TeSys LC1DT contactor  4 poles  screw clamp terminals or lugs  with cover  20A to 40A

TeSys D Contactor, 4P(4 NO) AC-1 - <= 440V, 32A, 110VDC, Standard Coil

Catalogue Number: LC1DT32FD
TeSys LC1DT contactor  4 poles  screw clamp terminals or lugs  with cover  20A to 40A
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
4 NO
[Ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current
      32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      DC standard
      [Uc] control circuit voltage
      110 V DC
      Auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
    • 10 A (at 60 °C) for signalling circuit
    • 32 A (at 60 °C) for power circuit
      • Irms rated making capacity
      • 140 A AC for signalling circuit conforming to IEC 60947-5-1
      • 250 A DC for signalling circuit conforming to IEC 60947-5-1
      • 300 A at 440 V for power circuit conforming to IEC 60947
        • Rated breaking capacity
          300 A at 440 V for power circuit conforming to IEC 60947
          [Icw] rated short-time withstand current
        • 40 A 40 °C - 10 min for power circuit
        • 84 A 40 °C - 1 min for power circuit
        • 145 A 40 °C - 10 s for power circuit
        • 240 A 40 °C - 1 s for power circuit
        • 100 A - 1 s for signalling circuit
        • 120 A - 500 ms for signalling circuit
        • 140 A - 100 ms for signalling circuit
          • Associated fuse rating
          • 10 A gG for signalling circuit conforming to IEC 60947-5-1
          • 50 A gG at <= 690 V coordination type 1 for power circuit
          • 35 A gG at <= 690 V coordination type 2 for power circuit
            • Average impedance
              2.5 mOhm - Ith 32 A 50 Hz for power circuit
              [Ui] rated insulation voltage
            • power circuit: 600 V CSA certified
            • power circuit: 600 V UL certified
            • signalling circuit: 690 V conforming to IEC 60947-1
            • signalling circuit: 600 V CSA certified
            • signalling circuit: 600 V UL certified
            • power circuit: 690 V conforming to IEC 60947-4-1
              • Electrical durability
                1 Mcycles 32 A AC-1 at Ue <= 440 V
                Power dissipation per pole
                2.5 W AC-1
                Protective cover
                with
                Mounting support
              • plate
              • rail
                • Standards
                • CSA C22.2 No 14
                • EN 60947-4-1
                • EN 60947-5-1
                • IEC 60947-4-1
                • IEC 60947-5-1
                • UL 508
                  • Product certifications
                  • RINA
                  • UL
                  • LROS (Lloyds register of shipping)
                  • BV
                  • CSA
                  • GOST
                  • CCC
                  • DNV
                  • GL
                    • Connections - terminals
                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                    • power circuit: connector 1 cable(s) 2.5-10 mm²flexible without cable end
                    • power circuit: connector 2 cable(s) 2.5-10 mm²flexible without cable end
                    • power circuit: connector 1 cable(s) 2.5-10 mm²flexible with cable end
                    • power circuit: connector 2 cable(s) 2.5-10 mm²flexible with cable end
                    • power circuit: connector 1 cable(s) 2.5-16 mm²solid without cable end
                    • power circuit: connector 2 cable(s) 2.5-16 mm²solid without cable end
                      • Tightening torque
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                      • power circuit: 1.7 N.m - on connector - with screwdriver flat Ø 6 mm
                      • power circuit: 1.7 N.m - on connector - with screwdriver Philips No 2
                        • Operating time
                        • 16...24 ms opening
                        • 53.55...72.45 ms closing
                          • Safety reliability level
                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                            • Mechanical durability
                              30 Mcycles
                              Maximum operating rate
                              3600 cyc/h 60 °C
                              Coil technology
                              built-in bidirectional peak limiting diode suppressor
                              Control circuit voltage limits
                            • drop-out: 0.1...0.25 Uc DC (at 60 °C)
                            • operational: 0.7...1.25 Uc DC (at 60 °C)
                              • Time constant
                                28 ms
                                Inrush power in W
                                5.4-5.4 W (at 20 °C)
                                Hold-in power consumption in W
                                5.4-5.4 W at 20 °C
                                Auxiliary contacts type
                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                • Signalling circuit frequency
                                  25...400 Hz
                                  Minimum switching current
                                  5 mA for signalling circuit
                                  Minimum switching voltage
                                  17 V for signalling circuit
                                  Non-overlap time
                                • 1.5 ms on de-energisation between NC and NO contact
                                • 1.5 ms on energisation between NC and NO contact
                                  • Insulation resistance
                                    > 10 MOhm for signalling circuit
                                    Contact compatibility
                                    M7
                                    Compatibility code
                                    LC1D
                                    IP degree of protection
                                    IP20 front face conforming to IEC 60529
                                    Protective treatment
                                    TH conforming to IEC 60068-2-30
                                    Pollution degree
                                    3
                                    Ambient air temperature for operation
                                    -5-60 °C
                                    Ambient air temperature for storage
                                    -60-80 °C
                                    Permissible ambient air temperature around the device
                                    -40-70 °C at Uc
                                    Operating altitude
                                    3000 m without
                                    Fire resistance
                                    850 °C conforming to IEC 60695-2-1
                                    Flame retardance
                                    V1 conforming to UL 94
                                    Mechanical robustness
                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                  • shocks contactor closed: 15 Gn for 11 ms
                                  • shocks contactor open: 8 Gn for 11 ms
                                    • Height
                                      91 mm
                                      Width
                                      45 mm
                                      Depth
                                      107 mm
                                      Net weight
                                      0.425 kg
                                      Sustainable offer status
                                      Green Premium product
                                      REACh Regulation
                                      Free of Substances of Very High Concern above the threshold
                                      EU RoHS Directive
                                      Compliant
                                      Mercury free
                                      Yes
                                      RoHS exemption information
                                      Yes
                                      China RoHS Regulation
                                      Product out of China RoHS scope. Substance declaration for your information
                                      Environmental Disclosure
                                      ENVPEP110230EN
                                      Circularity Profile
                                      ENVEOLI1102030EN
                                      WEEE
                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                      Warranty
                                      18 months

                                      Documents & downloads

                                      hide show
                                      Filter items
                                      • All

                                      • Product Brochures

                                      • Technical Data Catalogues

                                      • End of Life Manual

                                      • Product Environmental

                                      • Installation Instruction

                                      • Data Bulletin

                                      • Certificates (MSDS)

                                      • Declaration of Conformity

                                      Frequently Asked Questions

                                      hide show

                                      What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                      Issue:
                                      Identifying replacement coils for tesys D non-reversing and reversing conactors

                                      Product Line:
                                      IEC Contactors and Starters

                                      Environment:
                                      Products sold and used in the United States

                                      Cause:
                                      Replacement coil is needed

                                      Resolution:
                                      DC replacement coils are not available.
                                      AC Coils are 50/60 hertz for voltages as listed below:

                                      Volts - Part Number
                                      12 ____ LXD1J7
                                      21 ____ LXD1Z7
                                      24 ____ LXD1B7
                                      32 ____ LXD1C7
                                      36 ____ LXD1CC7
                                      42 ____ LXD1D7
                                      48 ____ LXD1E7
                                      60 ____ LXD1EE7
                                      100 ___ LXD1K7 ( never brought to North America )
                                      110 ___ LXD1F7
                                      115 ___ LXD1FE7
                                      120 ___ LXD1G7
                                      127 ___ LXD1FC7
                                      200 ___ LXD1L7
                                      208 ___ LXD1LE7
                                      220 ___ LXD1M7
                                      230 ___ LXD1P7
                                      240 ___ LXD1U7
                                      277 ___ LXD1W7
                                      380 ___ LXD1Q7
                                      400 ___ LXD1V7
                                      415 ___ LXD1N7
                                      440 ___ LXD1R7
                                      480 ___ LXD1T7
                                      575 ___ LXD1SC7
                                      600 ___ LXD1X7
                                      690 ___ LXD1Y7


                                      Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                      Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                      Issue:
                                      Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                      Product Line: 
                                      Tesys D Contactors

                                      Environment:
                                      IEC contactors

                                      Resolution:
                                      The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                       

                                      What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                      Issue:
                                      Identifying maximum voltage of an LC1D contactor

                                      Product Line:
                                      TeSys D Contactors

                                      Environment:
                                      IEC contactors and starters used in North America

                                      Cause:
                                      n/a

                                      Resolution:
                                      IThe maximum voltage per UL and CSA is 600VAC. 
                                       

                                      What is the altitude derating for a TeSys D-Line contactor?

                                      Issue:​
                                      What is the altitude derating for a TeSys D-Line contactor?

                                      Product Line:
                                      Digest 177 Section 18 : Contactors and Starters, IEC

                                      Environment:
                                      North American Products

                                      Resolution:
                                      The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                      Voltage
                                      3500m x 0.90
                                      4000m x 0.80
                                      4500m x 0.70
                                      5000m x 0.60

                                      Current
                                      3500m x 0.92
                                      4000m x 0.90
                                      4500m x 0.88
                                      5000m x 0.86

                                      For example, an LC1D80 at 5000 meters:
                                      - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                      - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                       

                                      Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                      Issue:
                                      Mounting adaptor for GV2 and LC1D contactor

                                      Product Line:
                                      Motor Starters and Protectors

                                      Environment:
                                      TeSys GV Manual Starter and Protectors
                                      Tesys D Contactors
                                       
                                      Resolution:
                                      The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                      What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                      Issue:
                                      Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                      Product Line:
                                      NEMA combination starters

                                      Environment:
                                      Products sold and used in the United States

                                      Resolution:
                                      For contactors with screw clamp terminals:
                                      stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                      stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                      solid cable: One or Two #18-8 AWG per terminal.

                                      What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

                                      Issue:
                                      LC*D09-38 coil consumption

                                      Product Line:
                                      Contactors and Overload Relays

                                      Environment:
                                      TeSys™ D Contactors and Overload Relays

                                      Resolution:
                                      The standard DC coil is 5.4 watts of consumption.

                                      What is the color scheme of the Tesys D-Line contactors?

                                      Issue:
                                      Looking for different color scheme of the Tesys D-Line contactors.

                                      Product Line:
                                      Tesys D Contactors

                                      Environment:
                                      LC1D contactors

                                      Resolution:
                                      Beige and dark gray.
                                       

                                      What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                      Issue:
                                      Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                      Product Line:
                                      Contactors and Starters IEC

                                      Environment:
                                      Tesys D contactors and GV manual starters

                                      Cause:
                                      Spacer required

                                      Resolution:
                                      Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                                      Are the D-Line contactors rated to break DC voltages?

                                      Issue: 
                                      Can the TeSys D line be used to control DC loads? 

                                      Product Line:
                                      Tesys D contactors

                                      Environment:
                                      Products sold and used in the United States
                                       
                                      Cause:
                                       DC power circuit
                                       
                                      Resolution:
                                       
                                      Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                      Devices are suitable but not UL Listed for DC applications.

                                      More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                       

                                      What are the stand alone short circuit current ratings on the LC1D** contactors?

                                      Issue:
                                      Tesys D SCCR

                                      Product Line:
                                      Contactors and Overload Relays

                                      Environment:
                                      TeSys™ D Contactors and Overload Relays
                                       
                                      Resolution:
                                      The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                      They are as follows:
                                      Horsepower SCCR (A)

                                      0 thru 1 1,000
                                      1 thru 50 5,000
                                      51 thru 200 10,000
                                      201 thru 400 18,000
                                      401 thru 600 30,000
                                      601 thru 900 42,000
                                      901 thru 1600 85,000
                                      1601+ 100,000

                                      What is the 110V DC coil to fit a Telemechanique contactor 3P 32Amp

                                       The part code is LC1D32FD

                                      What does the T indicate in the LC1DT contactor catalog number?

                                      Issue:
                                      LC1DT catalog numbers

                                      Product Line:
                                      Tesys D line Contactors

                                      Environment:
                                      North American Products

                                      Resolution:
                                      The T indicates that the device is a 4 poles with all normally open poles.  4 pole units only have resistive (AC-1) power contact ratings.

                                      What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

                                      Issue:
                                      What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

                                      Product Line:
                                      IEC Contactors

                                      Environment:
                                      Ordering

                                      Cause:
                                      Selection

                                      Resolution:
                                      The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                                      AC Volts ___Code     AC Volts ___Code
                                      12 ___ J7                   208 ___ LE7
                                      21 ___ Z7                   220 ___ M7
                                      24 ___ B7                  230 ___ P7
                                      32 ___ C7                  240 ___ U7
                                      36 ___ CC7               277 ___ W7
                                      42 ___ D7                  380 ___ Q7
                                      48 ___ E7                   400 ___ V7
                                      60 ___ EE7                415 ___ N7
                                      100 ___ K7                440 ___ R7
                                      110 ___ F7                480 ___ T7
                                      115 ___ FE7              575 ___ SC7
                                      120 ___ G7                600 ___ X7
                                      127 ___ FC7              690 ___ Y7
                                      200 ___ L7                
                                                     
                                      Standard Coil                Low Consumption
                                      DC Volts ___Code          DC Volts ___Code
                                      12 ___ JD                           5 ___ AL
                                      24 ___ BD                         12 ___ JL
                                      36 ___ CD                         20 ___ ZL
                                      48 ___ ED                         24 ___ BL
                                      60 ___ ND                         48 ___ EL
                                      72 ___ SD                         72 ___ SL
                                      110 ___ FD                       96 ___ DL
                                      125 ___ GD                     110 ___ FL
                                      220 ___ MD                    220 ___ ML
                                      250 ___ UD                     250 ___ UL
                                      440 ___ RD                

                                      Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                      Issue:
                                      Auxiliary contact modules for the LC1D and LC2D contactors

                                      Product Line: 
                                      Contactor and Starters - IEC

                                      Environment:
                                      North American Products

                                      Resolution:
                                      Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                      Front Mounting; maximum of 1 block per contactor:

                                      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                      --1-----------1---------LADN11-----------LA1DN11
                                      --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                      --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                      --2-----------0---------LADN20-----------LA1DN20
                                      --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                      --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                      --0-----------2---------LADN02-----------LA1DN02
                                      --2-----------2---------LADN22-----------LA1DN22
                                      --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                      --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                      --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                      --3-----------1---------LADN31------------LA1DN31
                                      --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                      --1-----------3---------LADN13------------LA1DN13
                                      --4-----------0---------LADN40------------LA1DN40
                                      --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                      --0-----------4---------LADN04------------LA1DN04




                                      Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                      --1-----------0--------LADN10----------LA1DN10
                                      --0-----------1--------LADN01----------LA1DN01

                                      Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                      (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                      --1-----------1--------LAD8N11----------LA8DN11
                                      --2-----------0--------LAD8N20----------LA8DN20
                                      --0-----------2--------LAD8N02----------N/A

                                      Footnotes:
                                      {1} EN50 012 Machine Tool Terminal Markings
                                      {2} (2) NO Sealed Dust Tight Contacts
                                      {3} Gold Flash Contacts
                                      {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                      {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                      {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                      What is the Part Number for the Mechanical Interlock for the 4-pole LC1DT20, LC1DT25, LC1DT32, and LC1DT40 Contactors?

                                      Issue:
                                      Four-pole IEC contactors needs the part number for the mechanical interlock

                                      Product Line:
                                      IEC Contactors

                                      Environment:
                                      Tesys D contactors

                                      Resolution:
                                      LADT9R1 is the mechanical interlock and power wiring only. The LADT9RV1 also includes an electrical interlock (2 NC contacts).

                                      What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                      Issue:
                                      Identifying the difference between LAD4TB and LAD4TBDL

                                      Product Line:
                                      IEC contactors and starters

                                      Environment:
                                      Products sold and used in the United States

                                      Cause:
                                      Identifying the difference between two similar part numbers

                                      Resolution:
                                      The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                       

                                      What is the code for a 32Amp 24VDC 3 Pole Contactor ?

                                      Code = LC1D32BD

                                      What is the mechanical interlock for an LC1D32U7

                                       The LAD9R1V reverser kit contains the mechanical interlock you need for the LC1D32U7

                                      What is the Coil control circuit voltage limit for the LC1D32D7 Contactor?

                                      The control circuit voltage limit for the 42V AC Coil on the LC1D32D7 Contactor is 0.8...1.1 Uc (0.8...1.1 x 42V AC) operational at 60 °C, AC 50 Hz

                                      https://www.schneider-electric.com.au/en/search/LC1D32D7

                                      Will a LC1D12F7 operate on 60V DC as a control voltage

                                      No it will not

                                      Need a LC2D323U7 reversing contactor

                                      Use 2 x LC1D32U7 with a LAD9R1V reversing wiring kit

                                      What is the code for a spare coil for LC1D32B7

                                      LXD1B7

                                      What is the code for a 32Amp 24VAC 3 Pole Contactor ?

                                      LC1D32B7

                                      What is the part number for mechanical interlock for 2 x LC1D32U7 contactors?

                                      The part number for a mechanical interlock for 2 x LC1D32U7 contactors is - LAD9V2

                                      For further information , visit link below:-
                                      https://www.schneider-electric.com.au/en/search/LAD9V2

                                      Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

                                      ISSUE
                                      Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?
                                      PRODUCT LINE
                                      Auxiliary contacts for the Tesys D line
                                      ENVIRONMENT
                                      Tesys D-Line and Tesys F
                                      CAUSE
                                      Fit
                                      RESOLUTION
                                      These contacts will only fit on the following contactors:
                                      Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
                                      Left side mount only to LC1F contactors
                                      CTA-ID : 2002751

                                      What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                      Issue:
                                      Identifying power terminal lug data for the D2 style contactors

                                      Product Line:
                                      Tesys D line contactors

                                      Environment:
                                      Products sold and used in the United States

                                      Cause:
                                      Power terminal lug data required

                                      Resolution:
                                      For contactors with screw clamp terminals:
                                      stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                      stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                      solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                      What is the Mechanical Interlock for the LC1D12F7 ?

                                      LAD9R1V Is the code for the Mechanical and Electrical Interlock kit.

                                      What replaces LC1D50BD

                                      Replacement LC1D50ABD

                                      What is the replacement for a LP1D1210BD

                                      You can use a LC1D12BD or for low consumption a LC1D12BL.

                                      I have a LC1D12BD contactor and want to fit a LA4DFB to it

                                       You need to use a LAD4BB adaptor

                                      What is the 24V DC coil to suit the LC1D32•• contactor?

                                      The code for a 24V DC coil to suit the LC1D09 - LC1D38 contactors is BD. So the code becomes LC1D32BD.
                                      But the coil on its own is not available as a separate item.

                                      Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                      Issue:
                                      Can new accessories be used on older style contactors

                                      Product Line:
                                      IEC contactors and starters

                                      Environment:
                                      Products sold and used in the United States

                                      Cause:
                                      Identifying product compatibility

                                      Resolution:
                                      Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                       

                                      Are there replacement dc coils available for LC1D12BD

                                      They are not available as a spare part for the LC1D09-D38 Contactors
                                       

                                      Can the LC1D12BD be changed from a DC operated device to AC operation by changing the coil?

                                      Issue:
                                      Is it possible to swap AC coil to DC coil and vice versa on an LC1D12BD?

                                      Product Line:
                                      Tesys D Contactors

                                      Environment:
                                      LC1D12BD

                                      Resolution:
                                      No, the coil assemblies are not compatible nor can you replace the DC coils.
                                       

                                      What is the part number for overload to suit LC1D32, range of 26.1?

                                      The part number for the overload will be LRD32.

                                       

                                      What is the code for a 40A 110VAC contactor ?

                                      LC1D40AF7

                                      What is the part number for a 3 pole 32amp 415VAC coil contactor and overload?

                                      The part number for a 3 pole 32amp 415VAC coil contactor and overload is - LC1D32N7 & LRD32

                                      For further information , visit links below:-
                                      https://www.schneider-electric.com.au/en/search/LC1D32N7
                                      https://www.schneider-electric.com.au/en/search/LRD32

                                      User-added image

                                      What is the code for a 24 v ac coil to suit a LC1D32 contactor?

                                      LXD1B7 is the code for the 24VAC coil for contactors LC1D09...38.

                                      The code for complete contactor + 24VAC coil is LC1D32B7

                                      What is the difference between LC1DT25 and LC1D25

                                       LC1DT25 is 4 pole and LC1D25 is 3 pole

                                      What is the replacement contactor for the LC1D65004F5?

                                      The new code is LC1DT80AF7 which is made to order.

                                      What is the replacement code for the LC1D633Q?

                                      The new code for this is LC1D65AU7.

                                      What is the part number for LC1D32 contactor with 380V AC Coil?

                                      The part number for LC1D32 contactor with 380V AC Coil is LC1D32N7.
                                      Even though the LC1D32N7 has a 415V AC coil the coil has + or -  10% rating making the coil range 373.5 - 456.5V AC which is suitable for 380V AC.

                                      For more information see:
                                      https://www.schneider-electric.com/en/product-range-selector/664-tesys-d/?p_url=http%3A%2F%2Fwww.ops-ecat.schneider-electric.com%2Fecatalogue%2Fbrowse.do%3Fel_typ%3Dproduct%26cat_id%3DBU_POW_664_L3%26prd_id%3DLC1D32N7%26scp_id%3DZ000

                                      Will the LAD4BB adapter work with a LC1D12BD contactor?

                                      Issue:
                                      Can we use the LAD4BB with the LC1D12BD?

                                      Product Line:
                                      IEC contactors and starters

                                      Environment:
                                      Products sold and used in the United States

                                      Cause:
                                      Identifying product compatibility

                                      Resolution:
                                      The LAD4BB will not work on the DC contactors, just the AC contactors.
                                       

                                      What is the part code for a 4P AC-1 rated 20Amp 24V ac coil contactor

                                       The part code is LC1DT20B7

                                      What mechanical interlock should I use with the LC1D50A••?

                                      The mechanical interlock LAD4CM is the correct one for use with the LC1D50A••.

                                      See attached datasheet for futher information on the LAD4CM.

                                      Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

                                      Issue:  
                                      Tesys D enclosed starter with a DC control 

                                      Product Line:
                                       Enclosed Tesys D line starters

                                      Environment:
                                      North American Products
                                       
                                      Cause:
                                      DC control circuit 
                                       
                                      Resolution:
                                      Yes but limited to 24 VDC.

                                      What is the coil consumption or burden for the Tesys LC*D** contactors?

                                      * 1 or 2
                                      ** 09 through 38

                                      Issue:
                                      Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

                                      Product Line: 
                                      Contactors and Starters - IEC

                                      Environment:
                                      North American Products

                                      Resolution:
                                      All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

                                      What is the part number for 4 pole, 415V Coil contactor and 3A overload?

                                      The part number for 4 pole, 415V Coil contactor and 3A overload is LC1DT20N7 and LRD08



                                      For more information on either item refer to:
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1DT20N7
                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD08

                                      Does the 150A IEC contactor LC1D150BD with a 24 volt DC coil have a coil suppressor built in?

                                      Issue: 
                                      Does the LC1D150 with a DC coil include suppression? 

                                      Product Line:
                                       Tesys D line contactors and accessories

                                      Environment:
                                      Products sold and used in the United States
                                       
                                      Cause:
                                       Identifying components and accessories
                                       
                                      Resolution:
                                       
                                      Yes. Suppression is built into the 150A DC contactor coil.
                                       
                                      Show More