TeSys D Contactor-3 Pole AC3 <= 440V 65A, 24 - 60V ACDC Coil

TeSys D Contactor-3 Pole AC3 <= 440V 65A, 24 - 60V ACDC Coil

TeSys D Contactor-3 Pole AC3 <= 440V 65A, 24 - 60V ACDC Coil

Item Number: LC1D65ABNE

Retail
$2,388.05
RRP (Inc. GST)

Product Dimensions

Width icon

Width55 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

  • 80 A (at <60 °C) at <= 440 V AC-1 for power circuit
  • 65 A (at <60 °C) at <= 440 V AC-3 for power circuit
    • Electrical durability

    • 1.8 Mcycles 57 A AC-3 at Ue <= 440 V
    • 0.5 Mcycles 80 A AC-1 at Ue <= 440 V
      • Mounting support

      • rail
      • plate
        • Standards

        • EN/IEC 60947-4-1
        • EN/IEC 60947-5-1
        • UL 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • CCC
          • CSA
          • EAC
          • UL
          • KC
          • DNV-GL
          • LROS (Lloyds register of shipping)
            • Connections - terminals

            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
              • Mechanical durability

                6 Mcycles

                Insulation resistance

                > 10 MOhm for signalling circuit

                IP degree of protection

                IP20 front face conforming to IEC 60529

                Ambient air temperature for storage

                -60-80 °C

                Height

                122 mm

                Width

                55 mm

                Depth

                120 mm

                Net weight

                1.002 kg

                EU RoHS Directive

                Compliant

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                Product out of China RoHS scope. Substance declaration for your information

                Environmental Disclosure

                ENVPEP1607010EN

                Circularity Profile

                ENVEOLI1607010EN

                Others

                Product name

                TeSys D Green

                Device short name

                LC1D

                Contactor application

              • motor control
              • resistive load
                • Utilisation category

                • AC-3
                • AC-1
                  • Poles description

                    3P

                    Pole contact composition

                    3 NO

                    Motor power kW

                  • 18.5 kW at 220...230 V AC 50 Hz (AC-3)
                  • 30 kW at 380...400 V AC 50 Hz (AC-3)
                  • 37 kW at 415 V AC 50 Hz (AC-3)
                  • 37 kW at 440 V AC 50 Hz (AC-3)
                  • 37 kW at 500 V AC 50 Hz (AC-3)
                  • 37 kW at 660...690 V AC 50 Hz (AC-3)
                    • Motor power hp

                    • 5 hp at 115 V AC 60 Hz for 1 phase motors
                    • 10 hp at 230/240 V AC 60 Hz for 1 phase motors
                    • 20 hp at 200/208 V AC 60 Hz for 3 phases motors
                    • 20 hp at 230/240 V AC 60 Hz for 3 phases motors
                    • 40 hp at 460/480 V AC 60 Hz for 3 phases motors
                    • 50 hp at 575/600 V AC 60 Hz for 3 phases motors
                      • Control circuit type

                        AC/DC at 50/60 Hz AC/DC electronic

                        [Uc] control circuit voltage

                      • 24...60 V AC 50/60 Hz
                      • 24...60 V DC
                        • Coil type

                          AC/DC electronic

                          Auxiliary contact composition

                          1 NO + 1 NC

                          [Uimp] rated impulse withstand voltage

                          6 kV conforming to IEC 60947

                          Overvoltage category

                          III

                          [Ith] conventional free air thermal current

                        • 80 A (at 60 °C) for power circuit
                        • 10 A (at 60 °C) for signalling circuit
                          • Irms rated making capacity

                          • 1000 A at 440 V for power circuit conforming to IEC 60947
                          • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                          • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                            • Rated breaking capacity

                              1000 A at 440 V for power circuit conforming to IEC 60947

                              [Icw] rated short-time withstand current

                            • 110 A 40 °C - 10 min for power circuit
                            • 260 A 40 °C - 1 min for power circuit
                            • 520 A 40 °C - 10 s for power circuit
                            • 900 A 40 °C - 1 s for power circuit
                            • 100 A - 1 s for signalling circuit
                            • 120 A - 500 ms for signalling circuit
                            • 140 A - 100 ms for signalling circuit
                              • Associated fuse rating

                              • 125 A gG at <= 690 V coordination type 1 for power circuit
                              • 125 A gG at <= 690 V coordination type 2 for power circuit
                              • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                                • Average impedance

                                  1.5 mOhm - Ith 80 A 50 Hz for power circuit

                                  [Ui] rated insulation voltage

                                • power circuit: 690 V conforming to IEC 60947-4-1
                                • signalling circuit: 690 V conforming to IEC 60947-1
                                  • Power dissipation per pole

                                  • 9.6 W AC-1
                                  • 6.3 W AC-3
                                    • Protective cover

                                      with

                                      Tightening torque

                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                    • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                      • Operating time

                                      • 55...65 ms closing
                                      • 20...120 ms opening (date code >= 17221)
                                      • 20...80 ms opening (date code >= 18011)
                                        • Safety reliability level

                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Maximum operating rate

                                            3600 cyc/h 60 °C

                                            Coil technology

                                            built-in bidirectional peak limiting

                                            Control circuit voltage limits

                                          • <= 0.1 Uc 60-60 °C drop-out
                                          • 0.8...1.2 Uc 60-60 °C operational DC

                                            Inrush power in VA

                                            15-15 VA 50/60 Hz (at 20 °C)
                                          • Inrush power in W

                                            16-16 W at 20 °C

                                            Hold-in power consumption in VA

                                            1-1 VA (at 20 °C) 50/60 Hz

                                            Hold-in power consumption in W

                                            0.7-0.7 W at 20 °C

                                            Heat dissipation

                                            0.7-0.7 W at 50/60 Hz

                                            Auxiliary contacts type

                                          • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                          • type mirror contact 1 NC conforming to IEC 60947-4-1
                                            • Signalling circuit frequency

                                              25...400 Hz

                                              Minimum switching current

                                              5 mA for signalling circuit

                                              Minimum switching voltage

                                              17 V for signalling circuit

                                              Non-overlap time

                                            • 1.5 ms on de-energisation between NC and NO contact
                                            • 1.5 ms on energisation between NC and NO contact
                                              • Compatibility code

                                                LC1D

                                                Protective treatment

                                                TH conforming to IEC 60068-2-30

                                                Pollution degree

                                                3

                                                Operating altitude

                                                3000 m without derating

                                                Fire resistance

                                                850 °C conforming to IEC 60695-2-1

                                                Flame retardance

                                                V1 conforming to UL 94

                                                Mechanical robustness

                                              • vibrations contactor open: 2 Gn, 5...300 Hz
                                              • vibrations contactor closed: 4 Gn, 5...300 Hz
                                              • shocks contactor open: 10 Gn for 11 ms
                                              • shocks contactor closed: 15 Gn for 11 ms
                                                • Unit Type of Package 1

                                                  PCE

                                                  Number of Units in Package 1

                                                  1

                                                  Package 1 Weight

                                                  1.066 kg

                                                  Package 1 Height

                                                  6.2 cm

                                                  Package 1 width

                                                  13.7 cm

                                                  Package 1 Length

                                                  15.2 cm

                                                  Unit Type of Package 2

                                                  S02

                                                  Number of Units in Package 2

                                                  9

                                                  Package 2 Weight

                                                  9.939 kg

                                                  Package 2 Height

                                                  15 cm

                                                  Package 2 width

                                                  30 cm

                                                  Package 2 Length

                                                  40 cm

                                                  WEEE

                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                  Halogen content performance

                                                  Halogen free plastic parts & cables product
                                                  Show all specifications

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • Product Brochures

                                                  • CAD Files and Packs

                                                  • Technical Data Catalogues

                                                  • Product Environmental

                                                  • End of Life Manual

                                                  • Installation Instruction

                                                  • Data Bulletin

                                                  • Declaration of Conformity

                                                  Frequently Asked Questions

                                                  hide show

                                                  What is the difference between a LC1D65A3U7 and LC1D65AU7?

                                                  The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                                                  see data sheets for comparrisons...
                                                  https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                                                  https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                                                  User-added image.................User-added image

                                                  Do the Everlink reversing contactors come with electrical interlocking?

                                                  Issue:
                                                  Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                  Product line:
                                                  Tesys D LC1D40A, LC1D50A, LC1D65A

                                                  Environment:
                                                  Everlink, all voltage codes

                                                  Cause:
                                                  Old D2 version offered an electrical interlock kit

                                                  Resolution:
                                                  The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                  Does LC1D65AB7 3P (3 NO) TeSys Model D contactor have a normally opened and normally closed auxiliary contact?

                                                  What is the part code for the contactor and overload that replaced the LR1D63359

                                                   The part codes are LC1D65A***  +  LRD365

                                                  What is the replacement code for the LC1D633Q?

                                                  The new code for this is LC1D65AU7.

                                                  What overload can be used with an LC1D65AU7?

                                                  You can use the Everlink range which is LRD313 - LRD365

                                                  What is the difference between the LC1D1506N7 and the LC1D150N7?

                                                  The LC1D1506N7 can accept 5X25mm Bars aswell as Lugs or ring terminals. The LC1D150N7 only accepts cable lugs upto 120mm2.

                                                  What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                  Issue:
                                                  Identifying maximum voltage of an LC1D contactor

                                                  Product Line:
                                                  TeSys D Contactors

                                                  Environment:
                                                  IEC contactors and starters used in North America

                                                  Cause:
                                                  n/a

                                                  Resolution:
                                                  IThe maximum voltage per UL and CSA is 600VAC. 
                                                   

                                                  What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                  Issue:
                                                  Identifying power terminal lug data for the D2 style contactors

                                                  Product Line:
                                                  Tesys D line contactors

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Power terminal lug data required

                                                  Resolution:
                                                  For contactors with screw clamp terminals:
                                                  stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                  stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                  solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                  How many wires can you install on the Power poles for the LC1D65A contactor?

                                                   Issue:
                                                  How many wires can you install on the Power poles for the LC1D65A contactor?

                                                  Product line:
                                                  Tesys D, Everlink

                                                  Environment:
                                                  LC1D40A LC1D50A LC1D65A

                                                  Cause:
                                                  Documentation not found

                                                  Resolution:
                                                  The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase.  1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2. 

                                                  Instruction bulletin attached.

                                                  What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                                                  17-25 Amps = LRD325
                                                  23-32 Amps =LRD332

                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Issue:​
                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Product Line:
                                                  Digest 177 Section 18 : Contactors and Starters, IEC

                                                  Environment:
                                                  North American Products

                                                  Resolution:
                                                  The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                  Voltage
                                                  3500m x 0.90
                                                  4000m x 0.80
                                                  4500m x 0.70
                                                  5000m x 0.60

                                                  Current
                                                  3500m x 0.92
                                                  4000m x 0.90
                                                  4500m x 0.88
                                                  5000m x 0.86

                                                  For example, an LC1D80 at 5000 meters:
                                                  - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                  - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                   
                                                  Show More