TeSys D Contactor, 3P, 80A, AC-3, <= 440V, Aux 1NO+1NC, 24V 50Hz Coil

TeSys D Contactor, 3P, 80A, AC-3, <= 440V, Aux 1NO+1NC, 24V 50Hz Coil

TeSys D Contactor, 3P, 80A, AC-3, <= 440V, Aux 1NO+1NC, 24V 50Hz Coil

Item Number: LC1D80B5

Retail
$2,286.30
RRP (Inc. GST)

Product Dimensions

Width icon

Width85 mm

Height icon

Height127 mm

Depth icon

Depth130 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 1000 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

    • 80 A (at <60 °C) at <= 440 V AC-3 for power circuit
    • 125 A (at <60 °C) at <= 440 V AC-1 for power circuit
      • Electrical durability

      • 1.5 Mcycles 80 A AC-3 at Ue <= 440 V
      • 0.8 Mcycles 125 A AC-1 at Ue <= 440 V
        • Mounting support

        • rail
        • plate
          • Standards

          • EN/IEC 60947-4-1
          • EN/IEC 60947-5-1
          • UL 60947-4-1
          • CSA C22.2 No 60947-4-1
            • Product certifications

            • UL
            • CSA
            • CCC
            • EAC
            • LROS (Lloyds register of shipping)
            • DNV-GL
            • RINA
            • BV
              • Connections - terminals

              • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
              • power circuit: connector 1 cable(s) 4-50 mm²flexible without cable end
              • power circuit: connector 2 cable(s) 4-25 mm²flexible without cable end
              • power circuit: connector 1 cable(s) 4-50 mm²flexible with cable end
              • power circuit: connector 2 cable(s) 4-16 mm²flexible with cable end
              • power circuit: connector 1 cable(s) 4-50 mm²solid without cable end
              • power circuit: connector 2 cable(s) 4-25 mm²solid without cable end
                • Mechanical durability

                  10 Mcycles

                  Insulation resistance

                  > 10 MOhm for signalling circuit

                  IP degree of protection

                  IP20 front face conforming to IEC 60529

                  Ambient air temperature for storage

                  -60-80 °C

                  Height

                  127 mm

                  Width

                  85 mm

                  Depth

                  130 mm

                  Net weight

                  1.59 kg

                  REACh free of SVHC

                  Yes

                  EU RoHS Directive

                  Compliant

                  Toxic heavy metal free

                  Yes

                  Mercury free

                  Yes

                  RoHS exemption information

                  Yes

                  China RoHS Regulation

                   Pro-active China RoHS declaration (out of China RoHS legal scope)

                  Environmental Disclosure

                  ENVPEP110205EN

                  Others

                  Product name

                  TeSys D

                  Device short name

                  LC1D

                  Contactor application

                • motor control
                • resistive load
                  • Utilisation category

                  • AC-1
                  • AC-3
                  • AC-4
                    • Poles description

                      3P

                      Pole contact composition

                      3 NO

                      Motor power kW

                    • 22 kW at 220...230 V AC 50 Hz (AC-3)
                    • 37 kW at 380...400 V AC 50 Hz (AC-3)
                    • 45 kW at 415...440 V AC 50 Hz (AC-3)
                    • 55 kW at 500 V AC 50 Hz (AC-3)
                    • 45 kW at 660...690 V AC 50 Hz (AC-3)
                    • 45 kW at 1000 V AC 50 Hz (AC-3)
                    • 15 kW at 400 V AC 50 Hz (AC-4)
                      • Motor power hp

                      • 7.5 hp at 115 V AC 60 Hz for 1 phase motors
                      • 15 hp at 230/240 V AC 60 Hz for 1 phase motors
                      • 20 hp at 200/208 V AC 60 Hz for 3 phases motors
                      • 25 hp at 230/240 V AC 60 Hz for 3 phases motors
                      • 60 hp at 460/480 V AC 60 Hz for 3 phases motors
                      • 60 hp at 575/600 V AC 60 Hz for 3 phases motors
                        • Control circuit type

                          AC at 50 Hz

                          [Uc] control circuit voltage

                          24 V AC 50 Hz

                          Auxiliary contact composition

                          1 NO + 1 NC

                          [Uimp] rated impulse withstand voltage

                          8 kV conforming to IEC 60947

                          Overvoltage category

                          III

                          [Ith] conventional free air thermal current

                        • 10 A (at 60 °C) for signalling circuit
                        • 125 A (at 60 °C) for power circuit
                          • Irms rated making capacity

                          • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                          • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                          • 1100 A at 440 V for power circuit conforming to IEC 60947
                            • Rated breaking capacity

                              1100 A at 440 V for power circuit conforming to IEC 60947

                              [Icw] rated short-time withstand current

                            • 135 A 40 °C - 10 min for power circuit
                            • 320 A 40 °C - 1 min for power circuit
                            • 640 A 40 °C - 10 s for power circuit
                            • 990 A 40 °C - 1 s for power circuit
                            • 100 A - 1 s for signalling circuit
                            • 120 A - 500 ms for signalling circuit
                            • 140 A - 100 ms for signalling circuit
                              • Associated fuse rating

                              • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                              • 200 A gG at <= 690 V coordination type 1 for power circuit
                              • 160 A gG at <= 690 V coordination type 2 for power circuit
                                • Average impedance

                                  0.8 mOhm - Ith 125 A 50 Hz for power circuit

                                  [Ui] rated insulation voltage

                                • power circuit: 1000 V conforming to IEC 60947-4-1
                                • power circuit: 600 V CSA certified
                                • power circuit: 600 V UL certified
                                • signalling circuit: 690 V conforming to IEC 60947-1
                                • signalling circuit: 600 V CSA certified
                                • signalling circuit: 600 V UL certified
                                  • Power dissipation per pole

                                  • 5.1 W AC-3
                                  • 12.5 W AC-1
                                    • Protective cover

                                      with

                                      Tightening torque

                                    • power circuit: 9 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
                                    • power circuit: 9 N.m - on connector hexagonal screw head 4 mm
                                    • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • Operating time

                                      • 20...35 ms closing
                                      • 6...20 ms opening
                                        • Safety reliability level

                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Maximum operating rate

                                            3600 cyc/h 60 °C

                                            Coil technology

                                            without built-in suppressor module

                                            Inrush power in VA

                                            200-200 VA 50 Hz cos phi 0.75 (at 20 °C)

                                            Hold-in power consumption in VA

                                            20-20 VA 50 Hz cos phi 0.3 (at 20 °C)

                                            Heat dissipation

                                            6-10 W at 50 Hz

                                            Auxiliary contacts type

                                          • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                          • type mirror contact 1 NC conforming to IEC 60947-4-1
                                            • Signalling circuit frequency

                                              25...400 Hz

                                              Minimum switching current

                                              5 mA for signalling circuit

                                              Minimum switching voltage

                                              17 V for signalling circuit

                                              Non-overlap time

                                            • 1.5 ms on de-energisation between NC and NO contact
                                            • 1.5 ms on energisation between NC and NO contact
                                              • Contact compatibility

                                                M12

                                                Compatibility code

                                                LC1D

                                                Protective treatment

                                                TH conforming to IEC 60068-2-30

                                                Pollution degree

                                                3

                                                Operating altitude

                                                3000 m without derating

                                                Fire resistance

                                                850 °C conforming to IEC 60695-2-1

                                                Flame retardance

                                                V1 conforming to UL 94

                                                Mechanical robustness

                                              • vibrations contactor open: 2 Gn, 5...300 Hz
                                              • shocks contactor open: 8 Gn for 11 ms
                                              • vibrations contactor closed: 3 Gn, 5...300 Hz
                                              • shocks contactor closed: 10 Gn for 11 ms
                                                • Unit Type of Package 1

                                                  PCE

                                                  Number of Units in Package 1

                                                  1

                                                  Package 1 Weight

                                                  1.56 kg

                                                  Package 1 Height

                                                  9.6 cm

                                                  Package 1 width

                                                  14 cm

                                                  Package 1 Length

                                                  14 cm

                                                  Unit Type of Package 2

                                                  S02

                                                  Number of Units in Package 2

                                                  6

                                                  Package 2 Weight

                                                  9.742 kg

                                                  Package 2 Height

                                                  15 cm

                                                  Package 2 width

                                                  30 cm

                                                  Package 2 Length

                                                  40 cm

                                                  WEEE

                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                  PVC free

                                                  Yes
                                                  Show all specifications

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • CAD Files and Packs

                                                  • Product Brochures

                                                  • Technical Data Catalogues

                                                  • Product Environmental

                                                  • Installation Instruction

                                                  • Data Bulletin

                                                  • Certificates (MSDS)

                                                  • Declaration of Conformity

                                                  Frequently Asked Questions

                                                  hide show

                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Issue:​
                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Product Line:
                                                  Digest 177 Section 18 : Contactors and Starters, IEC

                                                  Environment:
                                                  North American Products

                                                  Resolution:
                                                  The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                  Voltage
                                                  3500m x 0.90
                                                  4000m x 0.80
                                                  4500m x 0.70
                                                  5000m x 0.60

                                                  Current
                                                  3500m x 0.92
                                                  4000m x 0.90
                                                  4500m x 0.88
                                                  5000m x 0.86

                                                  For example, an LC1D80 at 5000 meters:
                                                  - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                  - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                   

                                                  What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                  Issue:
                                                  Identifying maximum voltage of an LC1D contactor

                                                  Product Line:
                                                  TeSys D Contactors

                                                  Environment:
                                                  IEC contactors and starters used in North America

                                                  Cause:
                                                  n/a

                                                  Resolution:
                                                  IThe maximum voltage per UL and CSA is 600VAC. 
                                                   

                                                  What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                  Issue:
                                                  Identifying power terminal lug data for the D2 style contactors

                                                  Product Line:
                                                  Tesys D line contactors

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Power terminal lug data required

                                                  Resolution:
                                                  For contactors with screw clamp terminals:
                                                  stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                  stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                  solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                  What replaces LC1D50BD

                                                  Replacement LC1D50ABD

                                                  Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                  Issue:
                                                  Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                  Product Line: 
                                                  Tesys D Contactors

                                                  Environment:
                                                  IEC contactors

                                                  Resolution:
                                                  The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                   

                                                  What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

                                                  Issue:
                                                  AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

                                                  Product Line:
                                                  Tesys D Replacement Parts

                                                  Environment:
                                                  TeSys™ D AC Coils

                                                  Resolution:

                                                  What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                                  Issue:
                                                  Identifying the difference between LAD4TB and LAD4TBDL

                                                  Product Line:
                                                  IEC contactors and starters

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Identifying the difference between two similar part numbers

                                                  Resolution:
                                                  The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                                   

                                                  Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                                  Issue:
                                                  Can new accessories be used on older style contactors

                                                  Product Line:
                                                  IEC contactors and starters

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Identifying product compatibility

                                                  Resolution:
                                                  Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                                   

                                                  Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                  Issue:
                                                  Mounting adaptor for GV2 and LC1D contactor

                                                  Product Line:
                                                  Motor Starters and Protectors

                                                  Environment:
                                                  TeSys GV Manual Starter and Protectors
                                                  Tesys D Contactors
                                                   
                                                  Resolution:
                                                  The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                  Are the D-Line contactors rated to break DC voltages?

                                                  Issue: 
                                                  Can the TeSys D line be used to control DC loads? 

                                                  Product Line:
                                                  Tesys D contactors

                                                  Environment:
                                                  Products sold and used in the United States
                                                   
                                                  Cause:
                                                   DC power circuit
                                                   
                                                  Resolution:
                                                   
                                                  Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                  Devices are suitable but not UL Listed for DC applications.

                                                  More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                   

                                                  What is the part number for the contactor that replaces the LC1D50E5?

                                                  The part number for the contactor that replaces the LC1D50E5 is - LC1D50AE7

                                                  For further information , visit link below:-
                                                  https://www.schneider-electric.com.au/en/search/LC1D50AE7
                                                   

                                                  What are the part numbers of contactors in LE3AC075N7*

                                                  Part no LE3AC075N7 consists  Two  of LC1D80U7 and one of LC1D50U7 contactors.
                                                  Show More