TeSys LC1D contactor, 3 poles, power connections by EverLink, with cover, 40A to 65A

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 65A, 690VAC, 50/60 Hz Coil

Catalogue Number: LC1D65AY7
TeSys LC1D contactor, 3 poles, power connections by EverLink, with cover, 40A to 65A
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-4
    • AC-1
    • AC-3
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 690 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
        • 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
          • Motor power kW
          • 11 kW at 400 V AC 50/60 Hz (AC-4)
          • 18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 30 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 37 kW at 500 V AC 50/60 Hz (AC-3)
          • 37 kW at 660...690 V AC 50/60 Hz (AC-3)
            • Motor power hp
            • 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 5 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                AC at 50/60 Hz
                [Uc] control circuit voltage
                690 V AC 50/60 Hz
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 80 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 1000 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    1000 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 520 A 40 °C - 10 s for power circuit
                  • 900 A 40 °C - 1 s for power circuit
                  • 110 A 40 °C - 10 min for power circuit
                  • 260 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 125 A gG at <= 690 V coordination type 1 for power circuit
                    • 125 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        1.5 mOhm - Ith 80 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                      • power circuit: 690 V conforming to IEC 60947-4-1
                        • Electrical durability
                        • 1.4 Mcycles 80 A AC-1 at Ue <= 440 V
                        • 1.45 Mcycles 65 A AC-3 at Ue <= 440 V
                          • Power dissipation per pole
                          • 9.6 W AC-1
                          • 6.3 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • rail
                            • plate
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • UL
                                • CSA
                                • GOST
                                • CCC
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end
                                    • Tightening torque
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                    • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                      • Operating time
                                      • 4...19 ms opening
                                      • 12...26 ms closing
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            6 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            without built-in suppressor module
                                            Control circuit voltage limits
                                          • drop-out: 0.3...0.6 Uc AC 50/60 Hz (at 60 °C)
                                          • operational: 0.8...1.1 Uc AC 50 Hz (at 60 °C)
                                          • operational: 0.85...1.1 Uc AC 60 Hz (at 60 °C)
                                            • Inrush power in VA
                                            • 140-140 VA 60 Hz cos phi 0.75 (at 20 °C)
                                            • 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
                                              • Hold-in power consumption in VA
                                              • 13-13 VA 60 Hz cos phi 0.3 (at 20 °C)
                                              • 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
                                                • Heat dissipation
                                                  4-5 W at 50/60 Hz
                                                  Auxiliary contacts type
                                                • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                                • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                  • Signalling circuit frequency
                                                    25...400 Hz
                                                    Minimum switching current
                                                    5 mA for signalling circuit
                                                    Minimum switching voltage
                                                    17 V for signalling circuit
                                                    Non-overlap time
                                                  • 1.5 ms on de-energisation between NC and NO contact
                                                  • 1.5 ms on energisation between NC and NO contact
                                                    • Insulation resistance
                                                      > 10 MOhm for signalling circuit
                                                      Contact compatibility
                                                      M2
                                                      Compatibility code
                                                      LC1D
                                                      IP degree of protection
                                                      IP20 front face conforming to IEC 60529
                                                      Protective treatment
                                                      TH conforming to IEC 60068-2-30
                                                      Pollution degree
                                                      3
                                                      Ambient air temperature for operation
                                                      -5-60 °C
                                                      Ambient air temperature for storage
                                                      -60-80 °C
                                                      Permissible ambient air temperature around the device
                                                      -40-70 °C at Uc
                                                      Operating altitude
                                                      3000 m without
                                                      Fire resistance
                                                      850 °C conforming to IEC 60695-2-1
                                                      Flame retardance
                                                      V1 conforming to UL 94
                                                      Mechanical robustness
                                                    • vibrations contactor open: 2 Gn, 5...300 Hz
                                                    • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                    • shocks contactor closed: 15 Gn for 11 ms
                                                    • shocks contactor open: 10 Gn for 11 ms
                                                      • Height
                                                        122 mm
                                                        Width
                                                        55 mm
                                                        Depth
                                                        120 mm
                                                        Net weight
                                                        0.86 kg
                                                        Sustainable offer status
                                                        Green Premium product
                                                        REACh Regulation
                                                        Free of Substances of Very High Concern above the threshold
                                                        REACh free of SVHC
                                                        Yes
                                                        EU RoHS Directive
                                                        Compliant
                                                        Toxic heavy metal free
                                                        Yes
                                                        Mercury free
                                                        Yes
                                                        RoHS exemption information
                                                        Yes
                                                        China RoHS Regulation
                                                        X
                                                        Environmental Disclosure
                                                        ENVPEP1503009EN
                                                        Circularity Profile
                                                        ENVEOLI1503009EN
                                                        WEEE
                                                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                        California proposition 65
                                                        WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                                        Warranty
                                                        18 months

                                                        Documents & downloads

                                                        hide show
                                                        Filter items
                                                        • All

                                                        • Product Brochures

                                                        • Installation Instruction

                                                        • Data Bulletin

                                                        • Product Environmental

                                                        • End of Life Manual

                                                        • Certificates (MSDS)

                                                        • Declaration of Conformity

                                                        Frequently Asked Questions

                                                        hide show

                                                        What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                        Issue:
                                                        Identifying maximum power voltage of an LC1D contactor

                                                        Product Line:
                                                        Digest 177 Section 18: IEC Contactors

                                                        Environment:
                                                        Products sold and used in the United States

                                                        Cause:
                                                        Identifying ratings per UL and CSA

                                                        Resolution:
                                                        It is 600Vac.


                                                         

                                                        What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                        Issue:
                                                        Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                        Product Line:
                                                        IEC Contactors and Starters

                                                        Environment:
                                                        Products sold and used in the United States

                                                        Cause:
                                                        Replacement coil is needed

                                                        Resolution:
                                                        DC replacement coils are not available.
                                                        AC Coils are 50/60 hertz for voltages as listed below:

                                                        Volts - Part Number
                                                        12 ____ LXD1J7
                                                        21 ____ LXD1Z7
                                                        24 ____ LXD1B7
                                                        32 ____ LXD1C7
                                                        36 ____ LXD1CC7
                                                        42 ____ LXD1D7
                                                        48 ____ LXD1E7
                                                        60 ____ LXD1EE7
                                                        100 ___ LXD1K7 ( never brought to North America )
                                                        110 ___ LXD1F7
                                                        115 ___ LXD1FE7
                                                        120 ___ LXD1G7
                                                        127 ___ LXD1FC7
                                                        200 ___ LXD1L7
                                                        208 ___ LXD1LE7
                                                        220 ___ LXD1M7
                                                        230 ___ LXD1P7
                                                        240 ___ LXD1U7
                                                        277 ___ LXD1W7
                                                        380 ___ LXD1Q7
                                                        400 ___ LXD1V7
                                                        415 ___ LXD1N7
                                                        440 ___ LXD1R7
                                                        480 ___ LXD1T7
                                                        575 ___ LXD1SC7
                                                        600 ___ LXD1X7
                                                        690 ___ LXD1Y7


                                                        Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                        What is the altitude derating for a TeSys D-Line contactor?

                                                        Issue:​
                                                        What is the altitude derating for a TeSys D-Line contactor?

                                                        Product Line:
                                                        Digest 177 Section 18 : Contactors and Starters, IEC

                                                        Environment:
                                                        North American Products

                                                        Resolution:
                                                        The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                        Voltage
                                                        3500m x 0.90
                                                        4000m x 0.80
                                                        4500m x 0.70
                                                        5000m x 0.60

                                                        Current
                                                        3500m x 0.92
                                                        4000m x 0.90
                                                        4500m x 0.88
                                                        5000m x 0.86

                                                        For example, an LC1D80 at 5000 meters:
                                                        - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                        - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                         

                                                        What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                        Issue:
                                                        Identifying power terminal lug data for the D2 style contactors

                                                        Product Line:
                                                        Tesys D line contactors

                                                        Environment:
                                                        Products sold and used in the United States

                                                        Cause:
                                                        Power terminal lug data required

                                                        Resolution:
                                                        For contactors with screw clamp terminals:
                                                        stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                        stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                        solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                        What is the difference between a LC1D65A3U7 and LC1D65AU7?

                                                        The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                                                        see data sheets for comparrisons...
                                                        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                                                        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                                                        User-added image.................User-added image

                                                        What is the heat dissipated by the LC1D09 contactor?

                                                        Issue:
                                                        Contactors dissipate heat

                                                        Product Line:
                                                        Tesys D Contactors

                                                        Environment:
                                                        IEC Contactors and Starters

                                                        Resolution:
                                                        Total heat dissipation is 3.60 watts maximum; .20 watts dissipated across each power pole and 2 to 3 watts dissipated by the AC control coil.


                                                         

                                                        What is the replacement for the Tesys D Contactor LC1D65U7?

                                                        use the new code - LC1D65AU7
                                                        3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC
                                                        See link for Data Sheet:
                                                        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7

                                                        What is the replacement code for the LC1D633Q?

                                                        The new code for this is LC1D65AU7.

                                                        What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                        Issue:
                                                        Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                        Product Line:
                                                        NEMA combination starters

                                                        Environment:
                                                        Products sold and used in the United States

                                                        Resolution:
                                                        For contactors with screw clamp terminals:
                                                        stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                        stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                        solid cable: One or Two #18-8 AWG per terminal.

                                                        Does LC1D65AB7 3P (3 NO) TeSys Model D contactor have a normally opened and normally closed auxiliary contact?

                                                        What is the difference between the LC1D25E7 and LC1D258E7?

                                                        The LC1D25E7 is a 3 Poles 25 Amps (AC-3) Contactor

                                                        Where as

                                                        The LC1D258E7 is a 4 Pole (2NO + 2NC) 25 Amps (AC-3) Contactor

                                                        https://www.schneider-electric.com.au/en/search/LC1D25E7

                                                        What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                                                        17-25 Amps = LRD325
                                                        23-32 Amps =LRD332

                                                        What is difference between LC1D50U7 and LC1D50AU7?

                                                        Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                                        LC1D50AU7 has everlink terminals.
                                                        LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                                        Whereas
                                                        LC1D50U7 contactors accommodate LRD33XX overloads.

                                                         

                                                        LC1D6511 contactor with 220V coil - NZ equivalent?

                                                        LC1D65A contactor with a U7 240VAC coil is the closest.

                                                        Looking for a LC1D50A.. with a 240v coil

                                                         Part code is LC1D50AU7

                                                        What overload can be used with an LC1D65AU7?

                                                        You can use the Everlink range which is LRD313 - LRD365

                                                        What is the difference between the LC1D1506N7 and the LC1D150N7?

                                                        The LC1D1506N7 can accept 5X25mm Bars aswell as Lugs or ring terminals. The LC1D150N7 only accepts cable lugs upto 120mm2.

                                                        What is the part number for 60A contactor with 240V/415V coil?

                                                        Will the LR3D325 overload relay fit a LC1D65G7 contactor?

                                                        Issue:
                                                        Will the LC1D65G7 mount to the LR3D325 overload relay?

                                                        Product Line:
                                                        IEC contactors and starters

                                                        Environment:
                                                        Products sold and used in the United States

                                                        Cause:
                                                        Identifying product compatibility

                                                        Resolution:
                                                        No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


                                                        CTA-ID : 2050461

                                                        How many wires can you install on the Power poles for the LC1D65A contactor?

                                                         Issue:
                                                        How many wires can you install on the Power poles for the LC1D65A contactor?

                                                        Product line:
                                                        Tesys D, Everlink

                                                        Environment:
                                                        LC1D40A LC1D50A LC1D65A

                                                        Cause:
                                                        Documentation not found

                                                        Resolution:
                                                        The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase.  1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2. 

                                                        Instruction bulletin attached.

                                                        Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                                        Issue:
                                                        Can new accessories be used on older style contactors

                                                        Product Line:
                                                        IEC contactors and starters

                                                        Environment:
                                                        Products sold and used in the United States

                                                        Cause:
                                                        Identifying product compatibility

                                                        Resolution:
                                                        Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                                         

                                                        How Can the LC1D50AU7 Contactor be mounted?

                                                        Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                                                        See the attached datasheet for further information.

                                                        What is the code for a 40A 110VAC contactor ?

                                                        LC1D40AF7

                                                        What does the (3) designate in the part number LC1D123G7?

                                                        For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                                                        CTA-ID : 2053127

                                                        What is the Overload for LC1D50AU7 range is 37..50 Amps?

                                                        LRD350

                                                        What is the code for a 240VAC coil for the LC1D65A Contactor?

                                                        The LC1D65A is the Everlink contactor and the coil code is LXD3U7. 

                                                        The code for complete contactor + 240VAC coil is LC1D65AU7
                                                         

                                                        Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                                        No, correct kit is a LAD9R3.

                                                        Are the D-Line contactors rated to break DC voltages?

                                                        Issue: 
                                                        Can the TeSys D line be used to control DC loads? 

                                                        Product Line:
                                                        Tesys D contactors

                                                        Environment:
                                                        Products sold and used in the United States
                                                         
                                                        Cause:
                                                         DC power circuit
                                                         
                                                        Resolution:
                                                         
                                                        Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                        Devices are suitable but not UL Listed for DC applications.

                                                        More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                         

                                                        What is the part code for the contactor and overload that replaced the LR1D63359

                                                         The part codes are LC1D65A***  +  LRD365

                                                        What is the part code for a 4P 2 N/O and 2 N/C 40Amp 240V ac coil contactor

                                                        Part code is LC1D258U7

                                                        Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                                        Issue:
                                                        Auxiliary contact modules for the LC1D and LC2D contactors

                                                        Product Line: 
                                                        Contactor and Starters - IEC

                                                        Environment:
                                                        North American Products

                                                        Resolution:
                                                        Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                                        Front Mounting; maximum of 1 block per contactor:

                                                        N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                        --1-----------1---------LADN11-----------LA1DN11
                                                        --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                                        --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                                        --2-----------0---------LADN20-----------LA1DN20
                                                        --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                                        --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                                        --0-----------2---------LADN02-----------LA1DN02
                                                        --2-----------2---------LADN22-----------LA1DN22
                                                        --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                                        --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                                        --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                                        --3-----------1---------LADN31------------LA1DN31
                                                        --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                                        --1-----------3---------LADN13------------LA1DN13
                                                        --4-----------0---------LADN40------------LA1DN40
                                                        --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                                        --0-----------4---------LADN04------------LA1DN04




                                                        Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                                        N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                        --1-----------0--------LADN10----------LA1DN10
                                                        --0-----------1--------LADN01----------LA1DN01

                                                        Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                                        (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                                        N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                        --1-----------1--------LAD8N11----------LA8DN11
                                                        --2-----------0--------LAD8N20----------LA8DN20
                                                        --0-----------2--------LAD8N02----------N/A

                                                        Footnotes:
                                                        {1} EN50 012 Machine Tool Terminal Markings
                                                        {2} (2) NO Sealed Dust Tight Contacts
                                                        {3} Gold Flash Contacts
                                                        {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                                        {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                                        {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                                        What is the code for the newer version of the LC1D40U7

                                                        That has been replaced with the Everlink LC1D40AU7

                                                        What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                        Issue:
                                                        Tesys D SCCR

                                                        Product Line:
                                                        Contactors and Overload Relays

                                                        Environment:
                                                        TeSys™ D Contactors and Overload Relays
                                                         
                                                        Resolution:
                                                        The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                        They are as follows:
                                                        Horsepower SCCR (A)

                                                        0 thru 1 1,000
                                                        1 thru 50 5,000
                                                        51 thru 200 10,000
                                                        201 thru 400 18,000
                                                        401 thru 600 30,000
                                                        601 thru 900 42,000
                                                        901 thru 1600 85,000
                                                        1601+ 100,000

                                                        what is the replacement for an LC1D2510 contactor with 240v coil ?

                                                        The replacement is an LC1D25U7

                                                        What overload to suit LC1D95U7 need to be 80-104A

                                                         Part code for the overload LRD3365

                                                        Can our "D" contactors handle 480volts?

                                                        Our "D" Contactors LC1D09 - LC1D65A are rated to 690volts AC and the LC1D80 to LC1D150 are rated up to 1000VAC/ 690VDC.

                                                        What do the LA4D timing modules require for mounting on LC1D40A through LC1D65A contactors?

                                                        Product Line:
                                                         
                                                        Tesys D line Contactors and Accessories

                                                        Resolution:
                                                         
                                                        Mounting this module to TeSys LC1D40A through LC1D65A contactor requires the use of the LAD4BB3 wiring adaptor. This adaptor can be fitted only to contactors with no coil suppressor.
                                                         

                                                        What are the dimensions of LC1D40AB7 ?

                                                        Height 122 mm
                                                        Width 55 mm
                                                        Depth 120 mm
                                                        Product weight 1.4 kg

                                                        What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                                                        The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                                                        What is the inrush current for the LC1D25B7 Contactor?

                                                        The inrush current of the LC1D25B7 will be 70VA..or 2.92 Amps
                                                        see technical data sheet on coil...
                                                        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lxd1b7
                                                         

                                                        What is the part number of the spare coil for LC1D25B7 contactor?

                                                        LXD1B7 is the part number of the spare coil to suit LC1D25B7 contactor. For further information on the coil, please refer to the attached datasheet.
                                                         

                                                        what coil voltage is the LC1D25N7 TeSys D?

                                                        it is 415v a.c.

                                                         

                                                        What is the part number of the mechanical link for reversing contactors LC1D25U7

                                                        LAD9R1V

                                                        What mechanical interlock should I use with the LC1D50A••?

                                                        The mechanical interlock LAD4CM is the correct one for use with the LC1D50A••.

                                                        See attached datasheet for futher information on the LAD4CM.

                                                        What is the code for a complete LC1D95 with a 415vAC Coil?

                                                           The code for the contactor is LC1D95N7

                                                        What is the part number for overload 37-50A for LC1D50U7?

                                                        The part number for overload 37-50A for LC1D50U7 is LRD3357
                                                        LRD3357
                                                        TeSys LRD thermal overload relays - 37...50 A - class 10A

                                                        For more information see:
                                                        https://eshop.schneider-electric.com/product.aspx?prod_id=LRD3357&org=21&lang=1&dist=276&tab=10&ses_id
                                                         

                                                        What is the part number for the overload that fits LC1D95U7 60-90 Amps?

                                                        The overload to suit is the LRD3365

                                                         

                                                        What replaces LC1D50BD

                                                        Replacement LC1D50ABD

                                                        What are the part numbers of contactors in LE3AC075N7*

                                                        Part no LE3AC075N7 consists  Two  of LC1D80U7 and one of LC1D50U7 contactors.

                                                        What is the code for the 240VAC Coil for the LC1D32 Contactor ?

                                                        Part Code = LXD1U7 
                                                        The LXD1U7 also fits the LC1D09 - D38 Contactors
                                                        Show More