Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-3
    • AC-1
    • AC-4
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 300 V DC 25...400 Hz
      • power circuit: <= 1000 V AC
        • [Ie] rated operational current
        • 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
        • 95 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
          • Motor power kW
          • 45 kW at 415...440 V AC 50/60 Hz (AC-3)
          • 55 kW at 500 V AC 50/60 Hz (AC-3)
          • 45 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 45 kW at 1000 V AC 50/60 Hz (AC-3)
          • 15 kW at 400 V AC 50/60 Hz (AC-4)
          • 25 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 45 kW at 380...400 V AC 50/60 Hz (AC-3)
            • Motor power hp
            • 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 7.5 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 25 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                AC at 50/60 Hz
                [Uc] control circuit voltage
                110 V AC 50/60 Hz
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                8 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 125 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 1100 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    1100 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 1100 A 40 °C - 1 s for power circuit
                  • 135 A 40 °C - 10 min for power circuit
                  • 800 A 40 °C - 10 s for power circuit
                  • 400 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 200 A gG at <= 690 V coordination type 1 for power circuit
                    • 160 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        0.8 mOhm - Ith 125 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • power circuit: 1000 V conforming to IEC 60947-4-1
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                        • Electrical durability
                        • 1.2 Mcycles 95 A AC-3 at Ue <= 440 V
                        • 1.3 Mcycles 125 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 12.5 W AC-1
                          • 7.2 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • rail
                            • plate
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • BV
                                • RINA
                                • CCC
                                • GL
                                • LROS (Lloyds register of shipping)
                                • DNV
                                • GOST
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: connector 1 cable(s) 4-50 mm²flexible without cable end
                                  • power circuit: connector 2 cable(s) 4-25 mm²flexible without cable end
                                  • power circuit: connector 1 cable(s) 4-50 mm²flexible with cable end
                                  • power circuit: connector 2 cable(s) 4-16 mm²flexible with cable end
                                  • power circuit: connector 1 cable(s) 4-50 mm²solid without cable end
                                  • power circuit: connector 2 cable(s) 4-25 mm²solid without cable end
                                    • Tightening torque
                                    • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 9 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
                                    • power circuit: 9 N.m - on connector hexagonal screw head 4 mm
                                      • Operating time
                                      • 20...35 ms closing
                                      • 6...20 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            4 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            without built-in suppressor module
                                            Control circuit voltage limits
                                          • operational: 0.85...1.1 Uc AC 60 Hz (at 55 °C)
                                          • drop-out: 0.3...0.6 Uc AC 50/60 Hz (at 55 °C)
                                          • operational: 0.8...1.1 Uc AC 50 Hz (at 55 °C)
                                            • Inrush power in VA
                                            • 245-245 VA 60 Hz cos phi 0.75 (at 20 °C)
                                            • 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
                                              • Hold-in power consumption in VA
                                              • 26-26 VA 60 Hz cos phi 0.3 (at 20 °C)
                                              • 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
                                                • Heat dissipation
                                                  6-10 W at 50/60 Hz
                                                  Auxiliary contacts type
                                                • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                                • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                  • Signalling circuit frequency
                                                    25...400 Hz
                                                    Minimum switching current
                                                    5 mA for signalling circuit
                                                    Minimum switching voltage
                                                    17 V for signalling circuit
                                                    Non-overlap time
                                                  • 1.5 ms on de-energisation between NC and NO contact
                                                  • 1.5 ms on energisation between NC and NO contact
                                                    • Insulation resistance
                                                      > 10 MOhm for signalling circuit
                                                      Contact compatibility
                                                      M11
                                                      Compatibility code
                                                      LC1D
                                                      Power range
                                                    • 55-100 kW at 480-500 V 3 phases
                                                    • 15-25 kW at 200-240 V 3 phases
                                                    • 30-50 kW at 380-440 V 3 phases
                                                    • 30-50 kW at 480-500 V 3 phases
                                                      • Motor starter type
                                                        direct on-line contactor
                                                        Contactor coil voltage
                                                        110 V AC standard
                                                        IP degree of protection
                                                        IP20 front face conforming to IEC 60529
                                                        Protective treatment
                                                        TH conforming to IEC 60068-2-30
                                                        Pollution degree
                                                        3
                                                        Ambient air temperature for operation
                                                        -5-60 °C
                                                        Ambient air temperature for storage
                                                        -60-80 °C
                                                        Permissible ambient air temperature around the device
                                                        -40-70 °C at Uc
                                                        Operating altitude
                                                        3000 m without
                                                        Fire resistance
                                                        850 °C conforming to IEC 60695-2-1
                                                        Flame retardance
                                                        V1 conforming to UL 94
                                                        Mechanical robustness
                                                      • vibrations contactor open: 2 Gn, 5...300 Hz
                                                      • shocks contactor open: 8 Gn for 11 ms
                                                      • vibrations contactor closed: 3 Gn, 5...300 Hz
                                                      • shocks contactor closed: 10 Gn for 11 ms
                                                        • Height
                                                          127 mm
                                                          Width
                                                          85 mm
                                                          Depth
                                                          130 mm
                                                          Net weight
                                                          1.61 kg
                                                          Sustainable offer status
                                                          Green Premium product
                                                          REACh Regulation
                                                          Free of Substances of Very High Concern above the threshold
                                                          REACh free of SVHC
                                                          Yes
                                                          EU RoHS Directive
                                                          Compliant
                                                          Toxic heavy metal free
                                                          Yes
                                                          Mercury free
                                                          Yes
                                                          RoHS exemption information
                                                          Yes
                                                          China RoHS Regulation
                                                          X
                                                          Environmental Disclosure
                                                          ENVPEP110205EN
                                                          WEEE
                                                          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                          California proposition 65
                                                          WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                                          Warranty
                                                          18 months

                                                          Documents & downloads

                                                          hide show
                                                          Filter items
                                                          • All

                                                          • CAD Files and Packs

                                                          • Product Brochures

                                                          • Technical Data Catalogues

                                                          • Product Environmental

                                                          • Installation Instruction

                                                          • Data Bulletin

                                                          • Certificates (MSDS)

                                                          • eTechPub

                                                          • Declaration of Conformity

                                                          Frequently Asked Questions

                                                          hide show

                                                          What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                          Issue:
                                                          Identifying maximum power voltage of an LC1D contactor

                                                          Product Line:
                                                          Digest 177 Section 18: IEC Contactors

                                                          Environment:
                                                          Products sold and used in the United States

                                                          Cause:
                                                          Identifying ratings per UL and CSA

                                                          Resolution:
                                                          It is 600Vac.


                                                           

                                                          What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                          Issue:
                                                          Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                          Product Line:
                                                          IEC Contactors and Starters

                                                          Environment:
                                                          Products sold and used in the United States

                                                          Cause:
                                                          Replacement coil is needed

                                                          Resolution:
                                                          DC replacement coils are not available.
                                                          AC Coils are 50/60 hertz for voltages as listed below:

                                                          Volts - Part Number
                                                          12 ____ LXD1J7
                                                          21 ____ LXD1Z7
                                                          24 ____ LXD1B7
                                                          32 ____ LXD1C7
                                                          36 ____ LXD1CC7
                                                          42 ____ LXD1D7
                                                          48 ____ LXD1E7
                                                          60 ____ LXD1EE7
                                                          100 ___ LXD1K7 ( never brought to North America )
                                                          110 ___ LXD1F7
                                                          115 ___ LXD1FE7
                                                          120 ___ LXD1G7
                                                          127 ___ LXD1FC7
                                                          200 ___ LXD1L7
                                                          208 ___ LXD1LE7
                                                          220 ___ LXD1M7
                                                          230 ___ LXD1P7
                                                          240 ___ LXD1U7
                                                          277 ___ LXD1W7
                                                          380 ___ LXD1Q7
                                                          400 ___ LXD1V7
                                                          415 ___ LXD1N7
                                                          440 ___ LXD1R7
                                                          480 ___ LXD1T7
                                                          575 ___ LXD1SC7
                                                          600 ___ LXD1X7
                                                          690 ___ LXD1Y7


                                                          Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                          What is the altitude derating for a TeSys D-Line contactor?

                                                          Issue:​
                                                          What is the altitude derating for a TeSys D-Line contactor?

                                                          Product Line:
                                                          Digest 177 Section 18 : Contactors and Starters, IEC

                                                          Environment:
                                                          North American Products

                                                          Resolution:
                                                          The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                          Voltage
                                                          3500m x 0.90
                                                          4000m x 0.80
                                                          4500m x 0.70
                                                          5000m x 0.60

                                                          Current
                                                          3500m x 0.92
                                                          4000m x 0.90
                                                          4500m x 0.88
                                                          5000m x 0.86

                                                          For example, an LC1D80 at 5000 meters:
                                                          - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                          - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                           

                                                          What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                          Issue:
                                                          Identifying power terminal lug data for the D2 style contactors

                                                          Product Line:
                                                          Tesys D line contactors

                                                          Environment:
                                                          Products sold and used in the United States

                                                          Cause:
                                                          Power terminal lug data required

                                                          Resolution:
                                                          For contactors with screw clamp terminals:
                                                          stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                          stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                          solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                          What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                          Issue:
                                                          Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                          Product Line:
                                                          NEMA combination starters

                                                          Environment:
                                                          Products sold and used in the United States

                                                          Resolution:
                                                          For contactors with screw clamp terminals:
                                                          stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                          stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                          solid cable: One or Two #18-8 AWG per terminal.

                                                          What is the heat dissipated by the LC1D09 contactor?

                                                          Issue:
                                                          Contactors dissipate heat

                                                          Product Line:
                                                          Tesys D Contactors

                                                          Environment:
                                                          IEC Contactors and Starters

                                                          Resolution:
                                                          Total heat dissipation is 3.60 watts maximum; .20 watts dissipated across each power pole and 2 to 3 watts dissipated by the AC control coil.


                                                           

                                                          What is the code for a complete LC1D95 with a 415vAC Coil?

                                                             The code for the contactor is LC1D95N7

                                                          What overload to suit LC1D95U7 need to be 80-104A

                                                           Part code for the overload LRD3365

                                                          what is the replacement for an LC1D2510 contactor with 240v coil ?

                                                          The replacement is an LC1D25U7

                                                          What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                                          Issue:
                                                          Identifying the difference between LAD4TB and LAD4TBDL

                                                          Product Line:
                                                          IEC contactors and starters

                                                          Environment:
                                                          Products sold and used in the United States

                                                          Cause:
                                                          Identifying the difference between two similar part numbers

                                                          Resolution:
                                                          The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                                           

                                                          What is the difference between the LC1D25E7 and LC1D258E7?

                                                          The LC1D25E7 is a 3 Poles 25 Amps (AC-3) Contactor

                                                          Where as

                                                          The LC1D258E7 is a 4 Pole (2NO + 2NC) 25 Amps (AC-3) Contactor

                                                          https://www.schneider-electric.com.au/en/search/LC1D25E7

                                                          What is the code for the 240VAC Coil for the LC1D32 Contactor ?

                                                          Part Code = LXD1U7 
                                                          The LXD1U7 also fits the LC1D09 - D38 Contactors

                                                          What replaces a LC1D18M7

                                                          Use the LC1D18U7

                                                          Are the D-Line contactors rated to break DC voltages?

                                                          Issue: 
                                                          Can the TeSys D line be used to control DC loads? 

                                                          Product Line:
                                                          Tesys D contactors

                                                          Environment:
                                                          Products sold and used in the United States
                                                           
                                                          Cause:
                                                           DC power circuit
                                                           
                                                          Resolution:
                                                           
                                                          Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                          Devices are suitable but not UL Listed for DC applications.

                                                          More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                           

                                                          What is the part number for the overload that fits LC1D95U7 60-90 Amps?

                                                          The overload to suit is the LRD3365

                                                           

                                                          What is the replacement for the Tesys D Contactor LC1D65U7?

                                                          use the new code - LC1D65AU7
                                                          3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC
                                                          See link for Data Sheet:
                                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7

                                                          What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                          Issue:
                                                          Tesys D SCCR

                                                          Product Line:
                                                          Contactors and Overload Relays

                                                          Environment:
                                                          TeSys™ D Contactors and Overload Relays
                                                           
                                                          Resolution:
                                                          The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                          They are as follows:
                                                          Horsepower SCCR (A)

                                                          0 thru 1 1,000
                                                          1 thru 50 5,000
                                                          51 thru 200 10,000
                                                          201 thru 400 18,000
                                                          401 thru 600 30,000
                                                          601 thru 900 42,000
                                                          901 thru 1600 85,000
                                                          1601+ 100,000

                                                          What is the inrush current for the LC1D25B7 Contactor?

                                                          The inrush current of the LC1D25B7 will be 70VA..or 2.92 Amps
                                                          see technical data sheet on coil...
                                                          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lxd1b7
                                                           

                                                          What is the part number of the spare coil for LC1D25B7 contactor?

                                                          LXD1B7 is the part number of the spare coil to suit LC1D25B7 contactor. For further information on the coil, please refer to the attached datasheet.
                                                           

                                                          what coil voltage is the LC1D25N7 TeSys D?

                                                          it is 415v a.c.

                                                           

                                                          Will a LC1D12F7 operate on 60V DC as a control voltage

                                                          No it will not

                                                          What is the part number of the mechanical link for reversing contactors LC1D25U7

                                                          LAD9R1V

                                                          What is the Mechanical Interlock for the LC1D12F7 ?

                                                          LAD9R1V Is the code for the Mechanical and Electrical Interlock kit.

                                                          Will LA6DK20* mechanical latch block suit LC1D150* contactor?

                                                          Yes,  LA6DK20* mechanical latch block can be used with LC1D150* contactor. 
                                                          For further information, please visit https://www.schneider-electric.com/en/product/LA6DK20M/contactor-latch-block-iec/

                                                          Will the LR3D325 overload relay fit a LC1D65G7 contactor?

                                                          Issue:
                                                          Will the LC1D65G7 mount to the LR3D325 overload relay?

                                                          Product Line:
                                                          IEC contactors and starters

                                                          Environment:
                                                          Products sold and used in the United States

                                                          Cause:
                                                          Identifying product compatibility

                                                          Resolution:
                                                          No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


                                                          CTA-ID : 2050461

                                                          What are the part numbers of contactors in LE3AC075N7*

                                                          Part no LE3AC075N7 consists  Two  of LC1D80U7 and one of LC1D50U7 contactors.

                                                          Are contactors LC1D09U7 and LC1D12U7 the same size?

                                                          Contactors LC1D09 , LC1D12 Aand LC1D18 are all exactly the same physical size with AC coils.
                                                          Height = 77mm
                                                          Width = 45mm
                                                          Depth = 86mm

                                                          LC1D6511 contactor with 220V coil - NZ equivalent?

                                                          LC1D65A contactor with a U7 240VAC coil is the closest.

                                                          What replaces LC1D1801U5

                                                           Part code LC1D18U7

                                                          L1 VME What is the alternate part code for LC1DLKU7

                                                           The alternate part code is LC1DLK11U7

                                                          What is the code for a 40A 110VAC contactor ?

                                                          LC1D40AF7

                                                          What is the code for a 24vac coil to suit LC1D18B7 Contactor ?

                                                          24V AC Coil =  LXD1B7

                                                          What is the mechanical interlock for an LC1D32U7

                                                           The LAD9R1V reverser kit contains the mechanical interlock you need for the LC1D32U7

                                                          What is the Coil control circuit voltage limit for the LC1D32D7 Contactor?

                                                          The control circuit voltage limit for the 42V AC Coil on the LC1D32D7 Contactor is 0.8...1.1 Uc (0.8...1.1 x 42V AC) operational at 60 °C, AC 50 Hz

                                                          https://www.schneider-electric.com.au/en/search/LC1D32D7

                                                          What is difference between LC1D50U7 and LC1D50AU7?

                                                          Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                                          LC1D50AU7 has everlink terminals.
                                                          LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                                          Whereas
                                                          LC1D50U7 contactors accommodate LRD33XX overloads.

                                                           

                                                          What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                                          Issue:
                                                          Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                                          Product Line:
                                                          Digest 177 Section 18 : Contactors and Starters IEC

                                                          Environment:
                                                          Products sold and used in the United States

                                                          Cause:
                                                          Spacer required

                                                          Resolution:
                                                          Compensation plate catalog number GV1F03, requires 2 pieces snap together.
                                                           

                                                          Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                                          Issue:
                                                          Can new accessories be used on older style contactors

                                                          Product Line:
                                                          IEC contactors and starters

                                                          Environment:
                                                          Products sold and used in the United States

                                                          Cause:
                                                          Identifying product compatibility

                                                          Resolution:
                                                          Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                                           

                                                          What is the part code for a 4P 2 N/O and 2 N/C 40Amp 240V ac coil contactor

                                                          Part code is LC1D258U7

                                                          Will the LC1D12U7 contactor go with the LADR2 timer?

                                                          Yes it will. the LADR2 timer slides on the top of the LC1D12U7 contactor.

                                                          Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                                          Issue:
                                                          Auxiliary contact modules for the LC1D and LC2D contactors

                                                          Product Line: 
                                                          Contactor and Starters - IEC

                                                          Environment:
                                                          North American Products

                                                          Resolution:
                                                          Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                                          Front Mounting; maximum of 1 block per contactor:

                                                          N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                          --1-----------1---------LADN11-----------LA1DN11
                                                          --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                                          --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                                          --2-----------0---------LADN20-----------LA1DN20
                                                          --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                                          --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                                          --0-----------2---------LADN02-----------LA1DN02
                                                          --2-----------2---------LADN22-----------LA1DN22
                                                          --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                                          --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                                          --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                                          --3-----------1---------LADN31------------LA1DN31
                                                          --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                                          --1-----------3---------LADN13------------LA1DN13
                                                          --4-----------0---------LADN40------------LA1DN40
                                                          --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                                          --0-----------4---------LADN04------------LA1DN04




                                                          Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                                          N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                          --1-----------0--------LADN10----------LA1DN10
                                                          --0-----------1--------LADN01----------LA1DN01

                                                          Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                                          (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                                          N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                          --1-----------1--------LAD8N11----------LA8DN11
                                                          --2-----------0--------LAD8N20----------LA8DN20
                                                          --0-----------2--------LAD8N02----------N/A

                                                          Footnotes:
                                                          {1} EN50 012 Machine Tool Terminal Markings
                                                          {2} (2) NO Sealed Dust Tight Contacts
                                                          {3} Gold Flash Contacts
                                                          {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                                          {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                                          {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                                          What is the spare coil for LC1D09U7 contactor

                                                           The spare coil is LXD1U7

                                                          What is the replacement for a LC1D1810U5 contactor

                                                          The replacement is a LC1D18U7

                                                          What is the mechanical durability of a LC1D12U7 contactor

                                                           It is 15 Million cycles

                                                          Need a LC2D323U7 reversing contactor

                                                          Use 2 x LC1D32U7 with a LAD9R1V reversing wiring kit

                                                          What is the code for a spare coil for LC1D32B7

                                                          LXD1B7

                                                          What is the code for a 32Amp 24VAC 3 Pole Contactor ?

                                                          LC1D32B7

                                                          What is the part number for mechanical interlock for 2 x LC1D32U7 contactors?

                                                          The part number for a mechanical interlock for 2 x LC1D32U7 contactors is - LAD9V2

                                                          For further information , visit link below:-
                                                          https://www.schneider-electric.com.au/en/search/LAD9V2

                                                          Is there a contactor 80A 3p which will operate on 42V AC

                                                           There is - part code LC1D80E7

                                                          What is the 110V DC coil to fit a Telemechanique contactor 3P 32Amp

                                                           The part code is LC1D32FD

                                                          What is the part number of a 23A -32A overload to fit LC1D40U7 contactor?

                                                          LRD3353 is a 23A -32A overload to fit LC1D40U7 contactor. 
                                                          For further information, please visit https://www.schneider-electric.com/en/product/LRD3353/tesys-lrd-thermal-overload-relays---23...32-a---class-10a



                                                           
                                                          Show More