Package 1 Bare Product Quantity
1
Contactor application
resistive load
Utilisation category
AC-1
[Uc] control circuit voltage
48 V AC 50/60 Hz
Pole contact composition
2 NO + 2 NC
[Ith] conventional free air thermal current
80 A (at 60 °C) for power circuit
Irms rated making capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
- 640 A 40 °C - 10 s for power circuit
- 900 A 40 °C - 1 s for power circuit
- 110 A 40 °C - 10 min for power circuit
- 260 A 40 °C - 1 min for power circuit
Associated fuse rating
- 125 A gG at <= 690="" v="" coordination="" type="" 1="" for="" power="">=>
- 125 A gG at <= 690="" v="" coordination="" type="" 2="" for="" power="">=>
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
9.6 W AC-1
[Ui] rated insulation voltage
- power circuit: 600 V CSA certified
- power circuit: 600 V UL certified
- power circuit: 690 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Safety reliability level
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
AC at 50/60 Hz
Coil technology
without built-in suppressor module
Control circuit voltage limits
- 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
- 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
- 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
- 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
Inrush power in VA
- 140 VA 60 Hz cos phi 0.75 (at 20 °C)
- 160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA
- 13 VA 60 Hz cos phi 0.3 (at 20 °C)
- 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation
4...5 W at 50/60 Hz
Operating time
- 4...19 ms opening
- 12...26 ms closing
Maximum operating rate
3600 cyc/h 60 °C
Tightening torque
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
- power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Protective treatment
TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
- -40...60 °C
- 60...70 °C with derating
Operating altitude
0...3000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
- shocks contactor open (8 Gn for 11 ms)
- shocks contactor closed (10 Gn for 11 ms)
- vibrations contactor opened (2 Gn, 5...300 Hz)
- vibrations contactor closed (3 Gn, 5...300 Hz)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
1.465 kg
Unit Type of Package 2
S02
Number of Units in Package 2
5
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins