MASTER YOUR CASTLE with your new build or reno project
Enter competition
TeSys d 4-pole contactor 65A, EverLink, control connection by screw clamp terminals

LC1DT60ACD

Contactor

TeSys d 4-pole contactor 65A, EverLink, control connection by screw clamp terminals
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
4 NO
[Ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current
      60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      DC standard
      [Uc] control circuit voltage
      36 V DC
      Auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
    • 10 A (at 60 °C) for signalling circuit
    • 60 A (at 60 °C) for power circuit
      • Irms rated making capacity
      • 140 A AC for signalling circuit conforming to IEC 60947-5-1
      • 250 A DC for signalling circuit conforming to IEC 60947-5-1
      • 800 A at 440 V for power circuit conforming to IEC 60947
        • Rated breaking capacity
          800 A at 440 V for power circuit conforming to IEC 60947
          [Icw] rated short-time withstand current
        • 320 A 40 °C - 10 s for power circuit
        • 720 A 40 °C - 1 s for power circuit
        • 72 A 40 °C - 10 min for power circuit
        • 165 A 40 °C - 1 min for power circuit
        • 100 A - 1 s for signalling circuit
        • 120 A - 500 ms for signalling circuit
        • 140 A - 100 ms for signalling circuit
          • Associated fuse rating
          • 10 A gG for signalling circuit conforming to IEC 60947-5-1
          • 80 A gG at <= 690 V coordination type 1 for power circuit
          • 80 A gG at <= 690 V coordination type 2 for power circuit
            • Average impedance
              1.6 mOhm - Ith 60 A 50 Hz for power circuit
              [Ui] rated insulation voltage
            • power circuit: 600 V CSA certified
            • power circuit: 600 V UL certified
            • signalling circuit: 690 V conforming to IEC 60947-1
            • signalling circuit: 600 V CSA certified
            • signalling circuit: 600 V UL certified
            • power circuit: 690 V conforming to IEC 60947-4-1
              • Electrical durability
                0.7 Mcycles 60 A AC-1 at Ue <= 440 V
                Power dissipation per pole
                5.8 W AC-1
                Protective cover
                with
                Mounting support
              • rail
              • plate
                • Standards
                • CSA C22.2 No 14
                • EN 60947-4-1
                • EN 60947-5-1
                • IEC 60947-4-1
                • IEC 60947-5-1
                • UL 508
                  • Product certifications
                  • GL
                  • BV
                  • RINA
                  • CSA
                  • LROS (Lloyds register of shipping)
                  • DNV
                  • CCC
                  • GOST
                  • UL
                    • Connections - terminals
                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end
                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end
                      • Tightening torque
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                      • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
                      • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
                        • Operating time
                        • 42.5...57.5 ms closing
                        • 16...24 ms opening
                          • Safety reliability level
                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                            • Mechanical durability
                              10 Mcycles
                              Maximum operating rate
                              3600 cyc/h 60 °C
                              Coil technology
                              built-in bidirectional peak limiting diode suppressor
                              Control circuit voltage limits
                            • drop-out: 0.1...0.3 Uc DC (at 60 °C)
                            • operational: 0.75...1.25 Uc DC (at 60 °C)
                              • Time constant
                                34 ms
                                Inrush power in W
                                19-19 W (at 20 °C)
                                Hold-in power consumption in W
                                7.4-7.4 W at 20 °C
                                Auxiliary contacts type
                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                • Signalling circuit frequency
                                  25...400 Hz
                                  Minimum switching current
                                  5 mA for signalling circuit
                                  Minimum switching voltage
                                  17 V for signalling circuit
                                  Non-overlap time
                                • 1.5 ms on de-energisation between NC and NO contact
                                • 1.5 ms on energisation between NC and NO contact
                                  • Insulation resistance
                                    > 10 MOhm for signalling circuit
                                    Contact compatibility
                                    M7
                                    Compatibility code
                                    LC1D
                                    IP degree of protection
                                    IP20 front face conforming to IEC 60529
                                    Protective treatment
                                    TH conforming to IEC 60068-2-30
                                    Pollution degree
                                    3
                                    Ambient air temperature for operation
                                    -5-60 °C
                                    Ambient air temperature for storage
                                    -60-80 °C
                                    Permissible ambient air temperature around the device
                                    -40-70 °C at Uc
                                    Operating altitude
                                    3000 m without
                                    Fire resistance
                                    850 °C conforming to IEC 60695-2-1
                                    Flame retardance
                                    V1 conforming to UL 94
                                    Mechanical robustness
                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                  • shocks contactor closed: 15 Gn for 11 ms
                                  • shocks contactor open: 10 Gn for 11 ms
                                    • Height
                                      122 mm
                                      Width
                                      70 mm
                                      Depth
                                      120 mm
                                      Net weight
                                      1.165 kg
                                      Warranty
                                      18 months

                                      Documents & downloads

                                      hide show
                                      Filter items
                                      • All

                                      • CAD Files and Packs

                                      • Product Brochures

                                      • Movies

                                      • Technical Data Catalogues

                                      • Catalog Page

                                      • Technical Leaflet

                                      • Product Environmental

                                      • End of Life Manual

                                      • Data Bulletin

                                      • Installation Instruction

                                      • Handout

                                      • Operating Manuals

                                      • Application Solutions

                                      • Certificates (MSDS)

                                      • Declaration of Conformity

                                      • White Paper

                                      • eTechPub

                                      • Marine Certificate

                                      • Software - Released