use with the LC1D50A••.

                                      See attached datasheet for futher information on the LAD4CM.

                                      What is difference between LC1D50U7 and LC1D50AU7?

                                      Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                      LC1D50AU7 has everlink terminals.
                                      LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                      Whereas
                                      LC1D50U7 contactors accommodate LRD33XX overloads.

                                       

                                      Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

                                      ISSUE
                                      Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?
                                      PRODUCT LINE
                                      Auxiliary contacts for the Tesys D line
                                      ENVIRONMENT
                                      Tesys D-Line and Tesys F
                                      CAUSE
                                      Fit
                                      RESOLUTION
                                      These contacts will only fit on the following contactors:
                                      Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
                                      Left side mount only to LC1F contactors
                                      CTA-ID : 2002751

                                      What is the part number for 4 pole, 415V Coil contactor and 3A overload?

                                      The part number for 4 pole, 415V Coil contactor and 3A overload is LC1DT20N7 and LRD08



                                      For more information on either item refer to:
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1DT20N7
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD08

                                      What is the part number for 60A contactor with 240V/415V coil?

                                      What is the difference between a LC1D65A3U7 and LC1D65AU7?

                                      The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                                      see data sheets for comparrisons...
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                                      User-added image.................User-added image

                                      What does the (3) designate in the part number LC1D123G7?

                                      For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                                      CTA-ID : 2053127

                                      Does the 150A IEC contactor LC1D150BD with a 24 volt DC coil have a coil suppressor built in?

                                      Issue: 
                                      Does the LC1D150 with a DC coil include suppression? 

                                      Product Line:
                                       Tesys D line contactors and accessories

                                      Environment:
                                      Products sold and used in the United States
                                       
                                      Cause:
                                       Identifying components and accessories
                                       
                                      Resolution:
                                       
                                      Yes. Suppression is built into the 150A DC contactor coil.