Quantcast

TeSys D Contactor, 4P(4 NO) AC-1 - <= 440V, 40A, 120VAC, 50/60 Hz Coil

TeSys D Contactor, 4P(4 NO) AC-1 - <= 440V, 40A, 120VAC, 50/60 Hz Coil

TeSys D Contactor, 4P(4 NO) AC-1 - <= 440V, 40A, 120VAC, 50/60 Hz Coil

Item Number: LC1DT40G7

Retail
$722.10
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height91 mm

Depth icon

Depth99 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

      40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

      Electrical durability

      1.4 Mcycles 40 A AC-1 at Ue <= 440 V

      Mounting support

    • rail
    • plate
      • Standards

      • CSA C22.2 No 14
      • EN 60947-4-1
      • EN 60947-5-1
      • IEC 60947-4-1
      • IEC 60947-5-1
      • UL 508
        • Product certifications

        • DNV
        • GOST
        • BV
        • GL
        • CSA
        • UL
        • LROS (Lloyds register of shipping)
        • RINA
        • CCC
          • Connections - terminals

          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
          • power circuit: connector 1 cable(s) 2.5-10 mm²flexible without cable end
          • power circuit: connector 2 cable(s) 2.5-10 mm²flexible without cable end
          • power circuit: connector 1 cable(s) 2.5-10 mm²flexible with cable end
          • power circuit: connector 2 cable(s) 2.5-10 mm²flexible with cable end
          • power circuit: connector 1 cable(s) 2.5-16 mm²solid without cable end
          • power circuit: connector 2 cable(s) 2.5-16 mm²solid without cable end
            • Mechanical durability

              15 Mcycles

              Insulation resistance

              > 10 MOhm for signalling circuit

              IP degree of protection

              IP20 front face conforming to IEC 60529

              Ambient air temperature for operation

            • -40-60 °C
            • 60-70 °C with derating
              • Ambient air temperature for storage

                -60-80 °C

                Height

                91 mm

                Width

                45 mm

                Depth

                99 mm

                Net weight

                0.425 kg

                REACh Regulation

                Free of Substances of Very High Concern above the threshold

                REACh free of SVHC

                Yes

                EU RoHS Directive

                Compliant

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                 Pro-active China RoHS declaration (out of China RoHS legal scope)

                Environmental Disclosure

                ENVPEP110229EN

                Circularity Profile

                ENVEOLI1102029EN

                California proposition 65

                WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

                Others

                Product name

                TeSys D

                Device short name

                LC1D

                Contactor application

                resistive load

                Utilisation category

                AC-1

                Poles description

                4P

                Pole contact composition

                4 NO

                Control circuit type

                AC at 50/60 Hz

                [Uc] control circuit voltage

                120 V AC 50/60 Hz

                Auxiliary contact composition

                1 NO + 1 NC

                [Uimp] rated impulse withstand voltage

                6 kV conforming to IEC 60947

                Overvoltage category

                III

                [Ith] conventional free air thermal current

              • 10 A (at 60 °C) for signalling circuit
              • 40 A (at 60 °C) for power circuit
                • Irms rated making capacity

                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 450 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity

                    450 A at 440 V for power circuit conforming to IEC 60947

                    [Icw] rated short-time withstand current

                  • 50 A 40 °C - 10 min for power circuit
                  • 120 A 40 °C - 1 min for power circuit
                  • 240 A 40 °C - 10 s for power circuit
                  • 380 A 40 °C - 1 s for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating

                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 63 A gG at <= 690 V coordination type 1 for power circuit
                    • 40 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance

                        2 mOhm - Ith 40 A 50 Hz for power circuit

                        [Ui] rated insulation voltage

                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                      • power circuit: 690 V conforming to IEC 60947-4-1
                        • Power dissipation per pole

                          3.2 W AC-1

                          Protective cover

                          with

                          Tightening torque

                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                        • power circuit: 1.7 N.m - on connector - with screwdriver flat Ø 6 mm
                        • power circuit: 1.7 N.m - on connector - with screwdriver Philips No 2
                          • Operating time

                          • 4...19 ms opening
                          • 12...22 ms closing
                            • Safety reliability level

                            • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                            • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                              • Maximum operating rate

                                3600 cyc/h 60 °C

                                Coil technology

                                without built-in suppressor module

                                Control circuit voltage limits

                              • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
                              • 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
                              • 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
                              • 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
                                • Inrush power in VA

                                • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
                                • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
                                  • Hold-in power consumption in VA

                                  • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
                                  • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
                                    • Heat dissipation

                                      2-3 W at 50/60 Hz

                                      Auxiliary contacts type

                                    • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                    • type mirror contact 1 NC conforming to IEC 60947-4-1
                                      • Signalling circuit frequency

                                        25...400 Hz

                                        Minimum switching current

                                        5 mA for signalling circuit

                                        Minimum switching voltage

                                        17 V for signalling circuit

                                        Non-overlap time

                                      • 1.5 ms on de-energisation between NC and NO contact
                                      • 1.5 ms on energisation between NC and NO contact
                                        • Contact compatibility

                                          M6

                                          Compatibility code

                                          LC1D

                                          Protective treatment

                                          TH conforming to IEC 60068-2-30

                                          Pollution degree

                                          3

                                          Operating altitude

                                          0...3000 m

                                          Fire resistance

                                          850 °C conforming to IEC 60695-2-1

                                          Flame retardance

                                          V1 conforming to UL 94

                                          Mechanical robustness

                                        • vibrations contactor open: 2 Gn, 5...300 Hz
                                        • vibrations contactor closed: 4 Gn, 5...300 Hz
                                        • shocks contactor closed: 15 Gn for 11 ms
                                        • shocks contactor open: 8 Gn for 11 ms
                                          • Package 1 Weight

                                            0.466 kg

                                            Package 1 Height

                                            1.2 dm

                                            Package 1 width

                                            1.1 dm

                                            Package 1 Length

                                            0.55 dm

                                            WEEE

                                            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                            PVC free

                                            Yes
                                            Show all specifications

                                            Documents & downloads

                                            hide show
                                            Filter items
                                            • All

                                            • CAD Files and Packs

                                            • Product Brochures

                                            • Technical Data Catalogues

                                            • Installation Instruction

                                            • End of Life Manual

                                            • Product Environmental

                                            • Data Bulletin

                                            • Technical Drawing

                                            • Certificates (MSDS)

                                            • Declaration of Conformity

                                            Frequently Asked Questions

                                            hide show

                                            What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                            Issue:
                                            Identifying power terminal lug data for the D2 style contactors

                                            Product Line:
                                            IEC Contactors and Starters

                                            Environment:
                                            Tesys D line contactors

                                            Cause:
                                            Power terminal lug data required

                                            Resolution:
                                            For contactors with screw clamp terminals:
                                            stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                            stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                            solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                            What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                            Issue:
                                            Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                            Product Line:
                                            IEC Contactors and Starters

                                            Environment:
                                            Tesys D Contactors

                                            Resolution:
                                            For contactors with screw clamp terminals:
                                            stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                            stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                            solid cable: One or Two #18-8 AWG per terminal.

                                            What does the T indicate in the LC1DT contactor catalog number?

                                            Issue:
                                            LC1DT catalog numbers

                                            Product Line:
                                            IEC Contactors and Starter

                                            Environment:
                                            Tesys D line Contactors

                                            Resolution:
                                            The T indicates that the device is a 4 poles with all normally open poles.  4 pole units only have resistive (AC-1) power contact ratings.

                                            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                            Issue:
                                            Identifying maximum voltage of an LC1D contactor

                                            Product Line:
                                            TeSys D Contactors

                                            Environment:
                                            IEC contactors and starters used in North America

                                            Cause:
                                            n/a

                                            Resolution:
                                            IThe maximum voltage per UL and CSA is 600VAC. 
                                             

                                            What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                            Issue:
                                            Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                            Product Line:
                                            Contactors and Starters IEC

                                            Environment:
                                            Tesys D contactors and GV manual starters

                                            Cause:
                                            Spacer required

                                            Resolution:
                                            Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                                            What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38?

                                            Issue:
                                            LC1D09 - LC1D38 Coil tolerance

                                            Product Line:
                                            Contactors and Starters, IEC

                                            Environment:
                                            Tesys D Contactors

                                            Cause:
                                            Needs the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38.

                                            Resolution:
                                            AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
                                            AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
                                            DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
                                            DC standard coil for LP1D12 and D25: (-20% / +10%)
                                            DC wide range coil for LP1D12 and D25 : (-30% to +25%)
                                            Show More