Quantcast

TeSys D Contactor, 4P(4 NO), AC-1, <= 440v,="" 20a,="" 110vdc,="" standard="">

TeSys D Contactor, 4P(4 NO), AC-1, <= 440v,="" 20a,="" 110vdc,="" standard="">

TeSys D Contactor, 4P(4 NO), AC-1, <= 440v,="" 20a,="" 110vdc,="" standard="">

Item Number: LC1DT20FD

Product Dimensions

Width icon

Width45 mm

Height icon

Height85 mm

Depth icon

Depth99 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • TeSys D
  • TeSys Deca

Range

  • TeSys
  • TeSys Deca

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690="" v="" ac="" 25...400="">
  • power circuit: <= 300="" v="">

[Ie] rated operational current

20 A (at <60 °c)="" at=""><= 440="" v="" ac="" ac-1="" for="" power="">

Mounting support

  • rail
  • plate

Standards

  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 508
  • IEC 60335-1

Product certifications

  • DNV
  • GOST
  • BV
  • UL
  • CCC
  • GL
  • LROS (Lloyds register of shipping)
  • RINA
  • CSA

Connections - terminals

  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
  • power circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end

Mechanical durability

30 Mcycles

Insulation resistance

> 10 MOhm for signalling circuit

IP degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

  • conforming to IACS E10
  • conforming to IEC 60947-1 Annex Q category D

Ambient air temperature for operation

  • -40...60 °C
  • 60...70 °C with derating

Ambient air temperature for storage

-60...80 °C

Height

85 mm

Width

45 mm

Depth

99 mm

Net weight

0.365 kg

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP110230EN

Circularity Profile

ENVEOLI1102030EN

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Product name

  • TeSys D
  • TeSys Deca

Device short name

LC1D

Contactor application

resistive load

Utilisation category

AC-1

Poles description

4P

Pole contact composition

4 NO

Control circuit type

DC standard

[Uc] control circuit voltage

110 V DC

Auxiliary contact composition

1 NO + 1 NC

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Overvoltage category

III

[Ith] conventional free air thermal current

  • 10 A (at 60 °C) for signalling circuit
  • 20 A (at 60 °C) for power circuit

Irms rated making capacity

  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 250 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

250 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

  • 30 A 40 °C - 10 min for power circuit
  • 61 A 40 °C - 1 min for power circuit
  • 105 A 40 °C - 10 s for power circuit
  • 210 A 40 °C - 1 s for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit

Associated fuse rating

  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 25 A gG at <= 690="" v="" coordination="" type="" 1="" for="" power="">
  • 20 A gG at <= 690="" v="" coordination="" type="" 2="" for="" power="">

Average impedance

2.5 mOhm - Ith 20 A 50 Hz for power circuit

[Ui] rated insulation voltage

  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
  • power circuit: 690 V conforming to IEC 60947-4-1

Power dissipation per pole

1.56 W AC-1

Protective cover

with

Tightening torque

  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
  • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Operating time

  • 16...24 ms opening
  • 53.55...72.45 ms closing

Safety reliability level

  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Maximum operating rate

3600 cyc/h 60 °C

Coil technology

built-in bidirectional peak limiting diode suppressor

Control circuit voltage limits

  • 0.1...0.25 Uc (-40-70 °C):drop-out DC
  • 0.7...1.25 Uc (-40-60 °C):operational DC
  • 1...1.25 Uc (60-70 °C):operational DC

Time constant

28 ms

Inrush power in W

5.4...5.4 W (at 20 °C)

Hold-in power consumption in W

5.4...5.4 W at 20 °C

Auxiliary contacts type

  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching current

5 mA for signalling circuit

Minimum switching voltage

17 V for signalling circuit

Non-overlap time

  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact

Contact compatibility

M7

Compatibility code

LC1D

Protective treatment

TH conforming to IEC 60068-2-30

Pollution degree

3

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

  • vibrations contactor open: 2 Gn, 5...300 Hz
  • vibrations contactor closed: 4 Gn, 5...300 Hz
  • shocks contactor closed: 15 Gn for 11 ms
  • shocks contactor open: 10 Gn for 11 ms

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

552.0 g

Package 1 Height

5.5 cm

Package 1 width

9.5 cm

Package 1 Length

12 cm

PVC free

Yes
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Product Environmental

  • Certificates (MSDS)

  • Declaration of Conformity