Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

      20 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

      Mounting support

    • rail
    • plate
      • Standards

      • CSA C22.2 No 14
      • EN 60947-4-1
      • EN 60947-5-1
      • IEC 60947-4-1
      • IEC 60947-5-1
      • UL 508
        • Product certifications

        • BV
        • GOST
        • LROS (Lloyds register of shipping)
        • DNV
        • UL
        • CSA
        • GL
        • RINA
        • CCC
          • Connections - terminals

          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
          • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
          • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
          • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
          • power circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
          • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
          • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
            • Mechanical durability

              15 Mcycles

              Insulation resistance

              > 10 MOhm for signalling circuit

              IP degree of protection

              IP20 front face conforming to IEC 60529

              Ambient air temperature for operation

            • -40-60 °C
            • 60-70 °C with derating
              • Ambient air temperature for storage

                -60-80 °C

                Height

                85 mm

                Width

                45 mm

                Depth

                92 mm

                Net weight

                0.365 kg

                REACh Regulation

                Free of Substances of Very High Concern above the threshold

                REACh free of SVHC

                Yes

                EU RoHS Directive

                Compliant

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                 Pro-active China RoHS declaration (out of China RoHS legal scope)

                Environmental Disclosure

                ENVPEP1501004EN

                Circularity Profile

                ENVEOLI1501004EN

                California proposition 65

                WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

                Others

                Product name

                TeSys D

                Device short name

                LC1D

                Contactor application

                resistive load

                Utilisation category

                AC-1

                Poles description

                4P

                Pole contact composition

                4 NO

                Control circuit type

                AC at 50/60 Hz

                [Uc] control circuit voltage

                110 V AC 50/60 Hz

                Auxiliary contact composition

                1 NO + 1 NC

                [Uimp] rated impulse withstand voltage

                6 kV conforming to IEC 60947

                Overvoltage category

                III

                [Ith] conventional free air thermal current

              • 10 A (at 60 °C) for signalling circuit
              • 20 A (at 60 °C) for power circuit
                • Irms rated making capacity

                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 250 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity

                    250 A at 440 V for power circuit conforming to IEC 60947

                    [Icw] rated short-time withstand current

                  • 30 A 40 °C - 10 min for power circuit
                  • 61 A 40 °C - 1 min for power circuit
                  • 105 A 40 °C - 10 s for power circuit
                  • 210 A 40 °C - 1 s for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating

                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 25 A gG at <= 690 V coordination type 1 for power circuit
                    • 20 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance

                        2.5 mOhm - Ith 20 A 50 Hz for power circuit

                        [Ui] rated insulation voltage

                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                      • power circuit: 690 V conforming to IEC 60947-4-1
                        • Power dissipation per pole

                          1.56 W AC-1

                          Protective cover

                          with

                          Tightening torque

                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                        • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                        • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                        • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                          • Operating time

                          • 4...19 ms opening
                          • 12...22 ms closing
                            • Safety reliability level

                            • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                            • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                              • Maximum operating rate

                                3600 cyc/h 60 °C

                                Coil technology

                                without built-in suppressor module

                                Control circuit voltage limits

                              • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
                              • 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
                              • 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
                              • 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
                                • Inrush power in VA

                                • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
                                • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
                                  • Hold-in power consumption in VA

                                  • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
                                  • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
                                    • Heat dissipation

                                      2-3 W at 50/60 Hz

                                      Auxiliary contacts type

                                    • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                    • type mirror contact 1 NC conforming to IEC 60947-4-1
                                      • Signalling circuit frequency

                                        25...400 Hz

                                        Minimum switching current

                                        5 mA for signalling circuit

                                        Minimum switching voltage

                                        17 V for signalling circuit

                                        Non-overlap time

                                      • 1.5 ms on de-energisation between NC and NO contact
                                      • 1.5 ms on energisation between NC and NO contact
                                        • Contact compatibility

                                          M6

                                          Compatibility code

                                          LC1D

                                          Protective treatment

                                          TH conforming to IEC 60068-2-30

                                          Pollution degree

                                          3

                                          Operating altitude

                                          0...3000 m

                                          Fire resistance

                                          850 °C conforming to IEC 60695-2-1

                                          Flame retardance

                                          V1 conforming to UL 94

                                          Mechanical robustness

                                        • vibrations contactor open: 2 Gn, 5...300 Hz
                                        • vibrations contactor closed: 4 Gn, 5...300 Hz
                                        • shocks contactor closed: 15 Gn for 11 ms
                                        • shocks contactor open: 10 Gn for 11 ms
                                          • Unit Type of Package 1

                                            PCE

                                            Number of Units in Package 1

                                            1

                                            Package 1 Weight

                                            397 g

                                            Package 1 Height

                                            5.5 cm

                                            Package 1 width

                                            9.5 cm

                                            Package 1 Length

                                            12 cm

                                            WEEE

                                            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                            PVC free

                                            Yes
                                            Show all specifications

                                            Documents & downloads

                                            hide show
                                            Filter items
                                            • All

                                            • CAD Files and Packs

                                            • Product Brochures

                                            • Technical Data Catalogues

                                            • Product Environmental

                                            • End of Life Manual

                                            • Installation Instruction

                                            • Data Bulletin

                                            • Certificates (MSDS)

                                            • Declaration of Conformity

                                            Frequently Asked Questions

                                            hide show

                                            What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                            Issue:
                                            Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                            Product Line:
                                            IEC Contactors and Starters

                                            Environment:
                                            Tesys D Contactors

                                            Resolution:
                                            For contactors with screw clamp terminals:
                                            stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                            stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                            solid cable: One or Two #18-8 AWG per terminal.