What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?
Issue:
Identifying replacement coils for tesys D non-reversing and reversing conactors
Product Line:
IEC Contactors and Starters
Environment:
Products sold and used in the United States
Cause:
Replacement coil is needed
Resolution:
DC replacement coils are not available.
AC Coils are 50/60 hertz for voltages as listed below:
Volts - Part Number
12 ____ LXD1J7
21 ____ LXD1Z7
24 ____ LXD1B7
32 ____ LXD1C7
36 ____ LXD1CC7
42 ____ LXD1D7
48 ____ LXD1E7
60 ____ LXD1EE7
100 ___ LXD1K7 ( never brought to North America )
110 ___ LXD1F7
115 ___ LXD1FE7
120 ___ LXD1G7
127 ___ LXD1FC7
200 ___ LXD1L7
208 ___ LXD1LE7
220 ___ LXD1M7
230 ___ LXD1P7
240 ___ LXD1U7
277 ___ LXD1W7
380 ___ LXD1Q7
400 ___ LXD1V7
415 ___ LXD1N7
440 ___ LXD1R7
480 ___ LXD1T7
575 ___ LXD1SC7
600 ___ LXD1X7
690 ___ LXD1Y7
Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil.
Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?
Issue:
Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor
Product Line:
Tesys D Contactors
Environment:
IEC contactors
Resolution:
The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section). They are next to the auxiliary contact (13/14, 21/22) terminals.
What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?
Issue:
Identifying maximum voltage of an LC1D contactor
Product Line:
TeSys D Contactors
Environment:
IEC contactors and starters used in North America
Cause:
n/a
Resolution:
IThe maximum voltage per UL and CSA is 600VAC.
What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?
Issue:
Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors
Product Line:
IEC Contactors and Starters
Environment:
Tesys D Contactors
Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
stranded cable w/cable end: One or Two #18-10 AWG per terminal.
solid cable: One or Two #18-8 AWG per terminal.
What is the altitude derating for a TeSys D-Line contactor?
Issue:
What is the altitude derating for a TeSys D-Line contactor?
Product Line:
Digest 177 Section 18 : Contactors and Starters, IEC
Environment:
North American Products
Resolution:
The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:
Voltage
3500m x 0.90
4000m x 0.80
4500m x 0.70
5000m x 0.60
Current
3500m x 0.92
4000m x 0.90
4500m x 0.88
5000m x 0.86
For example, an LC1D80 at 5000 meters:
- The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
- The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.
What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?
Issue:
LC*D09-38 coil consumption
Product Line:
Contactors and Overload Relays
Environment:
TeSys™ D Contactors and Overload Relays
Resolution:
The standard DC coil is 5.4 watts of consumption.