Contactor

Product Dimensions

Width icon

Width85 mm

Height icon

Height127 mm

Depth icon

Depth186 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Warranty

18 months

Physical

[Ie] rated operational current

  • 95 A (at <60 °C) at <= 440 V AC-3 for power circuit
  • 125 A (at <60 °C) at <= 690 V AC-1 for power circuit
    • Mounting support

    • plate
    • rail
      • Connections - terminals

      • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²rigid
      • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²rigid
      • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
      • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
      • control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
      • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
      • power circuit: screw terminals 1 cable(s) 4-50 mm²rigid
      • power circuit: screw terminals 2 cable(s) 4-25 mm²rigid
      • power circuit: screw terminals 1 cable(s) 4-50 mm²flexible without cable end
      • power circuit: screw terminals 2 cable(s) 4-25 mm²flexible without cable end
      • power circuit: screw terminals 1 cable(s) 4-50 mm²flexible with cable end
      • power circuit: screw terminals 2 cable(s) 4-16 mm²flexible with cable end
        • [Ue] rated operational voltage

          power circuit: 1000 V AC 25...400 Hz

          Mechanical durability

          10 Mcycles

          Electrical durability

        • 1.2 Mcycles 95 A AC-3
        • 1.3 Mcycles 125 A AC-1
          • Insulation resistance

            > 10 MOhm for signalling circuit

            Height

            127 mm

            Width

            85 mm

            Depth

            186 mm

            Net weight

            2.61 kg

            Standards

          • EN/IEC 60947-1
          • EN/IEC 60947-4-1
          • EN/IEC 60947-5-1
          • GB/T 14048.4
            • Product certifications

            • IECEE CB Scheme
            • CCC
            • EAC
            • LROS (Lloyds register of shipping)
            • RINA
            • BV
            • DNV-GL
              • IP degree of protection

                IP20 conforming to IEC 60529

                Ambient air temperature for storage

                -60-80 °C

                EU RoHS Directive

                Pro-active compliance (Product out of EU RoHS legal scope)

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                X

                Others

                Device short name

                LC1D

                Contactor application

              • motor control
              • resistive load
                • Utilisation category

                • AC-1
                • AC-4
                • AC-3
                  • Control circuit type

                    DC wide range

                    Poles description

                    3P

                    Pole contact composition

                    3 NO

                    Motor power kW

                  • 25 kW at 220...230 V AC 50 Hz (AC-3)
                  • 45 kW at 380...400 V AC 50 Hz (AC-3)
                  • 45 kW at 415...440 V AC 50 Hz (AC-3)
                  • 55 kW at 500 V AC 50 Hz (AC-3)
                  • 45 kW at 660...690 V AC 50 Hz (AC-3)
                  • 45 kW at 1000 V AC 50 Hz (AC-3)
                    • Coil technology

                      without built-in suppressor module

                      Protective cover

                      with

                      Motor power hp

                    • 7.5 hp at 115 V AC 60 Hz for 1 phase motors
                    • 15 hp at 230/240 V AC 60 Hz for 1 phase motors
                    • 25 hp at 200/208 V AC 60 Hz for 3 phases motors
                    • 30 hp at 230/240 V AC 60 Hz for 3 phases motors
                    • 60 hp at 460/480 V AC 60 Hz for 3 phases motors
                    • 60 hp at 575/600 V AC 60 Hz for 3 phases motors
                      • Auxiliary contacts type

                      • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                      • type mirror contact 1 NC conforming to IEC 60947-4-1
                        • Auxiliary contact composition

                          1 NO + 1 NC

                          [Uc] control circuit voltage

                          110 V DC

                          Time constant

                          75 ms

                          [Ui] rated insulation voltage

                        • power circuit: 1000 V conforming to IEC 60947-1
                        • signalling circuit: 690 V conforming to IEC 60947-1
                          • [Uimp] rated impulse withstand voltage

                            8 kV conforming to IEC 60947

                            Overvoltage category

                            III

                            Flame retardance

                            V1 conforming to UL 94

                            Tightening torque

                          • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
                          • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver Philips No 2
                          • power circuit: 9 N.m - on screw terminal - with screwdriver flat Ø 6 to Ø 8 mm
                          • power circuit: 9 N.m - on screw terminal - with screwdriver hex (Allen key)4 mm
                            • [Ith] conventional free air thermal current

                            • 10 A (at 60 °C) for signalling circuit
                            • 125 A (at 60 °C) for power circuit
                              • Irms rated making capacity

                              • 1100 A at 440 V AC for power circuit conforming to IEC 60947
                              • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                              • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                                • Rated breaking capacity

                                  1100 A at 440 V for power circuit conforming to IEC 60947

                                  Permissible short-time rating

                                • 1100 A 40 °C 1 s for power circuit
                                • 800 A 40 °C 10 s for power circuit
                                • 400 A 40 °C 1 min for power circuit
                                • 135 A 40 °C 10 min for power circuit
                                • 140 A 100 ms for signalling circuit
                                • 120 A 500 ms for signalling circuit
                                • 100 A 1 s for signalling circuit
                                  • Associated fuse rating

                                  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                                  • 160 A gG at <= 690 V coordination type 2 for power circuit
                                  • 200 A gG at <= 690 V coordination type 1 for power circuit
                                    • Average impedance

                                      0.8 Ohm - Ith 125 A 50 Hz for power circuit

                                      Power dissipation per pole

                                    • 12.5 W AC-1
                                    • 7.2 W AC-3
                                      • Inrush power in W

                                        22-22 W (at 20 °C)

                                        Hold-in power consumption in W

                                        22-22 W at 20 °C

                                        Operating time

                                      • 20...35 ms opening
                                      • 95...130 ms closing
                                        • Safety reliability level

                                        • B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Maximum operating rate

                                            3600 cyc/h 60 °C

                                            Minimum switching current

                                            5 mA for signalling circuit

                                            Minimum switching voltage

                                            17 V for signalling circuit

                                            Non-overlap time

                                          • 1.5 ms on de-energisation between NC and NO contacts
                                          • 1.5 ms on energisation between NC and NO contacts
                                            • Contact compatibility

                                              M9

                                              Compatibility code

                                              LC1D

                                              Protective treatment

                                              TH (pollution degree 3) conforming to IEC 60068-2-30

                                              Operating altitude

                                              0...3000 m

                                              Fire resistance

                                              850 °C conforming to IEC 60695-2-1

                                              Shock resistance

                                            • 8 gn contactor opened
                                            • 10 gn contactor closed
                                              • Vibration resistance

                                              • 2 gn 5-300 Hz contactor opened
                                              • 3 gn 5-300 Hz contactor closed
                                                • Package 1 Weight

                                                  2.6 kg

                                                  Package 1 Height

                                                  2.1 dm

                                                  Package 1 width

                                                  1 dm

                                                  Package 1 Length

                                                  1.4 dm

                                                  WEEE

                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                  Show all specifications

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • CAD Files and Packs

                                                  • Product Brochures

                                                  • Technical Data Catalogues

                                                  • Installation Instruction

                                                  • Certificates (MSDS)

                                                  • Declaration of Conformity

                                                  Frequently Asked Questions

                                                  hide show

                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Issue:​
                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Product Line:
                                                  Digest 177 Section 18 : Contactors and Starters, IEC

                                                  Environment:
                                                  North American Products

                                                  Resolution:
                                                  The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                  Voltage
                                                  3500m x 0.90
                                                  4000m x 0.80
                                                  4500m x 0.70
                                                  5000m x 0.60

                                                  Current
                                                  3500m x 0.92
                                                  4000m x 0.90
                                                  4500m x 0.88
                                                  5000m x 0.86

                                                  For example, an LC1D80 at 5000 meters:
                                                  - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                  - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                   

                                                  What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                  Issue:
                                                  Identifying maximum voltage of an LC1D contactor

                                                  Product Line:
                                                  TeSys D Contactors

                                                  Environment:
                                                  IEC contactors and starters used in North America

                                                  Cause:
                                                  n/a

                                                  Resolution:
                                                  IThe maximum voltage per UL and CSA is 600VAC. 
                                                   

                                                  What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                  Issue:
                                                  Identifying power terminal lug data for the D2 style contactors

                                                  Product Line:
                                                  Tesys D line contactors

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Power terminal lug data required

                                                  Resolution:
                                                  For contactors with screw clamp terminals:
                                                  stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                  stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                  solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                  Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                  Issue:
                                                  Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                  Product Line: 
                                                  Tesys D Contactors

                                                  Environment:
                                                  IEC contactors

                                                  Resolution:
                                                  The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                   

                                                  Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                  Issue:
                                                  Mounting adaptor for GV2 and LC1D contactor

                                                  Product Line:
                                                  Motor Starters and Protectors

                                                  Environment:
                                                  TeSys GV Manual Starter and Protectors
                                                  Tesys D Contactors
                                                   
                                                  Resolution:
                                                  The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                  What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                  Issue:
                                                  Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                  Product Line:
                                                  IEC Contactors and Starters

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Replacement coil is needed

                                                  Resolution:
                                                  DC replacement coils are not available.
                                                  AC Coils are 50/60 hertz for voltages as listed below:

                                                  Volts - Part Number
                                                  12 ____ LXD1J7
                                                  21 ____ LXD1Z7
                                                  24 ____ LXD1B7
                                                  32 ____ LXD1C7
                                                  36 ____ LXD1CC7
                                                  42 ____ LXD1D7
                                                  48 ____ LXD1E7
                                                  60 ____ LXD1EE7
                                                  100 ___ LXD1K7 ( never brought to North America )
                                                  110 ___ LXD1F7
                                                  115 ___ LXD1FE7
                                                  120 ___ LXD1G7
                                                  127 ___ LXD1FC7
                                                  200 ___ LXD1L7
                                                  208 ___ LXD1LE7
                                                  220 ___ LXD1M7
                                                  230 ___ LXD1P7
                                                  240 ___ LXD1U7
                                                  277 ___ LXD1W7
                                                  380 ___ LXD1Q7
                                                  400 ___ LXD1V7
                                                  415 ___ LXD1N7
                                                  440 ___ LXD1R7
                                                  480 ___ LXD1T7
                                                  575 ___ LXD1SC7
                                                  600 ___ LXD1X7
                                                  690 ___ LXD1Y7


                                                  Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                  What is the code for a complete LC1D95 with a 415vAC Coil?

                                                     The code for the contactor is LC1D95N7

                                                  Are the D-Line contactors rated to break DC voltages?

                                                  Issue: 
                                                  Can the TeSys D line be used to control DC loads? 

                                                  Product Line:
                                                  Tesys D contactors

                                                  Environment:
                                                  Products sold and used in the United States
                                                   
                                                  Cause:
                                                   DC power circuit
                                                   
                                                  Resolution:
                                                   
                                                  Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                  Devices are suitable but not UL Listed for DC applications.

                                                  More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                   

                                                  What overload to suit LC1D95U7 need to be 80-104A

                                                   Part code for the overload LRD3365

                                                  What is the color scheme of the Tesys D-Line contactors?

                                                  Issue:
                                                  Looking for different color scheme of the Tesys D-Line contactors.

                                                  Product Line:
                                                  Tesys D Contactors

                                                  Environment:
                                                  LC1D contactors

                                                  Resolution:
                                                  Beige and dark gray.
                                                   

                                                  what is the replacement for an LC1D2510 contactor with 240v coil ?

                                                  The replacement is an LC1D25U7

                                                  What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                  Issue:
                                                  Tesys D SCCR

                                                  Product Line:
                                                  Contactors and Overload Relays

                                                  Environment:
                                                  TeSys™ D Contactors and Overload Relays
                                                   
                                                  Resolution:
                                                  The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                  They are as follows:
                                                  Horsepower SCCR (A)

                                                  0 thru 1 1,000
                                                  1 thru 50 5,000
                                                  51 thru 200 10,000
                                                  201 thru 400 18,000
                                                  401 thru 600 30,000
                                                  601 thru 900 42,000
                                                  901 thru 1600 85,000
                                                  1601+ 100,000
                                                  Show More