TeSys D Contactor, 4P(4 NO) AC-1 - <= 440V, 32A, 24VDC, Standard Coil

TeSys D Contactor, 4P(4 NO) AC-1 - <= 440V, 32A, 24VDC, Standard Coil

TeSys D Contactor, 4P(4 NO) AC-1 - <= 440V, 32A, 24VDC, Standard Coil

Item Number: LC1DT32BD

Retail
$1,061.17
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height91 mm

Depth icon

Depth107 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

      32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

      Electrical durability

      1 Mcycles 32 A AC-1 at Ue <= 440 V

      Mounting support

    • rail
    • plate
      • Standards

      • CSA C22.2 No 14
      • EN 60947-4-1
      • EN 60947-5-1
      • IEC 60947-4-1
      • IEC 60947-5-1
      • UL 508
        • Product certifications

        • GOST
        • LROS (Lloyds register of shipping)
        • CSA
        • UL
        • DNV
        • RINA
        • GL
        • CCC
        • BV
          • Connections - terminals

          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
          • power circuit: connector 1 cable(s) 2.5-10 mm²flexible without cable end
          • power circuit: connector 2 cable(s) 2.5-10 mm²flexible without cable end
          • power circuit: connector 1 cable(s) 2.5-10 mm²flexible with cable end
          • power circuit: connector 2 cable(s) 2.5-10 mm²flexible with cable end
          • power circuit: connector 1 cable(s) 2.5-16 mm²solid without cable end
          • power circuit: connector 2 cable(s) 2.5-16 mm²solid without cable end
            • Mechanical durability

              30 Mcycles

              Insulation resistance

              > 10 MOhm for signalling circuit

              IP degree of protection

              IP20 front face conforming to IEC 60529

              Ambient air temperature for storage

              -60-80 °C

              Height

              91 mm

              Width

              45 mm

              Depth

              107 mm

              Net weight

              0.425 kg

              EU RoHS Directive

              Compliant

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

              Product out of China RoHS scope. Substance declaration for your information

              Environmental Disclosure

              ENVPEP110230EN

              Circularity Profile

              ENVEOLI1102030EN

              California proposition 65

              WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov

              Others

              Product name

              TeSys D

              Device short name

              LC1D

              Contactor application

              resistive load

              Utilisation category

              AC-1

              Poles description

              4P

              Pole contact composition

              4 NO

              Control circuit type

              DC standard

              [Uc] control circuit voltage

              24 V DC

              Auxiliary contact composition

              1 NO + 1 NC

              [Uimp] rated impulse withstand voltage

              6 kV conforming to IEC 60947

              Overvoltage category

              III

              [Ith] conventional free air thermal current

            • 10 A (at 60 °C) for signalling circuit
            • 32 A (at 60 °C) for power circuit
              • Irms rated making capacity

              • 140 A AC for signalling circuit conforming to IEC 60947-5-1
              • 250 A DC for signalling circuit conforming to IEC 60947-5-1
              • 300 A at 440 V for power circuit conforming to IEC 60947
                • Rated breaking capacity

                  300 A at 440 V for power circuit conforming to IEC 60947

                  [Icw] rated short-time withstand current

                • 40 A 40 °C - 10 min for power circuit
                • 84 A 40 °C - 1 min for power circuit
                • 145 A 40 °C - 10 s for power circuit
                • 240 A 40 °C - 1 s for power circuit
                • 100 A - 1 s for signalling circuit
                • 120 A - 500 ms for signalling circuit
                • 140 A - 100 ms for signalling circuit
                  • Associated fuse rating

                  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                  • 50 A gG at <= 690 V coordination type 1 for power circuit
                  • 35 A gG at <= 690 V coordination type 2 for power circuit
                    • Average impedance

                      2.5 mOhm - Ith 32 A 50 Hz for power circuit

                      [Ui] rated insulation voltage

                    • power circuit: 600 V CSA certified
                    • power circuit: 600 V UL certified
                    • signalling circuit: 690 V conforming to IEC 60947-1
                    • signalling circuit: 600 V CSA certified
                    • signalling circuit: 600 V UL certified
                    • power circuit: 690 V conforming to IEC 60947-4-1
                      • Power dissipation per pole

                        2.5 W AC-1

                        Protective cover

                        with

                        Tightening torque

                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                      • power circuit: 1.7 N.m - on connector - with screwdriver flat Ø 6 mm
                      • power circuit: 1.7 N.m - on connector - with screwdriver Philips No 2
                        • Operating time

                        • 16...24 ms opening
                        • 53.55...72.45 ms closing
                          • Safety reliability level

                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                            • Maximum operating rate

                              3600 cyc/h 60 °C

                              Coil technology

                              built-in bidirectional peak limiting diode suppressor

                              Time constant

                              28 ms

                              Inrush power in W

                              5.4-5.4 W (at 20 °C)

                              Hold-in power consumption in W

                              5.4-5.4 W at 20 °C

                              Auxiliary contacts type

                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                              • Signalling circuit frequency

                                25...400 Hz

                                Minimum switching current

                                5 mA for signalling circuit

                                Minimum switching voltage

                                17 V for signalling circuit

                                Non-overlap time

                              • 1.5 ms on de-energisation between NC and NO contact
                              • 1.5 ms on energisation between NC and NO contact
                                • Contact compatibility

                                  M7

                                  Compatibility code

                                  LC1D

                                  Protective treatment

                                  TH conforming to IEC 60068-2-30

                                  Pollution degree

                                  3

                                  Operating altitude

                                  3000 m without derating

                                  Fire resistance

                                  850 °C conforming to IEC 60695-2-1

                                  Flame retardance

                                  V1 conforming to UL 94

                                  Mechanical robustness

                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                • shocks contactor closed: 15 Gn for 11 ms
                                • shocks contactor open: 8 Gn for 11 ms
                                  • Unit Type of Package 1

                                    PCE

                                    Number of Units in Package 1

                                    1

                                    Package 1 Weight

                                    637 g

                                    Package 1 Height

                                    5.4 cm

                                    Package 1 width

                                    9.5 cm

                                    Package 1 Length

                                    11.8 cm

                                    WEEE

                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                    PVC free

                                    Yes
                                    Show all specifications

                                    Documents & downloads

                                    hide show
                                    Filter items
                                    • All

                                    • CAD Files and Packs

                                    • Product Brochures

                                    • Technical Data Catalogues

                                    • Product Environmental

                                    • End of Life Manual

                                    • Installation Instruction

                                    • Data Bulletin

                                    • Certificates (MSDS)

                                    • Declaration of Conformity

                                    Frequently Asked Questions

                                    hide show

                                    What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                    Issue:
                                    Identifying replacement coils for tesys D non-reversing and reversing conactors

                                    Product Line:
                                    IEC Contactors and Starters

                                    Environment:
                                    Products sold and used in the United States

                                    Cause:
                                    Replacement coil is needed

                                    Resolution:
                                    DC replacement coils are not available.
                                    AC Coils are 50/60 hertz for voltages as listed below:

                                    Volts - Part Number
                                    12 ____ LXD1J7
                                    21 ____ LXD1Z7
                                    24 ____ LXD1B7
                                    32 ____ LXD1C7
                                    36 ____ LXD1CC7
                                    42 ____ LXD1D7
                                    48 ____ LXD1E7
                                    60 ____ LXD1EE7
                                    100 ___ LXD1K7 ( never brought to North America )
                                    110 ___ LXD1F7
                                    115 ___ LXD1FE7
                                    120 ___ LXD1G7
                                    127 ___ LXD1FC7
                                    200 ___ LXD1L7
                                    208 ___ LXD1LE7
                                    220 ___ LXD1M7
                                    230 ___ LXD1P7
                                    240 ___ LXD1U7
                                    277 ___ LXD1W7
                                    380 ___ LXD1Q7
                                    400 ___ LXD1V7
                                    415 ___ LXD1N7
                                    440 ___ LXD1R7
                                    480 ___ LXD1T7
                                    575 ___ LXD1SC7
                                    600 ___ LXD1X7
                                    690 ___ LXD1Y7


                                    Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                    Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                    Issue:
                                    Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                    Product Line: 
                                    Tesys D Contactors

                                    Environment:
                                    IEC contactors

                                    Resolution:
                                    The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                     

                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                    Issue:
                                    Identifying maximum voltage of an LC1D contactor

                                    Product Line:
                                    TeSys D Contactors

                                    Environment:
                                    IEC contactors and starters used in North America

                                    Cause:
                                    n/a

                                    Resolution:
                                    IThe maximum voltage per UL and CSA is 600VAC. 
                                     

                                    What is the altitude derating for a TeSys D-Line contactor?

                                    Issue:​
                                    What is the altitude derating for a TeSys D-Line contactor?

                                    Product Line:
                                    Digest 177 Section 18 : Contactors and Starters, IEC

                                    Environment:
                                    North American Products

                                    Resolution:
                                    The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                    Voltage
                                    3500m x 0.90
                                    4000m x 0.80
                                    4500m x 0.70
                                    5000m x 0.60

                                    Current
                                    3500m x 0.92
                                    4000m x 0.90
                                    4500m x 0.88
                                    5000m x 0.86

                                    For example, an LC1D80 at 5000 meters:
                                    - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                    - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                     

                                    Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                    Issue:
                                    Mounting adaptor for GV2 and LC1D contactor

                                    Product Line:
                                    Motor Starters and Protectors

                                    Environment:
                                    TeSys GV Manual Starter and Protectors
                                    Tesys D Contactors
                                     
                                    Resolution:
                                    The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                    What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                    Issue:
                                    Identifying the difference between LAD4TB and LAD4TBDL

                                    Product Line:
                                    IEC contactors and starters

                                    Environment:
                                    Products sold and used in the United States

                                    Cause:
                                    Identifying the difference between two similar part numbers

                                    Resolution:
                                    The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                     

                                    What replaces LC1D50BD

                                    Replacement LC1D50ABD

                                    What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

                                    Issue:
                                    LC*D09-38 coil consumption

                                    Product Line:
                                    Contactors and Overload Relays

                                    Environment:
                                    TeSys™ D Contactors and Overload Relays

                                    Resolution:
                                    The standard DC coil is 5.4 watts of consumption.

                                    What is the color scheme of the Tesys D-Line contactors?

                                    Issue:
                                    Looking for different color scheme of the Tesys D-Line contactors.

                                    Product Line:
                                    Tesys D Contactors

                                    Environment:
                                    LC1D contactors

                                    Resolution:
                                    Beige and dark gray.
                                     

                                    What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                    Issue:
                                    Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                    Product Line:
                                    NEMA combination starters

                                    Environment:
                                    Products sold and used in the United States

                                    Resolution:
                                    For contactors with screw clamp terminals:
                                    stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                    stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                    solid cable: One or Two #18-8 AWG per terminal.

                                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                    Issue:
                                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                    Product Line:
                                    Contactors and Starters IEC

                                    Environment:
                                    Tesys D contactors and GV manual starters

                                    Cause:
                                    Spacer required

                                    Resolution:
                                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                                    Are the D-Line contactors rated to break DC voltages?

                                    Issue: 
                                    Can the TeSys D line be used to control DC loads? 

                                    Product Line:
                                    Tesys D contactors

                                    Environment:
                                    Products sold and used in the United States
                                     
                                    Cause:
                                     DC power circuit
                                     
                                    Resolution:
                                     
                                    Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                    Devices are suitable but not UL Listed for DC applications.

                                    More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                     
                                    Show More