TeSys LC1D contactor, 3 poles, screw clamp terminals or connectors, cover, 80A to 95A

Contactor

Catalogue Number: LC1D95U5
TeSys LC1D contactor, 3 poles, screw clamp terminals or connectors, cover, 80A to 95A
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-3
    • AC-4
    • AC-1
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 300 V DC 25...400 Hz
      • power circuit: <= 1000 V AC
        • [Ie] rated operational current
        • 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
        • 95 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
          • Motor power kW
          • 45 kW at 415...440 V AC 50/60 Hz (AC-3)
          • 55 kW at 500 V AC 50/60 Hz (AC-3)
          • 45 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 45 kW at 1000 V AC 50/60 Hz (AC-3)
          • 15 kW at 400 V AC 50/60 Hz (AC-4)
          • 25 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 45 kW at 380...400 V AC 50/60 Hz (AC-3)
            • Motor power hp
            • 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 7.5 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 25 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                AC at 50 Hz
                [Uc] control circuit voltage
                240 V AC 50 Hz
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                8 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 125 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 1100 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    1100 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 1100 A 40 °C - 1 s for power circuit
                  • 135 A 40 °C - 10 min for power circuit
                  • 800 A 40 °C - 10 s for power circuit
                  • 400 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 200 A gG at <= 690 V coordination type 1 for power circuit
                    • 160 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        0.8 mOhm - Ith 125 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • power circuit: 1000 V conforming to IEC 60947-4-1
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                        • Electrical durability
                        • 1.2 Mcycles 95 A AC-3 at Ue <= 440 V
                        • 1.3 Mcycles 125 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 12.5 W AC-1
                          • 7.2 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • CCC
                                • GOST
                                • RINA
                                • BV
                                • LROS (Lloyds register of shipping)
                                • DNV
                                • GL
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: connector 1 cable(s) 4-50 mm²flexible without cable end
                                  • power circuit: connector 2 cable(s) 4-25 mm²flexible without cable end
                                  • power circuit: connector 1 cable(s) 4-50 mm²flexible with cable end
                                  • power circuit: connector 2 cable(s) 4-16 mm²flexible with cable end
                                  • power circuit: connector 1 cable(s) 4-50 mm²solid without cable end
                                  • power circuit: connector 2 cable(s) 4-25 mm²solid without cable end
                                    • Tightening torque
                                    • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 9 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
                                    • power circuit: 9 N.m - on connector hexagonal screw head 4 mm
                                      • Operating time
                                      • 20...35 ms closing
                                      • 6...20 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            10 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            without built-in suppressor module
                                            Control circuit voltage limits
                                          • drop-out: 0.3...0.6 Uc AC 50 Hz (at 55 °C)
                                          • operational: 0.85...1.1 Uc AC 50 Hz (at 55 °C)
                                            • Inrush power in VA
                                              200-200 VA 50 Hz cos phi 0.75 (at 20 °C)
                                              Hold-in power consumption in VA
                                              20-20 VA 50 Hz cos phi 0.3 (at 20 °C)
                                              Heat dissipation
                                              6-10 W at 50 Hz
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Contact compatibility
                                                  M12
                                                  Compatibility code
                                                  LC1D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for operation
                                                  -5-60 °C
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Permissible ambient air temperature around the device
                                                  -40-70 °C at Uc
                                                  Operating altitude
                                                  3000 m without
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • shocks contactor open: 8 Gn for 11 ms
                                                • vibrations contactor closed: 3 Gn, 5...300 Hz
                                                • shocks contactor closed: 10 Gn for 11 ms
                                                  • Height
                                                    127 mm
                                                    Width
                                                    85 mm
                                                    Depth
                                                    130 mm
                                                    Net weight
                                                    1.61 kg
                                                    Sustainable offer status
                                                    Green Premium product
                                                    REACh Regulation
                                                    Free of Substances of Very High Concern above the threshold
                                                    REACh free of SVHC
                                                    Yes
                                                    EU RoHS Directive
                                                    Compliant
                                                    Toxic heavy metal free
                                                    Yes
                                                    Mercury free
                                                    Yes
                                                    RoHS exemption information
                                                    Yes
                                                    China RoHS Regulation
                                                    X
                                                    Environmental Disclosure
                                                    ENVPEP110205EN
                                                    WEEE
                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • CAD Files and Packs

                                                    • Product Brochures

                                                    • Technical Data Catalogues

                                                    • Product Environmental

                                                    • Installation Instruction

                                                    • Certificates (MSDS)

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                    Issue:
                                                    Identifying maximum power voltage of an LC1D contactor

                                                    Product Line:
                                                    Digest 177 Section 18: IEC Contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying ratings per UL and CSA

                                                    Resolution:
                                                    It is 600Vac.


                                                     

                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Issue:​
                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Product Line:
                                                    Digest 177 Section 18 : Contactors and Starters, IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                    Voltage
                                                    3500m x 0.90
                                                    4000m x 0.80
                                                    4500m x 0.70
                                                    5000m x 0.60

                                                    Current
                                                    3500m x 0.92
                                                    4000m x 0.90
                                                    4500m x 0.88
                                                    5000m x 0.86

                                                    For example, an LC1D80 at 5000 meters:
                                                    - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                    - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                     

                                                    What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                    Issue:
                                                    Identifying power terminal lug data for the D2 style contactors

                                                    Product Line:
                                                    Tesys D line contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Power terminal lug data required

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                    stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                    solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                    What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                    Issue:
                                                    Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                    Product Line:
                                                    IEC Contactors and Starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Replacement coil is needed

                                                    Resolution:
                                                    DC replacement coils are not available.
                                                    AC Coils are 50/60 hertz for voltages as listed below:

                                                    Volts - Part Number
                                                    12 ____ LXD1J7
                                                    21 ____ LXD1Z7
                                                    24 ____ LXD1B7
                                                    32 ____ LXD1C7
                                                    36 ____ LXD1CC7
                                                    42 ____ LXD1D7
                                                    48 ____ LXD1E7
                                                    60 ____ LXD1EE7
                                                    100 ___ LXD1K7 ( never brought to North America )
                                                    110 ___ LXD1F7
                                                    115 ___ LXD1FE7
                                                    120 ___ LXD1G7
                                                    127 ___ LXD1FC7
                                                    200 ___ LXD1L7
                                                    208 ___ LXD1LE7
                                                    220 ___ LXD1M7
                                                    230 ___ LXD1P7
                                                    240 ___ LXD1U7
                                                    277 ___ LXD1W7
                                                    380 ___ LXD1Q7
                                                    400 ___ LXD1V7
                                                    415 ___ LXD1N7
                                                    440 ___ LXD1R7
                                                    480 ___ LXD1T7
                                                    575 ___ LXD1SC7
                                                    600 ___ LXD1X7
                                                    690 ___ LXD1Y7


                                                    Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                    What overload to suit LC1D95U7 need to be 80-104A

                                                     Part code for the overload LRD3365

                                                    what is the replacement for an LC1D2510 contactor with 240v coil ?

                                                    The replacement is an LC1D25U7

                                                    What is the code for a complete LC1D95 with a 415vAC Coil?

                                                       The code for the contactor is LC1D95N7

                                                    What is the code for the 240VAC Coil for the LC1D32 Contactor ?

                                                    Part Code = LXD1U7 
                                                    The LXD1U7 also fits the LC1D09 - D38 Contactors

                                                    Are the D-Line contactors rated to break DC voltages?

                                                    Issue: 
                                                    Can the TeSys D line be used to control DC loads? 

                                                    Product Line:
                                                    Tesys D contactors

                                                    Environment:
                                                    Products sold and used in the United States
                                                     
                                                    Cause:
                                                     DC power circuit
                                                     
                                                    Resolution:
                                                     
                                                    Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                    Devices are suitable but not UL Listed for DC applications.

                                                    More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                     

                                                    What is the part number for the overload that fits LC1D95U7 60-90 Amps?

                                                    The overload to suit is the LRD3365

                                                     

                                                    What is the replacement for the Tesys D Contactor LC1D65U7?

                                                    use the new code - LC1D65AU7
                                                    3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC
                                                    See link for Data Sheet:
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7

                                                    What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                    Issue:
                                                    Tesys D SCCR

                                                    Product Line:
                                                    Contactors and Overload Relays

                                                    Environment:
                                                    TeSys™ D Contactors and Overload Relays
                                                     
                                                    Resolution:
                                                    The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                    They are as follows:
                                                    Horsepower SCCR (A)

                                                    0 thru 1 1,000
                                                    1 thru 50 5,000
                                                    51 thru 200 10,000
                                                    201 thru 400 18,000
                                                    401 thru 600 30,000
                                                    601 thru 900 42,000
                                                    901 thru 1600 85,000
                                                    1601+ 100,000

                                                    What is the part number of the mechanical link for reversing contactors LC1D25U7

                                                    LAD9R1V

                                                    Will LA6DK20* mechanical latch block suit LC1D150* contactor?

                                                    Yes,  LA6DK20* mechanical latch block can be used with LC1D150* contactor. 
                                                    For further information, please visit https://www.schneider-electric.com/en/product/LA6DK20M/contactor-latch-block-iec/

                                                    What are the part numbers of contactors in LE3AC075N7*

                                                    Part no LE3AC075N7 consists  Two  of LC1D80U7 and one of LC1D50U7 contactors.

                                                    Are contactors LC1D09U7 and LC1D12U7 the same size?

                                                    Contactors LC1D09 , LC1D12 Aand LC1D18 are all exactly the same physical size with AC coils.
                                                    Height = 77mm
                                                    Width = 45mm
                                                    Depth = 86mm

                                                    LC1D6511 contactor with 220V coil - NZ equivalent?

                                                    LC1D65A contactor with a U7 240VAC coil is the closest.

                                                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                                    Issue:
                                                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                                    Product Line:
                                                    Digest 177 Section 18 : Contactors and Starters IEC

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Spacer required

                                                    Resolution:
                                                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.
                                                     

                                                    What replaces a LC1D18M7

                                                    Use the LC1D18U7

                                                    What replaces LC1D1801U5

                                                     Part code LC1D18U7

                                                    L1 VME What is the alternate part code for LC1DLKU7

                                                     The alternate part code is LC1DLK11U7

                                                    Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                                    Issue:
                                                    Can new accessories be used on older style contactors

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying product compatibility

                                                    Resolution:
                                                    Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                                     

                                                    What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                    Issue:
                                                    Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                    Product Line:
                                                    NEMA combination starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                    stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                    solid cable: One or Two #18-8 AWG per terminal.

                                                    What is the mechanical interlock for an LC1D32U7

                                                     The LAD9R1V reverser kit contains the mechanical interlock you need for the LC1D32U7

                                                    Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                                    Issue:
                                                    Auxiliary contact modules for the LC1D and LC2D contactors

                                                    Product Line: 
                                                    Contactor and Starters - IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                                    Front Mounting; maximum of 1 block per contactor:

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------1---------LADN11-----------LA1DN11
                                                    --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                                    --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                                    --2-----------0---------LADN20-----------LA1DN20
                                                    --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                                    --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                                    --0-----------2---------LADN02-----------LA1DN02
                                                    --2-----------2---------LADN22-----------LA1DN22
                                                    --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                                    --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                                    --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                                    --3-----------1---------LADN31------------LA1DN31
                                                    --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                                    --1-----------3---------LADN13------------LA1DN13
                                                    --4-----------0---------LADN40------------LA1DN40
                                                    --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                                    --0-----------4---------LADN04------------LA1DN04




                                                    Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------0--------LADN10----------LA1DN10
                                                    --0-----------1--------LADN01----------LA1DN01

                                                    Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                                    (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------1--------LAD8N11----------LA8DN11
                                                    --2-----------0--------LAD8N20----------LA8DN20
                                                    --0-----------2--------LAD8N02----------N/A

                                                    Footnotes:
                                                    {1} EN50 012 Machine Tool Terminal Markings
                                                    {2} (2) NO Sealed Dust Tight Contacts
                                                    {3} Gold Flash Contacts
                                                    {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                                    {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                                    {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                                    What is difference between LC1D50U7 and LC1D50AU7?

                                                    Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                                    LC1D50AU7 has everlink terminals.
                                                    LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                                    Whereas
                                                    LC1D50U7 contactors accommodate LRD33XX overloads.

                                                     

                                                    What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                                    Issue:
                                                    Identifying the difference between LAD4TB and LAD4TBDL

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying the difference between two similar part numbers

                                                    Resolution:
                                                    The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                                     

                                                    What is the part code for a 4P 2 N/O and 2 N/C 40Amp 240V ac coil contactor

                                                    Part code is LC1D258U7

                                                    Will the LC1D12U7 contactor go with the LADR2 timer?

                                                    Yes it will. the LADR2 timer slides on the top of the LC1D12U7 contactor.

                                                    What is the difference between the LC1D25E7 and LC1D258E7?

                                                    The LC1D25E7 is a 3 Poles 25 Amps (AC-3) Contactor

                                                    Where as

                                                    The LC1D258E7 is a 4 Pole (2NO + 2NC) 25 Amps (AC-3) Contactor

                                                    https://www.schneider-electric.com.au/en/search/LC1D25E7

                                                    What are the coil voltage codes for the LC1D115 / LC2D115 and LC1D150 / LC2D150 TeSys contactor?

                                                    Product Line:
                                                     
                                                    Tesys D line Contactors
                                                     
                                                    Resolution:
                                                     
                                                    The following list the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                                                    Note 1: LC1D150 contactors are only available with *7 coil codes.
                                                    Note 2: Coil Code ending number represents frequency rating as follows:
                                                    5 = 50 Hertz
                                                    6 = 60 Hertz
                                                    7 = 50/60 Hertz

                                                    AC Volts ___Code                DC Volts ___Code
                                                    24 ___ B5 or B6 or B7          12 ___ Not Avail.        
                                                    42 ___ D5 or D7                   24 ___ BD
                                                    48 ___ E5 or E6 or E7          36 ___ CD
                                                    110 ___ F5 or F6 or F7         48 ___ ED
                                                    115 ___ FE5 or FE7             60 ___ ND
                                                    120 ___ G6 or G7                72 ___ SD
                                                    127 ___ FC5 or FC7            110 ___ FD
                                                    208 ___ L6 or LE7               125 ___ GD
                                                    220 ___ M5 or M6 or M7       220 ___ MD
                                                    230 ___ P5 or P7                 250 ___ UD
                                                    240 ___ U5 or U6 or U7        440 ___ RD
                                                    277 ___ W6 or UE7                
                                                    380 ___ Q5 or Q6 or Q7                
                                                    400 ___ V5 or V7                
                                                    415 ___ N5 or N7                
                                                    440 ___ R5 or R6 or R7                
                                                    480 ___ T6 or T7                
                                                    500 ___ S5 or S7                


                                                     

                                                    What is the spare coil for LC1D09U7 contactor

                                                     The spare coil is LXD1U7

                                                    What is the replacement for a LC1D1810U5 contactor

                                                    The replacement is a LC1D18U7

                                                    What is the inrush current for the LC1D25B7 Contactor?

                                                    The inrush current of the LC1D25B7 will be 70VA..or 2.92 Amps
                                                    see technical data sheet on coil...
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lxd1b7
                                                     

                                                    What is the part number of the spare coil for LC1D25B7 contactor?

                                                    LXD1B7 is the part number of the spare coil to suit LC1D25B7 contactor. For further information on the coil, please refer to the attached datasheet.
                                                     

                                                    what coil voltage is the LC1D25N7 TeSys D?

                                                    it is 415v a.c.

                                                     

                                                    What is the mechanical durability of a LC1D12U7 contactor

                                                     It is 15 Million cycles

                                                    Need a LC2D323U7 reversing contactor

                                                    Use 2 x LC1D32U7 with a LAD9R1V reversing wiring kit

                                                    What is the part number for mechanical interlock for 2 x LC1D32U7 contactors?

                                                    The part number for a mechanical interlock for 2 x LC1D32U7 contactors is - LAD9V2

                                                    For further information , visit link below:-
                                                    https://www.schneider-electric.com.au/en/search/LAD9V2

                                                    What is the part number of a 23A -32A overload to fit LC1D40U7 contactor?

                                                    LRD3353 is a 23A -32A overload to fit LC1D40U7 contactor. 
                                                    For further information, please visit https://www.schneider-electric.com/en/product/LRD3353/tesys-lrd-thermal-overload-relays---23...32-a---class-10a



                                                     

                                                    LC1D1506 What are the dimensions? Weight?

                                                    Height 158 mm
                                                    Width 120 mm
                                                    Depth 136 mm
                                                    Product weight 2.5 kg

                                                    What is the part number for an overload for LC1D80U7 contactor , with 37-50amp range?

                                                    The part number for an overload for LC1D80U7 contactor , with 37-50amp range is - LRD3357

                                                    For further information , visit link below:-
                                                    https://www.schneider-electric.com.au/en/search/LRD3357
                                                     

                                                    What is the 240v coil to fit an LC1D1506

                                                     The 240v coil is an LX1D8U7

                                                    Can you get the lid only for LE1D35U7 DOL Starter?

                                                    Yes, But it comes as a complete empty enclosure, the code is DE1DS2.
                                                     

                                                    Is the LC1D18U7 available with only 1 AUX contact

                                                     Not available with 1AUX contact - All LC1D18U7 have 1 x NO + 1 NC contact built into them

                                                    What is the part code for the RC suppressor to fit a LC1D09U7

                                                     The part code is LAD4RCU

                                                    240VAC spare coil for LC1D18U7 Contactor?


                                                    Code = Lxd1u7

                                                    Will the LR3D325 overload relay fit a LC1D65G7 contactor?

                                                    Issue:
                                                    Will the LC1D65G7 mount to the LR3D325 overload relay?

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying product compatibility

                                                    Resolution:
                                                    No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


                                                    CTA-ID : 2050461

                                                    What is the rating of auxiliaries on standard LC1D12U7 contactor

                                                     Rated at 10A thermal.

                                                    What is the complete part number for a 25A 11Kw 3P Contactor with 24VDC coil?

                                                    LC1D25BD is the correct part number
                                                    Show More