Quantcast

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 65A, 480VAC, 50/60 Hz Coil

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 65A, 480VAC, 50/60 Hz Coil

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 65A, 480VAC, 50/60 Hz Coil

Item Number: LC1D65AT7

Retail
$1,792.71
RRP (Inc. GST)

Product Dimensions

Width icon

Width55 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

    • 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
    • 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
      • Electrical durability

      • 1.4 Mcycles 80 A AC-1 at Ue <= 440 V
      • 1.45 Mcycles 65 A AC-3 at Ue <= 440 V
        • Mounting support

        • plate
        • rail
          • Standards

          • CSA C22.2 No 14
          • EN 60947-4-1
          • EN 60947-5-1
          • IEC 60947-4-1
          • IEC 60947-5-1
          • UL 508
            • Product certifications

            • CCC
            • GOST
            • UL
            • CSA
              • Connections - terminals

              • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
              • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
              • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
              • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
              • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
              • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end
              • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end
                • Mechanical durability

                  6 Mcycles

                  Insulation resistance

                  > 10 MOhm for signalling circuit

                  IP degree of protection

                  IP20 front face conforming to IEC 60529

                  Ambient air temperature for operation

                • -40-60 °C
                • 60-70 °C with derating
                  • Ambient air temperature for storage

                    -60-80 °C

                    Height

                    122 mm

                    Width

                    55 mm

                    Depth

                    120 mm

                    Net weight

                    0.86 kg

                    REACh Regulation

                    Free of Substances of Very High Concern above the threshold

                    REACh free of SVHC

                    Yes

                    EU RoHS Directive

                    Compliant

                    Toxic heavy metal free

                    Yes

                    Mercury free

                    Yes

                    RoHS exemption information

                    Yes

                    China RoHS Regulation

                     Pro-active China RoHS declaration (out of China RoHS legal scope)

                    Environmental Disclosure

                    ENVPEP1503009EN

                    Circularity Profile

                    ENVEOLI1503009EN

                    California proposition 65

                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

                    Others

                    Product name

                    TeSys D

                    Device short name

                    LC1D

                    Contactor application

                  • resistive load
                  • motor control
                    • Utilisation category

                    • AC-3
                    • AC-1
                    • AC-4
                      • Poles description

                        3P

                        Pole contact composition

                        3 NO

                        Motor power kW

                      • 11 kW at 400 V AC 50/60 Hz (AC-4)
                      • 18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
                      • 30 kW at 380...400 V AC 50/60 Hz (AC-3)
                      • 37 kW at 500 V AC 50/60 Hz (AC-3)
                      • 37 kW at 660...690 V AC 50/60 Hz (AC-3)
                        • Motor power hp

                        • 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
                        • 5 hp at 115 V AC 50/60 Hz for 1 phase motors
                        • 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
                        • 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
                        • 20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
                        • 50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
                          • Control circuit type

                            AC at 60 Hz

                            [Uc] control circuit voltage

                            480 V AC 60 Hz

                            Auxiliary contact composition

                            1 NO + 1 NC

                            [Uimp] rated impulse withstand voltage

                            6 kV conforming to IEC 60947

                            Overvoltage category

                            III

                            [Ith] conventional free air thermal current

                          • 10 A (at 60 °C) for signalling circuit
                          • 80 A (at 60 °C) for power circuit
                            • Irms rated making capacity

                            • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                            • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                            • 1000 A at 440 V for power circuit conforming to IEC 60947
                              • Rated breaking capacity

                                1000 A at 440 V for power circuit conforming to IEC 60947

                                [Icw] rated short-time withstand current

                              • 520 A 40 °C - 10 s for power circuit
                              • 900 A 40 °C - 1 s for power circuit
                              • 110 A 40 °C - 10 min for power circuit
                              • 260 A 40 °C - 1 min for power circuit
                              • 100 A - 1 s for signalling circuit
                              • 120 A - 500 ms for signalling circuit
                              • 140 A - 100 ms for signalling circuit
                                • Associated fuse rating

                                • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                                • 125 A gG at <= 690 V coordination type 1 for power circuit
                                • 125 A gG at <= 690 V coordination type 2 for power circuit
                                  • Average impedance

                                    1.5 mOhm - Ith 80 A 50 Hz for power circuit

                                    [Ui] rated insulation voltage

                                  • power circuit: 600 V CSA certified
                                  • power circuit: 600 V UL certified
                                  • signalling circuit: 690 V conforming to IEC 60947-1
                                  • signalling circuit: 600 V CSA certified
                                  • signalling circuit: 600 V UL certified
                                  • power circuit: 690 V conforming to IEC 60947-4-1
                                    • Power dissipation per pole

                                    • 9.6 W AC-1
                                    • 6.3 W AC-3
                                      • Protective cover

                                        with

                                        Tightening torque

                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                      • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                        • Operating time

                                        • 4...19 ms opening
                                        • 12...26 ms closing
                                          • Safety reliability level

                                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                            • Maximum operating rate

                                              3600 cyc/h 60 °C

                                              Coil technology

                                              without built-in suppressor module

                                              Control circuit voltage limits

                                            • 0.3...0.6 Uc (-40-70 °C):drop-out AC 60 Hz
                                            • 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
                                            • 1...1.1 Uc (60-70 °C):operational AC 60 Hz
                                              • Inrush power in VA

                                                140-140 VA 60 Hz cos phi 0.75 (at 20 °C)

                                                Hold-in power consumption in VA

                                                13-13 VA 60 Hz cos phi 0.3 (at 20 °C)

                                                Heat dissipation

                                                4-5 W at 60 Hz

                                                Auxiliary contacts type

                                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                • Signalling circuit frequency

                                                  25...400 Hz

                                                  Minimum switching current

                                                  5 mA for signalling circuit

                                                  Minimum switching voltage

                                                  17 V for signalling circuit

                                                  Non-overlap time

                                                • 1.5 ms on de-energisation between NC and NO contact
                                                • 1.5 ms on energisation between NC and NO contact
                                                  • Contact compatibility

                                                    M2

                                                    Compatibility code

                                                    LC1D

                                                    Protective treatment

                                                    TH conforming to IEC 60068-2-30

                                                    Pollution degree

                                                    3

                                                    Operating altitude

                                                    0...3000 m

                                                    Fire resistance

                                                    850 °C conforming to IEC 60695-2-1

                                                    Flame retardance

                                                    V1 conforming to UL 94

                                                    Mechanical robustness

                                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                  • shocks contactor closed: 15 Gn for 11 ms
                                                  • shocks contactor open: 10 Gn for 11 ms
                                                    • Package 1 Weight

                                                      0.941 kg

                                                      Package 1 Height

                                                      0.62 dm

                                                      Package 1 width

                                                      1.37 dm

                                                      Package 1 Length

                                                      1.52 dm

                                                      WEEE

                                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                      PVC free

                                                      Yes
                                                      Show all specifications

                                                      Documents & downloads

                                                      hide show
                                                      Filter items
                                                      • All

                                                      • CAD Files and Packs

                                                      • Product Brochures

                                                      • Technical Data Catalogues

                                                      • Installation Instruction

                                                      • End of Life Manual

                                                      • Product Environmental

                                                      • Data Bulletin

                                                      • Certificates (MSDS)

                                                      • Declaration of Conformity

                                                      Frequently Asked Questions

                                                      hide show

                                                      What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                                                      17-25 Amps = LRD325
                                                      23-32 Amps =LRD332

                                                      What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                      Issue:
                                                      Identifying power terminal lug data for the D2 style contactors

                                                      Product Line:
                                                      IEC Contactors and Starters

                                                      Environment:
                                                      Tesys D line contactors

                                                      Cause:
                                                      Power terminal lug data required

                                                      Resolution:
                                                      For contactors with screw clamp terminals:
                                                      stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                      stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                      solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                      What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                      Issue:
                                                      Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                      Product Line:
                                                      IEC Contactors and Starters

                                                      Environment:
                                                      Tesys D Contactors

                                                      Resolution:
                                                      For contactors with screw clamp terminals:
                                                      stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                      stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                      solid cable: One or Two #18-8 AWG per terminal.

                                                      What is the part code for the contactor and overload that replaced the LR1D63359

                                                       The part codes are LC1D65A**  +  LRD365
                                                      where ** refer to coil voltage.

                                                      What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                      Issue:
                                                      Identifying maximum voltage of an LC1D contactor

                                                      Product Line:
                                                      TeSys D Contactors

                                                      Environment:
                                                      IEC contactors and starters used in North America

                                                      Cause:
                                                      n/a

                                                      Resolution:
                                                      IThe maximum voltage per UL and CSA is 600VAC. 
                                                       

                                                      What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38?

                                                      Issue:
                                                      LC1D09 - LC1D38 Coil tolerance

                                                      Product Line:
                                                      Contactors and Starters, IEC

                                                      Environment:
                                                      Tesys D Contactors

                                                      Cause:
                                                      Needs the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38.

                                                      Resolution:
                                                      AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
                                                      AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
                                                      DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
                                                      DC standard coil for LP1D12 and D25: (-20% / +10%)
                                                      DC wide range coil for LP1D12 and D25 : (-30% to +25%)
                                                      Show More