Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
4 NO
[Ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current
      40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      AC at 50/60 Hz
      [Uc] control circuit voltage
      220 V AC 50/60 Hz
      Auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
    • 10 A (at 60 °C) for signalling circuit
    • 40 A (at 60 °C) for power circuit
      • Irms rated making capacity
      • 140 A AC for signalling circuit conforming to IEC 60947-5-1
      • 250 A DC for signalling circuit conforming to IEC 60947-5-1
      • 450 A at 440 V for power circuit conforming to IEC 60947
        • Rated breaking capacity
          450 A at 440 V for power circuit conforming to IEC 60947
          [Icw] rated short-time withstand current
        • 50 A 40 °C - 10 min for power circuit
        • 120 A 40 °C - 1 min for power circuit
        • 240 A 40 °C - 10 s for power circuit
        • 380 A 40 °C - 1 s for power circuit
        • 100 A - 1 s for signalling circuit
        • 120 A - 500 ms for signalling circuit
        • 140 A - 100 ms for signalling circuit
          • Associated fuse rating
          • 10 A gG for signalling circuit conforming to IEC 60947-5-1
          • 63 A gG at <= 690 V coordination type 1 for power circuit
          • 40 A gG at <= 690 V coordination type 2 for power circuit
            • Average impedance
              2 mOhm - Ith 40 A 50 Hz for power circuit
              [Ui] rated insulation voltage
            • power circuit: 600 V CSA certified
            • power circuit: 600 V UL certified
            • signalling circuit: 690 V conforming to IEC 60947-1
            • signalling circuit: 600 V CSA certified
            • signalling circuit: 600 V UL certified
            • power circuit: 690 V conforming to IEC 60947-4-1
              • Electrical durability
                1.4 Mcycles 40 A AC-1 at Ue <= 440 V
                Power dissipation per pole
                3.2 W AC-1
                Protective cover
                with
                Mounting support
              • rail
              • plate
                • Standards
                • CSA C22.2 No 14
                • EN 60947-4-1
                • EN 60947-5-1
                • IEC 60947-4-1
                • IEC 60947-5-1
                • UL 508
                  • Product certifications
                  • UL
                  • LROS (Lloyds register of shipping)
                  • CCC
                  • BV
                  • RINA
                  • DNV
                  • GL
                  • GOST
                  • CSA
                    • Connections - terminals
                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                    • power circuit: connector 1 cable(s) 2.5-10 mm²flexible without cable end
                    • power circuit: connector 2 cable(s) 2.5-10 mm²flexible without cable end
                    • power circuit: connector 1 cable(s) 2.5-10 mm²flexible with cable end
                    • power circuit: connector 2 cable(s) 2.5-10 mm²flexible with cable end
                    • power circuit: connector 1 cable(s) 2.5-16 mm²solid without cable end
                    • power circuit: connector 2 cable(s) 2.5-16 mm²solid without cable end
                      • Tightening torque
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                      • power circuit: 1.7 N.m - on connector - with screwdriver flat Ø 6 mm
                      • power circuit: 1.7 N.m - on connector - with screwdriver Philips No 2
                        • Operating time
                        • 4...19 ms opening
                        • 12...22 ms closing
                          • Safety reliability level
                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                            • Mechanical durability
                              15 Mcycles
                              Maximum operating rate
                              3600 cyc/h 60 °C
                              Coil technology
                              without built-in suppressor module
                              Inrush power in VA
                            • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
                            • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
                              • Hold-in power consumption in VA
                              • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
                              • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
                                • Heat dissipation
                                  2-3 W at 50/60 Hz
                                  Auxiliary contacts type
                                • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                • type mirror contact 1 NC conforming to IEC 60947-4-1
                                  • Signalling circuit frequency
                                    25...400 Hz
                                    Minimum switching current
                                    5 mA for signalling circuit
                                    Minimum switching voltage
                                    17 V for signalling circuit
                                    Non-overlap time
                                  • 1.5 ms on de-energisation between NC and NO contact
                                  • 1.5 ms on energisation between NC and NO contact
                                    • Insulation resistance
                                      > 10 MOhm for signalling circuit
                                      Contact compatibility
                                      M6
                                      Compatibility code
                                      LC1D
                                      IP degree of protection
                                      IP20 front face conforming to IEC 60529
                                      Protective treatment
                                      TH conforming to IEC 60068-2-30
                                      Pollution degree
                                      3
                                      Ambient air temperature for storage
                                      -60-80 °C
                                      Operating altitude
                                      3000 m without derating
                                      Fire resistance
                                      850 °C conforming to IEC 60695-2-1
                                      Flame retardance
                                      V1 conforming to UL 94
                                      Mechanical robustness
                                    • vibrations contactor open: 2 Gn, 5...300 Hz
                                    • vibrations contactor closed: 4 Gn, 5...300 Hz
                                    • shocks contactor closed: 15 Gn for 11 ms
                                    • shocks contactor open: 8 Gn for 11 ms
                                      • Height
                                        91 mm
                                        Width
                                        45 mm
                                        Depth
                                        99 mm
                                        Net weight
                                        0.425 kg
                                        Unit Type of Package 1
                                        PCE
                                        Number of Units in Package 1
                                        1
                                        Package 1 Weight
                                        470 g
                                        Package 1 Height
                                        5.3 cm
                                        Package 1 width
                                        9.5 cm
                                        Package 1 Length
                                        11.7 cm
                                        Sustainable offer status
                                        Green Premium product
                                        REACh free of SVHC
                                        Yes
                                        EU RoHS Directive
                                        Compliant
                                        Toxic heavy metal free
                                        Yes
                                        Mercury free
                                        Yes
                                        RoHS exemption information
                                        Yes
                                        China RoHS Regulation
                                         Pro-active China RoHS declaration (out of China RoHS legal scope)
                                        Environmental Disclosure
                                        ENVPEP110229EN
                                        Circularity Profile
                                        ENVEOLI1102029EN
                                        WEEE
                                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                        PVC free
                                        Yes
                                        California proposition 65
                                        WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                        Warranty
                                        18 months

                                        Documents & downloads

                                        hide show
                                        Filter items
                                        • All

                                        • CAD Files and Packs

                                        • Product Brochures

                                        • Technical Data Catalogues

                                        • Product Environmental

                                        • Installation Instruction

                                        • End of Life Manual

                                        • Data Bulletin

                                        • Certificates (MSDS)

                                        • Declaration of Conformity

                                        Frequently Asked Questions

                                        hide show

                                        What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                        Issue:
                                        Identifying replacement coils for tesys D non-reversing and reversing conactors

                                        Product Line:
                                        IEC Contactors and Starters

                                        Environment:
                                        Products sold and used in the United States

                                        Cause:
                                        Replacement coil is needed

                                        Resolution:
                                        DC replacement coils are not available.
                                        AC Coils are 50/60 hertz for voltages as listed below:

                                        Volts - Part Number
                                        12 ____ LXD1J7
                                        21 ____ LXD1Z7
                                        24 ____ LXD1B7
                                        32 ____ LXD1C7
                                        36 ____ LXD1CC7
                                        42 ____ LXD1D7
                                        48 ____ LXD1E7
                                        60 ____ LXD1EE7
                                        100 ___ LXD1K7 ( never brought to North America )
                                        110 ___ LXD1F7
                                        115 ___ LXD1FE7
                                        120 ___ LXD1G7
                                        127 ___ LXD1FC7
                                        200 ___ LXD1L7
                                        208 ___ LXD1LE7
                                        220 ___ LXD1M7
                                        230 ___ LXD1P7
                                        240 ___ LXD1U7
                                        277 ___ LXD1W7
                                        380 ___ LXD1Q7
                                        400 ___ LXD1V7
                                        415 ___ LXD1N7
                                        440 ___ LXD1R7
                                        480 ___ LXD1T7
                                        575 ___ LXD1SC7
                                        600 ___ LXD1X7
                                        690 ___ LXD1Y7


                                        Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                        What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                        Issue:
                                        Identifying maximum voltage of an LC1D contactor

                                        Product Line:
                                        TeSys D Contactors

                                        Environment:
                                        IEC contactors and starters used in North America

                                        Cause:
                                        n/a

                                        Resolution:
                                        IThe maximum voltage per UL and CSA is 600VAC. 
                                         

                                        Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                        Issue:
                                        Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                        Product Line: 
                                        Tesys D Contactors

                                        Environment:
                                        IEC contactors

                                        Resolution:
                                        The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                         

                                        What is the altitude derating for a TeSys D-Line contactor?

                                        Issue:​
                                        What is the altitude derating for a TeSys D-Line contactor?

                                        Product Line:
                                        Digest 177 Section 18 : Contactors and Starters, IEC

                                        Environment:
                                        North American Products

                                        Resolution:
                                        The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                        Voltage
                                        3500m x 0.90
                                        4000m x 0.80
                                        4500m x 0.70
                                        5000m x 0.60

                                        Current
                                        3500m x 0.92
                                        4000m x 0.90
                                        4500m x 0.88
                                        5000m x 0.86

                                        For example, an LC1D80 at 5000 meters:
                                        - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                        - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                         

                                        What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                        Issue:
                                        Identifying power terminal lug data for the D2 style contactors

                                        Product Line:
                                        Tesys D line contactors

                                        Environment:
                                        Products sold and used in the United States

                                        Cause:
                                        Power terminal lug data required

                                        Resolution:
                                        For contactors with screw clamp terminals:
                                        stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                        stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                        solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                        What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                        Issue:
                                        Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                        Product Line:
                                        NEMA combination starters

                                        Environment:
                                        Products sold and used in the United States

                                        Resolution:
                                        For contactors with screw clamp terminals:
                                        stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                        stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                        solid cable: One or Two #18-8 AWG per terminal.

                                        What is the color scheme of the Tesys D-Line contactors?

                                        Issue:
                                        Looking for different color scheme of the Tesys D-Line contactors.

                                        Product Line:
                                        Tesys D Contactors

                                        Environment:
                                        LC1D contactors

                                        Resolution:
                                        Beige and dark gray.
                                         

                                        What is the heat dissipated by the LC1D09 contactor?

                                        Issue:
                                        Contactors dissipate heat

                                        Product Line:
                                        Tesys D Contactors

                                        Environment:
                                        IEC Contactors and Starters

                                        Resolution:
                                        Total heat dissipation is 3.60 watts maximum; .20 watts dissipated across each power pole and 2 to 3 watts dissipated by the AC control coil.


                                         

                                        What does the T indicate in the LC1DT contactor catalog number?

                                        Issue:
                                        LC1DT catalog numbers

                                        Product Line:
                                        Tesys D line Contactors

                                        Environment:
                                        North American Products

                                        Resolution:
                                        The T indicates that the device is a 4 poles with all normally open poles.  4 pole units only have resistive (AC-1) power contact ratings.

                                        Are the D-Line contactors rated to break DC voltages?

                                        Issue: 
                                        Can the TeSys D line be used to control DC loads? 

                                        Product Line:
                                        Tesys D contactors

                                        Environment:
                                        Products sold and used in the United States
                                         
                                        Cause:
                                         DC power circuit
                                         
                                        Resolution:
                                         
                                        Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                        Devices are suitable but not UL Listed for DC applications.

                                        More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                         

                                        What are the stand alone short circuit current ratings on the LC1D** contactors?

                                        Issue:
                                        Tesys D SCCR

                                        Product Line:
                                        Contactors and Overload Relays

                                        Environment:
                                        TeSys™ D Contactors and Overload Relays
                                         
                                        Resolution:
                                        The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                        They are as follows:
                                        Horsepower SCCR (A)

                                        0 thru 1 1,000
                                        1 thru 50 5,000
                                        51 thru 200 10,000
                                        201 thru 400 18,000
                                        401 thru 600 30,000
                                        601 thru 900 42,000
                                        901 thru 1600 85,000
                                        1601+ 100,000

                                        What is the code for the newer version of the LC1D40U7

                                        That has been replaced with the Everlink LC1D40AU7
                                        Show More