hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor
Device short name
LC1D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-2
    • AC-3
    • AC-1
    • AC-4
      • Control circuit type
        DC wide range
        Poles description
        3P
        Pole contact composition
        3 NO
        [Ie] rated operational current
      • 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      • 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
        • Motor power kW
        • 37 kW at 380...400 V AC 50 Hz
        • 55 kW at 500 V AC 50 Hz
        • 45 kW at 660...690 V AC 50 Hz
        • 22 kW at 220...230 V AC 50 Hz
        • 45 kW at 415...440 V AC 50 Hz
        • 45 kW at 1000 V AC 50 Hz
          • Coil technology
            built-in bidirectional peak limiting diode suppressor
            Protective cover
            with
            Motor power hp
          • 7.5 hp at 115 V AC 60 Hz for 1 phase motors
          • 15 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 25 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 30 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 60 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 60 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Auxiliary contacts type
            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
            • type mirror contact 1 NC conforming to IEC 60947-4-1
              • Auxiliary contact composition
                1 NO + 1 NC
                [Uc] control circuit voltage
                12 V DC
                Control circuit voltage limits
              • operational: 0.75...1.2 Uc (at <55 °C)
              • drop-out: 0.1...0.3 Uc (at <55 °C)
                • Time constant
                  75 ms
                  [Ui] rated insulation voltage
                • control circuit: 600 V CSA certified
                • control circuit: 600 V UL certified
                • power circuit: 600 V CSA certified
                • power circuit: 600 V UL certified
                • control circuit: 690 V conforming to IEC 60947-1
                • power circuit: 1000 V conforming to IEC 60947-1
                  • [Uimp] rated impulse withstand voltage
                    8 kV conforming to IEC 60947
                    Overvoltage category
                    III
                    Mounting support
                  • rail
                  • plate
                    • Flame retardance
                      V1 conforming to UL 94
                      Connections - terminals
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²rigid
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²rigid
                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                    • control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                    • power circuit: screw terminals 1 cable(s) 4-50 mm²rigid
                    • power circuit: screw terminals 2 cable(s) 4-25 mm²rigid
                    • power circuit: screw terminals 1 cable(s) 4-50 mm²flexible without cable end
                    • power circuit: screw terminals 2 cable(s) 4-25 mm²flexible without cable end
                    • power circuit: screw terminals 1 cable(s) 4-50 mm²flexible with cable end
                    • power circuit: screw terminals 2 cable(s) 4-16 mm²flexible with cable end
                      • Tightening torque
                      • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
                      • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver Philips No 2
                      • power circuit: 9 N.m - on screw terminal - with screwdriver flat Ø 6 to Ø 8 mm
                      • power circuit: 9 N.m - on screw terminal - with screwdriver hex (Allen key)4 mm
                        • [Ue] rated operational voltage
                          power circuit: <= 1000 V AC 25...400 Hz
                          [Ith] conventional free air thermal current
                        • 10 A (at 60 °C) for control circuit
                        • 125 A (at 60 °C) for power circuit
                          • Irms rated making capacity
                          • 250 A DC for control circuit conforming to IEC 60947-5-1
                          • 1100 A at 440 V for power circuit conforming to IEC 60947
                            • Rated breaking capacity
                              1100 A at 440 V for power circuit conforming to IEC 60947
                              Associated fuse rating
                            • 10 A gG for control circuit conforming to IEC 60947-5-1
                            • 160 A gG at <= 690 V coordination type 2 for power circuit
                            • 200 A gG at <= 690 V coordination type 1 for power circuit
                              • Power dissipation per pole
                              • 5.1 W AC-3
                              • 12.5 W AC-1
                                • Inrush power in W
                                  22-22 W (at 20 °C)
                                  Hold-in power consumption in W
                                  22-22 W at 20 °C
                                  Operating time
                                • 20...35 ms opening
                                • 95...130 ms closing
                                  • Safety reliability level
                                  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                    • Mechanical durability
                                      10000000 cycles
                                      Maximum operating rate
                                      3600 cyc/h 60 °C
                                      Minimum switching current
                                      5 mA for control circuit
                                      Minimum switching voltage
                                      17 V for control circuit
                                      Non-overlap time
                                    • 1.5 ms on de-energisation between NC and NO contacts
                                    • 1.5 ms on energisation between NC and NO contacts
                                      • Insulation resistance
                                        > 10 MOhm for control circuit
                                        Height
                                        127 mm
                                        Width
                                        85 mm
                                        Depth
                                        186 mm
                                        Net weight
                                        2.59 kg
                                        Compatibility code
                                        LC1D
                                        Standards
                                      • EN 60947-5-1
                                      • CSA C22.2 No 14
                                      • EN 60947-4-1
                                      • IEC 60947-5-1
                                      • UL 508
                                      • IEC 60947-4-1
                                        • Product certifications
                                        • GL
                                        • RINA
                                        • BV
                                        • CSA
                                        • CCC
                                        • DNV
                                        • UL
                                        • GOST
                                        • LROS (Lloyds register of shipping)
                                          • IP degree of protection
                                          • IP2x conforming to IEC 60529
                                          • IP2x conforming to VDE 0106
                                            • Ambient air temperature for operation
                                              -5-60 °C
                                              Ambient air temperature for storage
                                              -60-80 °C
                                              Permissible ambient air temperature around the device
                                              -40-70 °C at Uc
                                              Operating altitude
                                              3000 m without
                                              Fire resistance
                                              850 °C conforming to IEC 60695-2-1
                                              Shock resistance
                                            • 8 gn contactor opened
                                            • 10 gn contactor closed
                                              • Vibration resistance
                                              • 2 gn 5-300 Hz contactor opened
                                              • 3 gn 5-300 Hz contactor closed
                                                • Warranty
                                                  18 months

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • CAD Files and Packs

                                                  • Technical Data Catalogues

                                                  • Technical Leaflet

                                                  • Product Environmental

                                                  • Certificates (MSDS)

                                                  • Declaration of Conformity